Power-Genex LSB-3 Series Instructions And Operating Manual

Type
Instructions And Operating Manual

This manual is also suitable for

Instruction and Operating
Manual
Valve Monitoring Indicator
LSB-3 Series
Ver. 1.0
LSB-3000 Series
jjautomation.com 1
Safety Instructions 1
These safety instructions are intended to prevent hazardous situations and/or equipment damage.
These instructions indicate the level of potential hazard with the labels of “Caution,” “Warning” or
“Danger.They are all important notes for safety and must be followed in addition to International
Standards (IEC)Note 1), and other safety regulations.
Note 1) IEC 60079-0 : 2007 EN 60079-0 : 2009
IEC 60079-1 : 2007 EN 60079-1 : 2007
Caution Caution indicates a hazard with a low level of risk which, if not avoided, could result in
minor or moderate injury.
Warning
Warning indicates a hazard with a medium level of risk which, if not avoided, could
result in death or serious injury.
Danger Danger indicates a hazard with a high level of risk which, if not avoided, will result in
death or serious injury.
Warning
1. The compatibility of the product is the responsibility of the person who designs the equipment or
decides its specifications.
Since the product specified here is used under various operating conditions, its compatibility with specific
equipment must be decided by the person who designs the equipment or decides its specifications based
on necessary analysis and test results. The expected performance and safety assurance of the equipment
will be the responsibility of the person who has determined its compatibility with the product. This person
should also continuously review all specifications of the product referring to its latest catalogue information,
with a view to giving due consideration to any possibility of equipment failure when configuring the
equipment.
2. Only personnel with appropriate training should operate machinery and equipment. The product
specified here may become unsafe if handled incorrectly.
The assembly, operation and maintenance of machines or equipment including our products must be
performed by an operator who is appropriately trained and experienced.
3. Do not service or attempt to remove product and machinery/equipment until safety is confirmed.
1. The inspection and maintenance of machinery/equipment should only be performed after measures to
prevent falling or runaway of the driven objects have been confirmed.
2. When the product is to be removed, confirm that the safety measures as mentioned above are
implemented and the power from any appropriate source is cut, and read and understand the specific
product precautions of all relevant products carefully.
3. Before machinery/equipment is restarted, take measures to prevent unexpected operation and
malfunction.
4. Contact POWER-GENEX beforehand and take special consideration of safety measures if the
product is to be used in any of the following conditions.
1. Conditions and environments outside of the given specifications, or use outdoors or in a place exposed to
direct sunlight.
2. Installation on equipment in conjunction with atomic energy, railways, air navigation, space, shipping,
vehicles, military, medical treatment, combustion and recreation, or equipment in contact with food and
beverages, emergency stop circuits, clutch and brake circuits in press applications, safety equipment or
other applications unsuitable for the standard specifications described in the product catalogue.
3. An application which could have negative effects on people, property, or animals requiring special safety
analysis.
4. Use in an interlock circuit, which requires the provision of double interlock for possible failure by using a
mechanical protective function, and periodical checks to confirm proper operation.
5. Do not open when an explosive gas and dust atmosphere may be present
6. To avoid the risks of electrostatic discharges, the user has to make sure of the absence of
dangerous atmosphere before cleaning the device, or will have to clean it only with a damp cloth or
antistatic products.
LSB-3000 Series
jjautomation.com 2
Safety Instructions 2
Caution
1. The product is provided for use in manufacturing industries.
The product herein described is basically provided for peaceful use in manufacturing industries. If
considering using the product in other industries, consult POWER-GENEX beforehand and exchange
specifications or a contract if necessary. If anything is unclear, contact your nearest sales branch.
Limited warranty and Disclaimer/Compliance Requirements
The product used is subject to the following “Limited warranty and Disclaimer” and “Compliance
Requirements”. Read and accept them before using the product.
Limited warranty and Disclaimer
1. The warranty period of the product is 1 year in service or 1.5 years after the product is delivered. Note
2)
Also, the product may have specified durability, running distance or replacement parts. Please consult your
nearest sales branch.
2. For any failure or damage reported within the warranty period which is clearly our responsibility, a
replacement product or necessary parts will be provided. This limited warranty applies only to our
product independently, and not to any other damage incurred due to the failure of the product.
3. Prior to using POWER-GENEX products, please read and understand the warranty terms and
disclaimers noted in the specified catalogue for the particular products.
Note 2) Vacuum pads are excluded from this 1 year warranty.
A vacuum pad is a consumable part, so it is warranted for a year after it is delivered.
Also, even within the warranty period, the wear of a product due to the use of the vacuum pad or failure due to the
deterioration of rubber material are not covered by the limited warranty.
Compliance Requirements
1. The use of POWER-GENEX products with production equipment for the manufacture of weapons of
mass destruction (WMD) or any other weapon is strictly prohibited.
2. The exports of POWER-GENEX products or technology from one country to another are governed by
the relevant security laws and regulations of the countries involved in the transaction. Prior to the
shipment of a POWER-GENEX product to another country, assure that all local rules governing that
export are known and followed.
LSB-3000 Series
jjautomation.com 3
Precautions 1
Be sure to read before handling.
Handling
Caution
1. Avoid excessive vibration or impact to the positioner body and any excessive force to the
armature, as these actions may cause damage to the product. Handle carefully while
transporting and operating.
2. If being used in a place where vibration occurs, using a binding band is recommended to
prevent broken wires because of the vibration.
3. When exposed to possible moisture invasion, please take the necessary measures. For example,
if the positioner is left onsite for long periods, a plug should be put in the piping port and a body
cover unit fitted to avoid water penetration.
Take measures to avoid dew condensation inside the positioner if exposed to high temperature and
humidity. Take enough measures against condensation especially when packing for export.
4. Keep magnetic field off the positioner, as this affects its characteristics.
Air Supply
Caution
1. Use only dehumidified and dust extracted clean compressed air as the air supply.
2. Do not use compressed air containing chemicals, organic solvents, salinity or corrosive gases,
as this may cause malfunction.
3. When operating below the freezing point, protect the positioner from freezing.
Operating Environment
Caution
1. Do not operate in locations with an atmosphere of corrosive gases, chemicals, sea water, or
where these substances will adhere to the regulator.
2. Do not operate out of the indicated operation temperature range as this may cause damage to
electronic parts and seal materials to deteriorate.
3. Do not operate in locations where excessive vibration or impact occurs.
LSB-3000 Series
jjautomation.com 4
2. Overview of Structure
This product consists of the following parts optionally.
SPDT / DPDT / P&F NJ2-V3-N / P&F NJ2-12GM-N
Potentiometer for position feedback
Able to Bottom visual indicator
The followings are descriptions of internal parts without cover.
No. Description
1 Main body
2 Switches or sensors
3 Terminal
4 Ground
5 Feedback shaft
6 Cam
7 Terminal bracket
8 Cable entry
LSB-3000 Series
jjautomation.com 5
3. Specifications
LSB – 30xx LSB – 31xx
Explosion proof
/ protection class
Ex d IIC T* / IP 66, 67, 68
Ambient
Temperature
T6 : -40 ~ +75
T5 : -40 ~ +90
Tcable : 95°C
T4 : -40 ~ +110
Tcable : 115°C
Switches / Sensor **
Mechanical switches
SPDT (STD or Haneywell)
DPDT (OMRON or ITW-switch)
Proximity sensors
NJ2-V3-N
NJ2-12GK-SN
NJ4-12GK-SN
NBB3-V3-E2
NBB3-V3-Z4
PSN17-5D PNP or NPN
Magnet proximity
sensors
MS-20
MS-100
GO switch Model 35 (Topworx)
Operating Temperature -40 ~ +100℃ (-40 ~ +212℉) **
Electrical connections PT 1/2 , NPT 1/2,
M20 x 1.5, PT 3/4, NPT 3/4 NPT 3/4
Body material / painting Aluminum diecast /
powder coating Stainless steel, 316SS
Weight 2 Kg 4 kg
* See Ambient Temperature
** See Specifications of Switches and Sensors
4. Description on Nameplate
MODEL NUMBER : Model number and options are described.
Switch Type : Mechanical switches / Proximity sensors type / Magnet sensors type / GO switch type
Voltage Ratings : switche / sensor voltage ratings
Electrical Connections
Operating Temp.
Serial No : A serial number and a manufacturing date for tracking are described.
Certificate No
INERIS 14ATEX 0060X / IECEx KTL 14.0013 / 14-KB2BO-0080
Code : Ex d IIC T* Gb (T6 : -40 to +75℃ / T5 : -40 to +95℃ / T5 : -40 to +115℃)
VALVE POSITION MONITOR
S
LSB-3000 Series
jjautomation.com 6
5. Part Numbering System (order code)
LSB — 3
x
x
x
x
x
x
x
x
x
x
Body Material Aluminum die-cast 0
Stainless steel 316 1
Switches / Sensors *
Mechanical
switches
2 x SPDT 0
4 x SPDT 2
2 x DPDT / OMRON or ITW 4
Proximity
sensors
2 x NJ2-V3-N / P&F 6
4 x NJ2-V3-N / P&F 7
2 x NJ2-12GK-SN / P&F
2 x NJ4-12GK-SN / P&F 8
GO
switches 2 x GO switches E
Honeywell
switches
2 x SPDT (Silver) G
4 x SPDT (Silver) H
2 x SPDT (Gold) I
4 x SPDT (Gold) J
Position Transmitter None 0
4 ~ 20mA output signal P
Explosion proof KC – Ex d IIC K
IECEx / ATEX Ex d IIC E
KC – Ex ia IIC A
Ingress Protection IP66 6
IP code IP67 7
IP68 8
Beacon / Indicator Beacon indicator (90° - open / close) A
Bottom indicator (90° - open / close) B
Beacon & Bottom indicator (90° - open / close) C
Other flow direction indicator (L or T port) ** D
Electrical PF 3/4 A
Connections NPT 3/4 (LSB-31xx only NPT 3/4) B
PF 1/2 C
NPT 1/2
E
M25 F
Numbers of Electrical
Connections
2 pcs 2
3 pcs 3
Feedback Shaft Rotary type NAMUR shaft (direct mounting) N
Fork lever F
Linear type
Stroke 10 ~ 40mm A
Stroke 10 ~ 80mm B
Stroke 10 ~ 150mm C
Stroke 10 ~ 200mm D
Mounting Bracket None N
30 x 80 x 20(H) - VDI / VDE3845 (IEC60534-6-2) 1
30 x 80 x 30(H) - VDI / VDE3845 (IEC60534-6-2) 2
30 x 130 x 30(H) - VDI / VDE3845 (IEC60534-6-2) 3
30 x 130 x 50(H) - VDI / VDE3845 (IEC60534-6-2) 4
Multi-size Backet M
* Other brand / model switches / sensors on request
** Other flow direction indicators on request
LSB-3000 Series
jjautomation.com 7
6. Specifications of Switches and Sensors
6.1 Mechanical Switches
6.1.1 SPDT, SZM-V16-2FA-61 (STD)
< SPDT Mechanical Switch >
Type
Non-inductive load Inductive load
Resistive Lamp Inductive Motor
Rating
250VAC
8VDC
30VDC
125VDC
250VDC
16A
16A
10A
0.6A
0.3A
2A
4A
4A
0.1A
0.05A
10A
10A
10A
0.6A
0.3A
3A
6A
4A
0.1A
0.05A
< Wiring >
Operating
Temperature -30 ~ +105 ℃
6.1.2 SPDT, V7-1C17E9-022 (Honeywell - Gold)
< SPDT Mechanical Switch >
Type Resistive load / Inductive load
Rating
125VAC
250VAC
277VAC
125VDC
250VDC
15.1A 1/2HP
15.1A 1/2HP
15.1A 1/2HP
0.5A
0.25A
< Wiring >
Operating
Temperature -40 ~ +82 ℃
6.1.3 DPDT, Licon-22 (ITW)
< DPDT Mechanical Switch >
Type Resistive load Inductive load
Rating
125VAC
250VAC
28VDC
10A 1/2HP
10A 3/4HP
10A
10A 1/2HP
10A 3/4HP
7A
< Wiring >
Operating
Temperature -30 ~ +80 ℃
LSB-3000 Series
jjautomation.com 8
6.2 Proximity Sensors
6.2.1 NJ2-V3-N (P&F)
< Proximity Switch >
General Specifiactions
Switching element function
Rated operating distance
Installation
Output polarity
Assured operating distance
NAMUR NC
2mm
embeddable
NAMUR
0 ~ 1.62 mm
Nomial Ratings
Nominal voltage
Switching frequency
Hysteresis
Current consumption
Mesasuring plate not detected
Measuring plate detected
8.2 VDC
0 ~ 1000 Hz
0.01 ~ 0.1 mm
> 3mA
< 1mA
< Wiring >
Mechanical Specifications
Connection type
Core cross-section
Housing material
Sensing face
Protection degree
Cable PCV, 130 mm
0.14 mm
PBT
PBT
IP67
Operating Temperature
-
25 ~ +100
6.2.2 NJ2-12GK-SN (P&F)
< Proximity Switch >
General Specifiactions
Switching element function
Rated operating distance
Installation
Output polarity
Assured operating distance
NAMUR NC
2mm
flush
Safety Function
0 ~ 1.62 mm
Nomial Ratings
Nominal voltage
Switching frequency
Hysteresis
Current consumption
Mesasuring plate not detected
Measuring plate detected
8 VDC
0 ~ 2000 Hz
3%
> 3mA
< 1mA
< Wiring >
Mechanical Specifications
Connection type
Core cross-section
Housing material
Sensing face
Protection degree
Cable PCV, 2 m
0.34 mm
PP
PP
IP68
Operating Temperature
-
40
~ +100
7. Specifications of Position Transmitter
General
Specifications
Current Output Signal
Power Supply Range
Span Adjustable Angle
4 ~ 20mA , 2-wire
12 ~ 30VDC (24VDC recommendable)
0 ~ 120°
Nomi
n
al Ratings
Linearity
Repeatability
Hysteresis
Within ± 1.0% F.S.
Within ± 0.25% F.S.
Within ± 1.0% F.S.
<with mA calibrator>
<with mA tester>
LSB-3000 Series
jjautomation.com 9
8. Electrical Connections
2 x SPDT 2 x DPDT
Be sure to supply the rated voltage and current stated on this manual. Otherwise, it may cause a
serious damage or malfunctions.
Check polarity of + and – exactly and connect wires.
When it is necessary to open the positioner cover at a humid place, more attention is required. It may
cause a serious damage or malfunctions.
Explosion-proof construction
LSB-3 becomes explosion proof, as certified by IECEx/ATEX/KC, according to the model selected.
The explosion-proof grade has the following approval : Ex d IIC T*
Take extra care when handling the LSB-3 as explosion-proof equipment
To use as Ex d IIC T*
A) Pressure-proof packing.
As shown below in the chart, use "Cable gland"
B) Metal Piping.
Attach the sealant fitting bracket near the cable port.
(For details, refer to "The guideline on electric equipment explosion proof" published by the
Technology Institution of Industrial Safety).
LSB-3000 Series
jjautomation.com 10
2 x P&F NJ2-V3-N 4 x P&F NJ2-V3-N
-Position Transmitter Option
a) With mA loop calibrator
b) With multi-meter
<2 x SPDT single coil + Position transmitter>
- Setting
10.1 Earthing
The Postioner must be connected to a good quality earth. The units are provided with internal and
external earthing terminals which are both located on the terminal chamber section of the unit
It is necessary to set Zero and Span of position transmitter manually.
The power supply of 12 – 30VDC should be supplied.
- Install the LSB-7 properly before setting the position transmitter.
- Check the proper position of the RA/DA switch before setting.
1. Turn the Zero screw until the output signal reaches 4mA.
2. Turn the Span screw until the output signal reaches 20mA.
3. Repeat the above procedure until the output signals reach 4mA and 20mA.
4. Operate the valve and check if the output signals are transmitted properly.
LSB-3000 Series
jjautomation.com 11
9. Setting of Cams and Switches
a) Push up the red cam if it is necessary to set the position of the red cam.
b) Turn the red cam until it touches the limit switch. And put down and fix it with a wrench bolt.
c) Do the same procedure for setting of the blue cam. But push it down to move.
LSB-3000 Series
jjautomation.com 12
10. Dimensions
LSB-3000 Series
jjautomation.com 13
J+J Automation UK Ltd
Unit 5 & 6 Lime Tree Business Park
Lime Tree Road
Matlock
Derbyshire DE4 3EJ
U.K.
Tel : +44 1629 55577
Website : jjautomationcom
Subject to change without prior notice
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14

Power-Genex LSB-3 Series Instructions And Operating Manual

Type
Instructions And Operating Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI