Arcteq AQ-T256 User manual

Type
User manual
AQ-T256
Transformer protection IED
Instruction manual
Table of contents
6
6
6
7
8
9
9
9
10
11
11
12
12
22
24
25
25
39
44
48
53
57
71
78
82
90
127
132
138
151
151
157
162
164
168
168
176
183
187
191
196
199
199
199
199
200
201
203
205
205
205
206
206
206
209
209
1. Manual revision notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1. Version 2 revision notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2. Version 1 revisionnotes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4. IED user interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1. Panel structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.1. AQ 250 series local panel structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2. User level password conguration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5. Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1. Functions included in AQ-T256 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2. Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.1. Current measurement and scaling in differential application . . . . . . . . . . . . . . . . . .
5.2.2. Frequency tracking and scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3. General menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4. Protection functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.1. General properties of a protection function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.2. Non-directional overcurrent I> (50/51) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.3. Non-directional earth fault I0> (50N/51N) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.4. Current unbalance I2> (46) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.5. Harmonic overcurrent Ih> (50H/51H/68H) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.6. Circuit breaker failure protection CBFP (50BF) . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.7. Restricted earth fault / cable end differential (REF) I0D> (87N) . . . . . . . . . . . . . . . .
5.4.8. Transformer status monitoring (TRF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.9. Transformer thermal overload protection TT> (49TR) . . . . . . . . . . . . . . . . . . . . . . .
5.4.10. Transformer differential Idb> Idi> I0dhv> I0dLv> (87T,87N) . . . . . . . . . . . . . . . . . .
5.4.11. Resistance temperature detectors (Modbus IO) (RTD) (49T) . . . . . . . . . . . . . . .
5.4.12. Arc fault protection IArc>/I0Arc>(50Arc/50NArc) . . . . . . . . . . . . . . . . . . . . . . . .
5.4.13. Programmable stage PGx >/< (99) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5.1. Setting group selection (SGS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5.2. Object control and monitoring (OBJ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5.3. Indicator object monitoring (CIN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5.4. mA Output control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6.1. Current transformer supervision (CTS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6.2. Disturbance recorder (DR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6.3. Measurement recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6.4. Circuit breaker wear-monitor (CBW) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6.5. Total harmonic distortion monitor (THD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6.6. Measurement value recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6. System integration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.1. NTP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.2. ModbusTCP and ModbusRTU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.3. ModbusIO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.4. IEC 61850 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.5. GOOSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.6. IEC 103 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.7. DNP3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.8. IEC 101/104 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.9. SPA protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7. Applications and connection examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AQ-T256
Instruction manual
Version: 2.00
1 © Arcteq Relays Ltd
211
212
216
216
218
220
221
223
224
225
226
228
229
229
232
232
232
232
233
233
233
234
235
235
236
236
236
237
238
238
238
239
239
239
239
239
240
241
242
243
243
244
244
244
245
246
246
246
247
247
247
248
248
248
249
251
253
8. Construction and installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.1. Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.1.1. Current measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.1.2. Frequency measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.2. CPU & Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.2.1. Auxiliary voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.2.2. CPU communication ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.2.3. CPU Binary inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.2.4. CPU Binary outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.3. Option cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.3.1. Binaryinput module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.3.2. Binary output module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.3.3. Arc protection module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.3.4. mAout & mAin module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.3.5. RTD & mA input module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.3.6. RS232 & Serial ber communication module . . . . . . . . . . . . . . . . . . . . . .
9.1.3.7. Double LC100Mb Ethernet module(Redundant) . . . . . . . . . . . . . . . . . . .
9.1.4. Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2.1. Protection functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2.1.1. Non-directional overcurrent (50/51) I> . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2.1.2. Non-directional earth fault (50N/51N) I0> . . . . . . . . . . . . . . . . . . . . . . . .
9.2.1.3. Current unbalance (46/46R/46L) I2> . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2.1.4. Harmonic overcurrent (50H/51H, 68) Ih> . . . . . . . . . . . . . . . . . . . . . . . .
9.2.1.5. Circuit breaker failure protection (50BF/52BF) CBFP . . . . . . . . . . . . . . .
9.2.1.6. Restricted earth fault / Cable end differential (87N) Iod> . . . . . . . . . . . . .
9.2.1.7. Transformer thermal overload (49T) T> . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2.1.8. Resistance temperature detector alarm (49RTD) T> . . . . . . . . . . . . . . . .
9.2.1.9. Transformer monitoring function (TRF) . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2.1.10. Transformer differential (87T,87R) Idb>, Idi>,HV Iod>, LV Iod> . . . . . . .
9.2.1.11. Arc protection (50ARC/50NARC) IARC> I0ARC> (option) . . . . . . . . . . .
9.2.2. Control functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2.2.1. Setting group selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2.2.2. Object control (OBJ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2.3. Monitoring functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2.3.1. Current transformer supervision (CTS) . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2.3.2. Disturbance recorder (DR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2.3.3. Circuit breaker wear monitor (CBW) . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2.3.4. Total harmonic distortion (THD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10. Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11. Contact and reference information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AQ-T256
Instruction manual
Version: 2.00
© Arcteq Relays Ltd 2
Disclaimer
Please read these instructions carefully before using the equipment or taking any other actions with
respect to the equipment. Only trained and qualied persons are allowed to perform installation,
operation, service or maintenance of the equipment. Such qualied persons have the responsibility to
take all appropriate measures, including e.g. use of authentication, encryption, anti-virus programs,
safe switching programs etc. necessary to ensure a safe and secure environment and usability of the
equipment. The warranty granted to the equipment remains in force only provided that the instructions
contained in this document have been strictly complied with.
Nothing contained in this document shall increase the liability or extend the warranty obligations of the
manufacturer Arcteq Relays Ltd. The manufacturer expressly disclaims any and all liability for any
damages and/or losses caused due to a failure to comply with the instructions contained herein or
caused by persons who do not full the aforementioned requirements. Furthermore, the manufacturer
shall not be liable for possible errors in this document. 
Please note that you must always comply with applicable local legislation and regulations. The
manufacturer gives no warranties that the content of this document is in all respects in line with local
laws and regulations and assumes no liability for such possible deviations.
You are advised to notify the manufacturer in case you become aware of any errors in this document or
of defects in the equipment.
The manufacturer reserves the right to update or amend this document at any time.
AQ-T256
Instruction manual
Version: 2.00
3 © Arcteq Relays Ltd
Copyright
Copyright © Arcteq Relays Ltd. 2018. All rights reserved.
AQ-T256
Instruction manual
Version: 2.00
© Arcteq Relays Ltd 4
1. Manual revision notes
1.1. Version 2 revision notes
Revision 2.00
Date 6.6.2019
Changes
- New more consistent look.
- Improved descriptions generally in many chapters.
- Improved readability of a lot of drawings and images.
- Updated protections included included in every IED manual.
- Every protection IED type now has connection drawing, application example drawingwith function block diagram
and application example with wiring.
- Added current measurement side selection description to functions with such feature.
- Added General-menu description.
1.2. Version 1 revisionnotes
Revision 1.00
Date 13.4.2016
Changes - The rst revision for AQ-T256, T257 and T259 IEDs.
Revision 1.01
Date 10.2.2017
Changes
- Order code updated
- Added programmable stage description
Revision 1.02
Date 9.1.2018
Changes
- Measurement value recorder description
- ZCT connection added to current measurement description
- Internal harmonics blocking to I>,I0> function descriptions
- Non-standard delay curves added
- Event lists revised on several functions
- RTD&mA card description improvements
- Ring-lug CT card option description added
- New U> and U< function measurement modes documented
- Order code revised
Revision 1.03
Date 14.8.2018
Changes
- Added mA output option card description and ordercode
- Added HMI display technical data
AQ-T256
Instruction manual
Version: 2.00
5 © Arcteq Relays Ltd
2. Abbreviations
CB – Circuit breaker
CBFP – Circuit breaker failure protection
CT – Current transformer
CPU – Central processing unit
EMC – Electromagnetic compatibility
HMI – Human machine interface
HW – Hardware
IED – Intelligent electronic device
IO – Input output 
LED – Light emitting diode
LV – Low voltage
MV – Medium voltage
NC – Normally closed
NO – Normally open
RMS – Root mean square
SF – System failure
TMS – Time multiplier setting
TRMS – True root mean square
VAC – Voltage alternating current
VDC – Voltage direct current
SW – Software
uP - Microprocessor
AQ-T256
Instruction manual
Version: 2.00
© Arcteq Relays Ltd 6
3. General
AQ-T256 Transformer Protection IEDisa members of the AQ-200 product line. The AQ-200 protection
product line in respect of hardware and software is a modular concept. The hardware modules are
assembled and congured according to the application IO requirements and the software determines
the available functions. This manual describes the specic applications of the AQ-T256Transformer
Protection IEDs. For other AQ-200 series products please consult corresponding device manuals.
AQ-T256
Instruction manual
Version: 2.00
7 © Arcteq Relays Ltd
4. IED user interface
4.1. Panel structure
AQ 200 series IED user interface section is divided into hardware- and software user interface
sections. Software interface is divided into local panel conguration and programming by using
AQtivate 200 freeware software suite.
4.1.1. AQ 250 series local panel structure
AQ 200 series IED have multiple LEDs, control buttons, function buttons and local RJ-45 Ethernet port
for conguration on front as a default. On rear each unit is equipped with RS-485 serial interface and
RJ-45 Ethernet interface options as a standard. See list below.
Figure. 4.1.1. - 1. Local panel structure.
4 default LEDs for free conguration: Power, Error, Start and Trip.
16 freely congurable LEDs with programmable legend texts.
3 object control buttons: Choose the controllable object with Ctrl –button, control breaker with
0- and I push buttons.
L/R push button for local remote control.
7 Navigation buttons for IED local programming and a button for password activation.
12 freely congurable function buttons.
RJ-45 Ethernet port for IED conguration.
Used views are freely congurable with buttons for changing settings groups or controlling the relays
logic in general. Object status (Circuit breaker/Disconnector) can be displayed on the screen. All
measured and calculated values (currents, voltages, power, energy, frequency etc.) can be shown in
the screen.
AQ-T256
Instruction manual
Version: 2.00
© Arcteq Relays Ltd 8
4.2. User level password conguration
As a factory default IEDs do not have any user levels locked behind passwords. In order to activate
different user levels click the IED HMI lock button and set the desired passwords for different user
levels.
NOTE: Passwords can be set only at local HMI.
In the HMI the user level currently in use is indicated in the upper right corner with stars.
Different user levels and the indicators are:
SUPERUSER (***) = full access including congurations
CONFIGURATOR (**) = access to all settings
OPERATOR (*) = access to limited settings and control
USER ( - ) = view only
You can set a new password for the user level by selecting the key icon next to the user level. After this
you can lock the user level by pressing return key while the lock is selected. If you need to change the
password you can select the key icon again and give a new password. Please note that in order to do
this the user level must be unlocked.
The required access level required to change a parameter is indicated with star (*) symbol if such is
required. As a general rule the access levels are divided as follows:
User:
Can view any menus and settings but cannot change any settings nor operate breakers
or other equipment.
Operator:
Can view any menus and settings but cannot change any settings BUT can operate
breakers or other equipment.
Congurator:
Can change most settings like basic protection pick-up levels or time delays,
breaker control functions, signal descriptions etc. Can operate breakers or other equipment.
Super user:
Access to change any setting and can operate breakers or other equipment.
AQ-T256
Instruction manual
Version: 2.00
9 © Arcteq Relays Ltd
5. Functions
5.1. Functions included in AQ-T256
This chapter presents the functions of AQ-T256 Transformer Protection IED. AQ-T256includes
following functions and amounts of instances of the functions.
Table. 5.1. - 1. Protection functions of AQ-T256
Name IEC ANSI Description
NOC1
NOC2
NOC3
NOC4
I>
I>>
I>>>
I>>>>
50/51 Overcurrent protection (4 stages)
NEF1
NEF2
NEF3
NEF4
I0>
I0>>
I0>>>
I0>>>>
50N/51N Residual overcurrent protection (4 stages)
CUB1
CUB2
CUB3
CUB4
I2>
I2>>
I2>>>
I2>>>>
46/46R/46L
Negative sequence overcurrent / phase current reversal / unbalance protection (4
stages)
HOC1
HOC2
HOC3
HOC4
Ih>
Ih>>
Ih>>>
Ih>>>>
50h/51h/68h
Detection and blocking or tripping from selectable 2nd, 3rd, 4th, 5th, 7th, 9th, 11th,
13th, 15th, 17th, 19th harmonic. Phase currents and residual currents separate
stages. (4 stages)
CBF1 CBFP 50BF/52BF Breaker failure protection
DIF1
Idb>
Idi>
87T Transformer differential function. Biased and non-biased stages
REF1
REF2
I0d>
I0d>
87N Low or high impedance restricted earth fault, cable end differential protection
TOLT1 TT> 49L Transformer thermal overload protection
TRF TRF - Transformer status monitoring function
RTD1 RTD 49T Resistance Temperature Detectors for temperature measurements
PGS1 PGx >/< 99 Programmable stage
ARC1 IArc>/I0Arc> 50Arc/50NArc Arc protection (Option)
Table. 5.1. - 2. Control functions of AQ-T256
Name IEC ANSI Description
SG - - Set group settings
OBJ - - Object control
Table. 5.1. - 3. Monitoring functions of AQ-T256
Name IEC ANSI Description
CTS - - Current transformer supervision
DR - - Disturbance recorder
MR - - Measurement recorder
CBW - - Circuit breaker wear monitor
THD - - Total harmonic distortion
VREC - - Measurement value recorder
AQ-T256
Instruction manual
Version: 2.00
© Arcteq Relays Ltd 10
5.2. Measurements
5.2.1. Current measurement and scaling in differential application
Current measurement module (CT-module) is used for measuring the currents from current
transformers and processing the measured currents to measurement database and for use of
measurement- and protection functions. For the measurements to be correct it is essential to
understand the concept of current measurements.
Figure. 5.2.1. - 2. Current measurement terminology
PRI: Primary current, the current which flows in the primary circuit and through primary side of the
current transformer.
SEC: Secondary current, the current which the current transformer transforms according to its ratios.
This current is measured by the protection IED.
NOM: Nominal primary current of the protected transformer. Nominal current differs on the HV and LV
side according to the transformer voltage ratio. Nominal current is calculated based on transformers
MVA and nominal voltage on each winding.
For the measurements to be correct it needs to be made sure that the measurement signals are
connected to correct inputs, current direction is connected correctly and the scaling is set correctly.
AQ-T256
Instruction manual
Version: 2.00
11 © Arcteq Relays Ltd
For scaling, the relay calculates scaling factors based onto the set CT primary, secondary and nominal
current values. Relay measures secondary current which in this case mean the current output from the
current transformer which is installed into the primary circuit of the application. In order the relay to
“know” primary and per unit values it needs to be told the current transformer rated primary and
secondary currents. In case of a power transformer the protected unit nominal current in both windings
is calculated based on given nominal power (MVA) and nominal voltage (V), only when the nominal
current is known the settings can be per unitized to apparatus nominal. By knowing the transformer
nominal current it makes the unit protection a lot easier and straight forward. In modern protection
devices this scaling calculation is done internally after the current transformer primary, secondary and
machine nominal currents are known.
Figure. 5.2.1. - 3. Nominal current calculation in differential protection relay
Normally the primary current ratings for phase current transformers are from 10A to thousands of
Amps and their decimal multiples, while normal secondary current ratings are 1 and 5A. Other, non-
standard ratings can be directly connected too since the scaling settings are flexible in large ranges.
For ring core current transformers the ratings may be different. Ring core current transformers are
commonly used for sensitive earth fault protection and their rated secondary may be as low as 0.2 A in
some cases.
In following chapter is given example for the scaling of the relay measurements to the example current
transformers and nominal load.
CT scaling example (application 1)
The connection of CTs to the IED measurement inputs and the ratings of the current transformers and
transformer nominal current are as in following gure.
AQ-T256
Instruction manual
Version: 2.00
© Arcteq Relays Ltd 12
Figure. 5.2.1. - 4. Example connection (S1 always to odd connector regardless the CT direction). CT direction is selected under
differential function
Please see the above gure, as a result of the direction of the CTs and according to the fact that P1/S1
side of the CTs are always wired to the odd inputs of the relay CT module, the “Differential calculation
mode” under the
Protection
TrafoModule
Idx> [87T,87N]
Settings
has to be set as “Subtract”.
Due to this the direction of measured currents are checked correctly from the relay perspective.
Initial data of the connection and the ratings are presented in following table.
AQ-T256
Instruction manual
Version: 2.00
13 © Arcteq Relays Ltd
Table. 5.2.1. - 4. Initial data from example connection.
High voltage side CT:
CT primary 800A
CT secondary 1A
HV-side nominal current:
669A
Ring core CT in Input I02:
3I0CT primary 250A
3I0CT secondary 1A
Low voltage side CT:
CT primary 8000A
CT secondary 1A
LV-side nominal current:
5888A
Both CTs are pointing through the transformer (HV-S2 and LV-S2 are pointing to same direction).
Nominal current for both high voltage and low voltage side of the protected transformer are calculated
based on given values under the “Transformer Characteristics” menu, which is located under the
protection main menu. CT module 1 and 2 ratio can be set directly under the same menu, or optionally
under
Measurement
Transformers
–menu. Per unit (PU) scaling is automatically set as xed to
“Object In p.u.” in all machine protection relays and it cannot be changed.
Figure. 5.2.1. - 5. Phase current transformer scaling to machine nominal.
As it can be seen in the gure above, the high voltage side nominal current is calculated to be 669.2A
and the low voltage side current is 5888.97A. These nominal currents are calculated as follow:
Per unit values for high –and low voltage side nominal currents can be calculated as shown below:
AQ-T256
Instruction manual
Version: 2.00
© Arcteq Relays Ltd 14
To multiply the per unit value with Phase CT secondary side current, it is possible to get the nominal
secondary current of transformer as Amperes. This current can be used when the unit is
commissioned and the directions of CTs are checked. See an example calculation below:
In case coarse residual current (I01) input is used for CT sum (Holmgren) input then it should be set to
phase current CT ratings 100/5A.
Figure. 5.2.1. - 6. Residual current I01 scaling to summing connection.
For the sensitive residual current (I02) measurement the CT primary and secondary currents are set
directly as rated currents 250/1A.
Figure. 5.2.1. - 7. Residual current I02 scaling to ring core CT input.
CT scaling example (application 2)
The connection of CTs to the IED measurement inputs and the ratings of the current transformers and
transformer nominal current are as in following gure.
AQ-T256
Instruction manual
Version: 2.00
15 © Arcteq Relays Ltd
Figure. 5.2.1. - 8. Example connection (S1 always to odd connector regardless the CT direction). CT direction is selected under
differential function
Please see the above gure, as a result of the direction of the CTs and according to the fact that P1/S1
side of the CTs are always wired to the odd inputs of the relay CT module, the “Differential calculation
mode” under the
Protection
TrafoModule
Idx> [87T,87N]
Settings
has to be set as “Add”. The
difference to the rst application is that here the CTs are pointing towards the protected object instead
of pointing through it.
Initial data of the connection and the ratings are presented in following table.
Table. 5.2.1. - 5. Initial data from example connection.
Machine nominal power: 153MVA
Machine high voltage side nominal amplitude: 132kV
Machine low voltage side nominal amplitude: 15kV
AQ-T256
Instruction manual
Version: 2.00
© Arcteq Relays Ltd 16
High voltage side CT:
CT primary 800A
CT secondary 2A
HV-side nominal current:
669A
Ring core CT in Input I02:
3I0CT primary 250A
3I0CT secondary 1A
Low voltage side CT:
CT primary 8000A
CT secondary 5A
LV-side nominal current:
5888A
Both CTs are pointing through the transformer (HV-S2 and LV-S2 are pointing to same direction).
The nominal currents on high voltage and low voltage side are exactly the same as in application 1.
The only difference is that the secondary current level of the CTs have been changed to 2A on high
voltage side and to 5A on low voltage side. Nominal currents are still calculated the same way:
Per unit values for high –and low voltage side nominal currents can be calculated as shown below:
To multiply the per unit value with Phase CT secondary side current, it is possible to get the nominal
secondary current of transformer as Amperes. This current can be used when the unit is
commissioned and the directions of CTs are checked. In application 2 it is necessary to inject higher
amplitudes to the CTs via secondary injection tool to reach the nominal currents. See an example
calculation below:
Settings
Table. 5.2.1. - 6. Settings of the Phase CT scaling
Name Range Step Default Description
Scale
meas to In
0:CT
nom
p.u.
1:Object
In p.u.
-
0:CT
nom
p.u.
Selection of the IED per unit system scaling reference, either the set phase
current CT primary or protected object nominal current. (NOT APPLICABLE IN
MACHINE PROTECTION).
Phase CT
primary
1…
5000.0A
0.1A 100.0A Rated primary current of the CT in amperes.
Phase CT
secondary
0.2…
10.0A
0.1A 5.0A Rated secondary current of the CT in amperes.
AQ-T256
Instruction manual
Version: 2.00
17 © Arcteq Relays Ltd
Nominal
current In
1…
5000A
0.01A 100.00A
Protected object nominal current in amperes. (This setting is visible if “Scale meas
to In” setting is set to “Object In p.u.”)
IL1
Polarity
0:-
1:Invert
- 0:-
IL1 (rst current) measurement channel polarity (direction) selection. Default
setting is that positive current flow is from connector 1 to connector 2 and the
secondary currents starpoint is towards line.
IL2
Polarity
0:-
1:Invert
- 0:-
IL2 (second current) measurement channel polarity (direction) selection. Default
setting is that positive current flow is from connector 3 to connector 4 and the
secondary currents starpoint is towards line.
IL3
Polarity
0:-
1:Invert
- 0:-
IL3 (third current) measurement channel polarity (direction) selection. Default
setting is that positive current flow is from connector 5 to connector 6 and the
secondary currents starpoint is towards line.
CT
scaling
factor P/S
- - -
IED feedback value, this is the calculated scaling factor for primary /secondary
current ratio
CT
scaling
factor
NOM
- - -
IED feedback value, this is the calculated ratio in between of set primary and
nominal currents.
Ipu
scaling
primary
- - - IED feedback value, scaling factor from p.u. value to primary current.
Ipu
scaling
secondary
- - - IED feedback value, scaling factor from p.u. value to secondary current.
Table. 5.2.1. - 7. Settings of the residual I01 CT scaling
Name Range Step Default Description
I01 CT
primary
1…
5000.0A
0.1A 100.0A Rated primary current of the CT in amperes.
I01 CT
secondary
0.2…
10.0A
0.1A 5.0A Rated secondary current of the CT in amperes.
I01 Polarity
0:-
1:Invert
- 0:-
I01 (coarse residual) measurement channel polarity (direction) selection. Default
setting is that positive current flow is from connector 7 to connector 8.
CT scaling
factor P/S
- - -
IED feedback value, this is the calculated scaling factor for primary /secondary
current ratio
Table. 5.2.1. - 8. Settings of the residual I02 CT scaling
Name Range Step Default Description
I02 CT
primary
1…
5000.0A
0.1A 100.0A Rated primary current of the CT in amperes.
I02 CT
secondary
0.1…
10.0A
0.1A 5.0A Rated secondary current of the CT in amperes.
I02 Polarity
0:-
1:Invert
- 0:-
I02 (ne residual) measurement channel polarity (direction) selection. Default
setting is that positive current flow is from connector 9 to connector 10.
CT scaling
factor P/S
- - -
IED feedback value, this is the calculated scaling factor for primary /secondary
current ratio
Measurements
Following measurements are available from the measured current channels.
Table. 5.2.1. - 9. Per unit phase current measurements
Name Range Step Description
AQ-T256
Instruction manual
Version: 2.00
© Arcteq Relays Ltd 18
Phase current ILx
0.00…
1250.0xIn
0.01xIn
Per unit measurement from each phase current channel fundamental
frequency RMS current.
Phase current ILx
TRMS
0.00…
1250.0xIn
0.01xIn
Per unit measurement from each current channel TRMS current including
harmonics up to 31
st
.
Peak to peak
current ILx
0.00…
500.0xIn
0.01xIn
Per unit measurement peak to peak current from each phase current
measurement channel.
Table. 5.2.1. - 10. Primary phase current measurements
Name Range Step Description
Primary Phase
current ILx
0.00…
1000000.0A
0.01A
Primary measurement from each phase current channel fundamental
frequency RMS current.
Phase current ILx
TRMS pri
0.00…
1000000.0A
0.01A
Primary measurement from each current channel TRMS current including
harmonics up to 31
st
.
Table. 5.2.1. - 11. Secondary phase current measurements
Name Range Step Description
Secondary Phase
current ILx
0.00…
300.0A
0.01A
Secondary measurement from each phase current channel fundamental
frequency RMS current.
Phase current ILx
TRMS sec
0.00…
300.0A
0.01A
Secondary measurement from each current channel TRMS current including
harmonics up to 31
st
.
Table. 5.2.1. - 12. Phase current angles measurements
Name Range Step Description
Phase angle ILx 0.00…360.00deg 0.01deg Phase angle measurement of the three phase current inputs.
Table. 5.2.1. - 13. Per unit residual current measurements
Name Range Step Description
Residual current
I01
0.00…
1250.0xIn
0.01xIn
Per unit measurement from residual current channel I01 fundamental
frequency RMS current.
Residual current
I02
0.00…
1250.0xIn
0.01xIn
Per unit measurement from residual current channel I02 fundamental
frequency RMS current.
Calculated I0
0.00…
1250.0xIn
0.01xIn
Per unit measurement from calculated I0 current fundamental frequency RMS
current.
Phase current I01
TRMS
0.00…
1250.0xIn
0.01xIn
Per unit measurement from I01 residual current channel TRMS current
including harmonics up to 31
st
.
Phase current I02
TRMS
0.00…
1250.0xIn
0.01xIn
Per unit measurement from I02 residual current channel TRMS current
including harmonics up to 31
st
.
Peak to peak
current I01
0.00…
500.0xIn
0.01xIn
Per unit measurement peak to peak current from I01 residual current
measurement channel.
Peak to peak
current I02
0.00…
500.0xIn
0.01xIn
Per unit measurement peak to peak current from I02 residual current
measurement channel.
Table. 5.2.1. - 14. Primary residual current measurements
Name Range Step Description
Primary residual
current I01
0.00…
1000000.0A
0.01A
Primary measurement from residual current channel I01 fundamental
frequency RMS current.
Primary residual
current I02
0.00…
1000000.0A
0.01A
Primary measurement from residual current channel I02 fundamental
frequency RMS current.
AQ-T256
Instruction manual
Version: 2.00
19 © Arcteq Relays Ltd
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253

Arcteq AQ-T256 User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI