B.E.G. LUXOMAT Installation and Operating Instructions

Type
Installation and Operating Instructions
Installation and operating instructions
LUXOMAT
®
KNXnet/IP Interface Multicontrol
GB
1. General use
The KNXnet/IP Interface Multicontrol includes all the modules
required to implement time switching functions, trigger condi-
tions for defined events, event handling, logic functions and
the function of a real-time clock.
The following are available:
- Weekly switching programs (100 time switch entries)
- Event trigger / threshold switch (30 triggers)
- Event processing / scenes (200 events)
- Logic functions (30 logic functions)
- Real-time clock with battery backup
- Tunnel link to bus for visualisation
- Automatic time synchronisation via UDP time server
- Automatic adjustment to daylight-saving time
- IP address assignment via DHCP
In the device, up to 80 objects are defined with free data
type assignment from the following options:
- 1 bit (EIS 1)
- 1 byte without sign bit (EIS 14)
- 1 byte with sign bit (EIS 14)
- 2 bytes without sign bit (EIS 10)
- 2 bytes with sign bit (EIS 10)
- 2 bytes floating (EIS 5)
- 4 bytes without sign bit (EIS 11)
- 4 bytes with sign bit (EIS 11)
- 4 bytes floating (EIS 9)
7. Location and function of indication and control
elements
The device connections, as well as the learn button and pro-
gramming LED that are required during EIB startup, can only
be accessed in the distributor when the cover is removed.
The pushbuttons (Move, Prg/Set, ESC) and the 2 - line display
can be operated when the distributor cover is closed.
A1: 24 V bus terminal
A2: KNX bus terminal
A3: Ethernet RJ45 socket
A4: KNX programming LED
A5: KNX learn button
A6: Display 2 x 12 characters
A7: Move button
A8: Prg/Set button
A9: ESC button
A10: Ethernet Link LED
A11: Ethernet Activity LED
A12: Battery compartment
6. Technical data
Power supplies
24 V AC/DC; input range 12 .. 30V AC/DC
Additionally via EIB/KNX bus
Control elements
Learn button for switching between standard and
addressing mode
3 x pushbuttons (Move, Prg/Set, ESC) on the front for
setting the device (time and date) and indication of
the IP and MAC address
Indication elements
Red LED for indicating standard/addressing mode
Green LK LED for indicating the Ethernet link
Green LA LED for indicating communication on the
Ethernet link
LCD with 2 lines of 12 characters for indicating the
time and date
Connections
Bus line: EIB/KNX bus terminal (black/red)
Power supply: Bus terminal (yellow/white)
Ethernet 10 Mbps: RJ45 socket
Mechanical data
Casing: Plastic LEXAN UL-94-V0
Dimen sions for REG casing 4 div.:
Width: 70 mm
Height: 55 mm
Length: 86 mm
Weight: 150g
Installation: On standard 35mm DIN rail
Electrical safety
Pollution degree: 2
Degree of protection (according to EN 60529): IP20
Protection class (according to IEC 1140): I
Surge voltage category: III
Bus: Safety extra-low voltage SELV 24 V DC
EMC requirements
Meets EN 50081-1 and EN 50082-2,
EN 50090-2-2
Ambient conditions
Resistance to extreme climates: EN 50090-2-2,
Ambient conditions during operationb: 0°C to +45°C
Storage temperature: -25°C to +70°C
Relative humidity (no condensation): 5% to 93%
Approval
EIB/KNX registered
CE marking
In accordance with EMC directive (residential and functional
building), low-voltage directive
2. Device types and accessories
At present, the following device types are available from the
Interface product group:
KNXnet/IP Interface Multicontrol Part number: 90124
KNXnet/IP Interface Part number: 90125
KNXnet/IP Interface Web Part number: 90126
3. Scope of supply
The KNXnet/IP Interface Multicontrol is supplied as standard
with the following individual components:
Complete device including battery with EIB bus terminal
(black/red) and 24V supply bus terminal (yellow/white)
inserted
• Operating and installation instructions
4. Application programs
At present, the following application programs are available:
KNXInterface-90124, for function of the application program
see application program description
A4
A1
A3
A7
A8
A9
A6
A10
A11
A12
A5
A2
All defined objects can be used by all available modules.
This means that up to 80 objects can be selected for time
switching functions, as inputs for logic functions, as trigger
objects or as outputs for the event programs.
46
60
86
70
55
46
5. Installation notes
The device should only be installed and started up by an
approved electrical engineer.
Observe the applicable safety and accident prevention
regulations.
The device is designed for fixed installation indoors in dry
conditions.
When connecting the device, ensure it has been discon-
nected from the power supply.
The device must not be opened. Faulty devices should be
returned to the manufacturer.
When planning and erecting electrical systems, observe
the specifications and regulations of the relevant country.
8. Display
The display shows the current time. Press to the Move button
display the additional information:
Time:
12:45 Mo
05.Jun.2004
IP address:
IP: 192.168.
100.1
Mac address:
MAC: 00-05-64
00-0A-22
9. Setting the time
Hold down the Prg/Set button to change the display to
programming mode. The following appears:
Hour ?
12:45
The Move button can now be used to set the desired hour.
Press the Prg/Set button to confirm the set value and proceed
to the next input window.
Minute ?
12:45
Day ?
05.Jun.2004
Month ?
05.Jun.2004
Year ?
05.Jun.2004
Return ?
At the end of the input cycle, press Return to return to the
normal display. Programming can be exited at any time using
the ESC button.
Please note that when parameterising a time server via ETS,
the manual setting of the time is overwritten by an external
signal from the time server. As soon as a time server has been
configured in the ETS, it has priority.
10. Error indication in the display
The KNXnet/IP Interface Multicontrol includes an automatic
battery monitoring function. Every 24 hours, the battery is used
briefly in order to evaluate the service life and status of the
battery. If the voltage under this load falls below a limit value,
this is indicated both in the display and as an event on the
EIB/KNX bus.
Battery test not OK display via B
12:45 Mo B
05.Jun.2004
When this message is displayed the
battery should be replaced.
The KNXnet/IP Interface Multicontrol displays the load status
of the application for information. After an ETS download, all
application parameters that were set via the web configuration
tool are deleted. This status is indicated by an “E” (empty) in
the display.
12:45 Mo E
05.Jun.2004
11. Replacing the battery
The KNXnet/IP Interface Multicontrol has a 1/2 AA 3.6 V
lithium battery. Under normal operating conditions, the battery
has a service life of up to 2 years. However, if it does have
to be replaced, the battery cover can be opened by inserting
a screwdriver in the notches provided. Pull the battery out of
the battery compartment and insert a new battery. Ensure the
correct polarity.
MAN 6688040411–1