Eaton PXMP Series Quick start guide

  • Hello! I am an AI chatbot trained to assist you with the Eaton PXMP Series Quick start guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
For detailed information concerning the operation and features
available in the PXMP meter display - 6” color touchscreen (PXMP-
DISP-6-XV), please refer to PXMP meter color touchscreen display
Features (IB150022EN) available on the Eaton website (www.eaton.
com/meters).
Figure 1. Color touchscreen display for PXMP series meter.
Figure 2. PXMP-DISP-6 cut out dimensions.
Effective June 2019
Technical Data TD150030EN
PXMP display quickstart guide
Installation
1. Disconnect and lockout all power to the enclosure.
2. Inspect the enclosure door to determine the best mounting loca-
tion for the PXMP display.
ote:N A minimum clearance of 1.18 in. (30.0 mm) must be maintained
between the ventilation holes in the back of the display and any other
component within the enclosure.
3. Use the mounting template to mark the cutout area on the
enclosure door. Cut out the marked area.
4. Insure proper gasket placement on the PXMP display.
5. Insert PXMP display through the cutout.
6. Fit the supplied threaded pins in the retaining brackets. The tips
of the threaded pins must point towards the wider ends of the
retaining brackets. Clip on the retaining brackets in the recesses
provided for them on the device.
7. Check for proper alignment of the PXMP meter color touch-
screen display. Then fix the device by torquing the threaded pins
to 0.1 Nm (0.86 lb-in) with a 2mm hexagonal screwdriver. The
front of the display should be flush with the surface of the con-
trol cabinet at the fixing points.
Technical Data TD150030EN
Effective June 2019
PXMP display quickstart guide
Eaton
Electrical Sector
1000 Eaton Boulevard
Cleveland, OH 44122
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2019 Eaton
All Rights Reserved
Printed in USA
Publication No. TD150030EN / TBG001463
June 2019
Eaton is a registered trademark.
All other trademarks are property of their
respective owners.
Figure 3. Mounting the PXMP display.
Connections
To use the PXMP display, provide 24 Vdc and connect the communi-
cation cable between the display and the PXMP meter base.
The Eaton PSG60E is an appropriate 24 Vdc power supply for both
the PXMP-MB meter base and PXMP display. The display’s plug-in
terminals provide connections for +24, GND and Common (0).
Figure 4. PXMP-DISP-6-XV.
Included with the PXMP display is a communications cable to con-
nect DB9 Com 2 of the display to 4-terminal Com 2 of the PXMP
meter base.
For best results, use the default communication settings for the
PXMP-MB and PXMP display (115.2 kbps, 1 start bit, 1 stop bit, no
parity).
ote:N By default, the PXMP display is preset for a PXMP meter base slave
address of “01”. To accommodate a different slave address, the User MUST
change the PXMP display’s “Modbus ID”. This setting can be found under
Settings > Meter ID.
Figure 6. Changing the Modbus ID.
5 4 3 2 1
9 8 7 6
Eaton P/N 67A2124HXX
YY-MM-DD
2.0"
PIN 2
PIN 3
RED
WHITE
BLACK
PIN 1
PIN 4 BARE
72.0"
PIN 1
PHOENIX CONN.
TERMINATION
PIN 3
PIN 5
PIN 7
RED
BLACK
WHITE
DB9 SHELL
DB9 TERMINATION
H12 (XV)
SHIELD WIRE TERMINATED to
67A2124H12
PSG60E
Power supply
connections
(-)
(+)
N
L
(-)
(+)
Display 24 VDC
control power
terminal
Figure 5. Power and COM port communications for the PXMP touch screen display.
/