i When additional bus devices are added, the corresponding physical addresses can be
assigned twice. Delete the additional physical addresses – press the programming button
(9) for approx. 10 seconds – and assign them again.
5 Appendix
5.1 Technical data
Power over Ethernet supply
Power over Ethernet IEEE802.3af
Rated voltage DC 48 V
Power consumption max. 0.8 W
External supply
Rated voltage AC 12 ... 24 V SELV
Rated voltage DC 12 ... 30 V SELV
Power consumption max. 1.7 W
Connection of power supply Connection terminal
Ambient conditions
Ambient temperature -5 ... +45 °C
Storage/transport temperature -25 ... +70 °C
Relative humidity 5 ... 93 % (No moisture condensation)
Fitting width 36 mm / 2 modules
Weight approx. 100 g
Network communication
IP communication Ethernet 10BaseT
IP transmission rate 10 Mbit/s
IP connection mode RJ45 socket
Protocols ARP, ICMP, IGMP, UDP/IP, DHCP
KNXnet/IP Core, Tunneling, Device Management
KNX
KNX medium TP 1
Commissioning mode S mode
Rated voltage KNX DC 21 V ... 32 V SELV
Connection mode KNX Connection terminal
Current consumption KNX max. 10 mA
5.2 Troubleshooting
After installation of the ETS3 driver and enabling of the device as a communication
interface, an error message that the class is not known appears on the PC.
Microsoft
®
.Net Framework not installed.
Download and install Microsoft
®
.Net Framework from the Microsoft website.
5.3 Accessories
Power supply AC 24V~ Art.-No.: WSSV10
4/5
82571223
J:0082571223
06.04.2010
KNX IP interface