Configurable Parameters
Table 1 defines the network parameters of the Modbus Communication Module that are available via
the unit controller keypad/display. At a minimum, you must set the network address (ident number),
and verify the correct baud rate before establishing network communication between the unit
controller and the BAS. Change remaining parameters as required for your network.
Note: To save changes to these parameters, select “Apply Changes” under Modbus Setup. For
additional information on using the keypad/display, refer to the appropriate MicroTech III
Chiller Unit Controller Operation Manual.
Table 1. Network Configuration Menu
Parameter Value (Range)/Definition Initial Value/Note
Apply Changes No-Yes/ Setting this to yes will
cycle power to the controller to
allow the network setup changes to
take place.
No
Address
1
1-247/The Modbus Address of the
communication module
1/This must be unique
throughout the entire
Modbus network.
Baud Rate
1
9600-19200-38400-76800/ Data
transfer speed (bps).
38400
Parity
Even(0), Odd(1), None(2)/ Defines
the parity that is used on the bus.
None/ This must also be
identical for all nodes on the
bus.
Two Stop Bits
No-Yes/ This defines the number of
stop bits.
Yes/ If No is set, one stop bit is
used, otherwise two are used.
This value must also be
coordinated with the other bus
nodes.
Load Resistor No-Yes/ Switches on or off the
Termination Resistor.
No/Set this to Yes, if this unit
is the first or last slave on the
segment. If an external
terminating resistor is used, set
this parameter to No.
Response Dly 0-30000ms/ Response Delay. When
a request is received, the response is
delayed by this many milliseconds
to avoid over-run of the master.
0 milliseconds/Normally it is
not needed to change this
delay. It is just used if the
Master is too slow.
Com LED Tmout
0-3600/If the master does not poll
within this time, then the BUS LED
will turn red.
3Sec/ If this is set to 0, the
BUS LED is always green and
cannot be used to indicate
communications to the master.
Modbus BSP Basic Support Package Version x.xx
1
Parameters that require configuration for proper network communication.
Note: If unit controller application software requires uploading in the field, the network
configuration parameters revert to their default values. Please contact the Technical
Response Center at 877-349-7782 for assistance with upgrading unit controller application
software.