ADJUSTMENTS
The Time Delay and PIR Sensitivity
adjustments are located on the back of the
FS‑755 under a removable cover.
The sensors are factory preset for maximum
sensitivity and a 30 second time delay, which
is optimized for use with LED lighting.
For fluorescent loads we recommend at
least 5 minutes for the time delay.
TEST OCCUPANCY SENSOR
Important, there is an initial warm‑up period:
It may take up to a minute for the sensor to warm‑up during the
initial power‑up. During this time, the sensor does not detect
motion.
• If the load is ON when power is applied, it turns OFF within
25 seconds. Approximately 35 seconds after the load turns
off, the sensor starts detecting motion and controlling the
load.
• If the load is OFF when power is applied, the load will stay
off for 60 seconds before the sensor starts detecting and
controlling the load.
1. Set the time delay to minimum (this is the factory preset).
2. Move out of the sensor’s view. Lights should turn off after 30
seconds.
3. Walk down the aisle. When the first sensor detects motion the
green LED in the sensor will flash and the first cooler’s lights
should turn on.
4. Proceed down the aisle, the second cooler’s sensor should
detect you, the green LED in the sensor will flash and the
second cooler’s lights should turn on.
5. This process should continue down the rest of the aisle. As
you walk down the aisle, the cooler lights should progressively
turn on prior to you walking in front of that cooler, turning on
one at a time as you proceed down the aisle.
6. Repeat this process from the opposite end of the aisle. No
matter which direction you approach the system should
function in this way.
TROUBLESHOOTING
The green motion detection LED is located on the front of the
sensor, under the cover plate. Remove the cover plate when
troubleshooting.
Lights will not turn ON:
•SensorLEDdoesnotflashwhenmotioniswithinthecoverage
zone of the detector:
1. Check that the circuit breaker has been turned back on.
2. Check all sensor wire connections.
3. Check for line voltage input to the sensor.
- If line voltage is present, try a different sensor.
- If line voltage is not present, check line wiring.
•SensorLEDdoesflashwhenmotioniswithinthecoverage
zone of the detector:
1. Check all wire connections and verify the load wires are
tightly secured.
2. Check the light switch in the cooler.
3. Check for line voltage on the red load wire.
- If line voltage is present, the sensor is functioning
properly.
- If line voltage is not present, try a different sensor.
* If lights still do not turn ON, call 866‑588‑5473 for technical
support.
Lights will not turn OFF:
The time delay on the sensor can be set from 30 seconds to 20
minutes. Ensure that the time delay is set to the desired delay
and that there is no movement within the sensor’s view for that
time period. To quickly test the unit for proper operation, set
the time delay to 30 seconds and move out of the sensor’s view.
Lights should turn off after 30 seconds.
•IfgreenLEDflasheswhennomotioniswithinthesensor’s
view and the lights do not turn off:
‑ The sensor may be experiencing activations from outside
the controlled area or from some type of interference. Turn
the sensitivity to minimum and allow the sensor to time out.
If the lights turn off, the sensor is working properly.
•IfgreenLEDdoesnotflashwhenmotioniswithinthe
sensor’s view and the lights do not turn off:
1. Check all sensor wire connections.
- If the neutral is not connected the LED will not flash
and the relay will not change state.
2. Check for line voltage input to the sensor.
- If line voltage is present and wiring is correct, try a
different sensor.
- If line voltage is not present, check line wiring.
* If lights still do not turn off, call 866‑588‑5473 for technical
support.
=ON =OFF
234
Time Delay
30 second
5 minutes
10 minutes
20 minutes
1
Sensitivity
Minimum
Maximum
Call 866.588.5473 for Technical Support
www.wattstopper.com