UNCLASSIFIED AREA
Isolator
Isolator
4+
Postitioner
Ii : 29,7mA
Pi : 79mW
Ci : 40 nF
Ui : 10,6V
HAZARDEOUS AREA
7+
6-
Positioner
Ui : 10,6V
Pi : 79mW
Ci : 40 nF
Li : 100 µH
Ii : 29,7mA
HAZARDEOUS AREA
3-
Li : 100 µH
Pin 3;4 : Switch 1
Pin 6;7 : Switch 2
UNCLASSIFIED AREA
Pi : 653mW
D2xIxx-xxxxxx-xxTxx
Positioner
Model no: D3Ixx-xxxxxx-xxTx/Logix 8xx-02-xxxxxx-xxx-xxT
Pin 9;10
4-20 mA Output
UNCLASSIFIED AREAHAZARDEOUS AREA
Safety Barrier
/PA/PA
10-
Ii : 93mA
Ui : 28V
Li : 11,3 µH
Ci : 16,4 nF
9+
Ci : 5,64 nF
D2xIxx-xxxxx-xxTxx
Positioner
Model no: D3Ixx-xxxxxx-xxTx/Logix 8xx-02-xxxxxx-xxx-xxT
Alarm
Pin 11;12
/PA/PA
11+
12-
UNCLASSIFIED AREA
Safety Barrier
Ui : 28V
Pi : 315mW
Ii : 45mA
Li : 11,3 µH
HAZARDEOUS AREA
Pi : 315mW
Positioner
Positioner
Normally Closed
Pin 7;8 : Switch 2
Pin 4;5 : Switch 1
Safety Barrier
3 or 4
5
Pin 3;5 : Switch 1
Pin 6;8 : Switch 2
Normally Open
UNCLASSIFIED AREA
Ui : 28V
Ci : 1 nF
Ii : 45mA
HAZARDEOUS AREA
Pi : 315mW
/PA/PA
/PA/PA
Safety Barrier
6 or 7
8
UNCLASSIFIED AREA
Ui : 28V
Ci : 1 nF
Ii : 45mA
Li : 1 µH
HAZARDEOUS AREA
Li : 1 µH
UNCLASSIFIED AREA
Positioner
Positioner
Pin 7;8 : Switch 2
Pin 4;5 : Switch 1
Normally Closed
Pin 6;8 : Switch 2
Pin 3;5 : Switch 1
Normally Open
Isolator
Isolator
3 or 4
Ui : 10,6V
HAZARDEOUS AREA
5
8
6 or 7
Pi : 79mW
Ci : 1 nF
Li : 1 µH
Ui : 10,6V
Ii : 29,7mA
Ci : 1 nF
Li : 1 µH
Pi : 79mW
HAZARDEOUS AREA
Ii : 29,7mA
UNCLASSIFIED AREA
4
Remote unit output parameter
Po : 0,38W
Positioner
Shielded cable less than 10 metres
HAZARDEOUS AREA
Pot.
Pin 3;4;5
4
3
55
3
D3Ixx-xxxxxx-xx6x
D2xIxx-xxxxxx-xx6xxD2xIxx-xxxxxx-xx5xxD2xIxx-xxxxxx-xx4xxD2xIxx-xxxxxx-xxNxxD2xIxx-xxxxxx-xxPxxD2xIxx-xxxxxx-xxSxx
All components need Saftey Barriers * except the Switches on transmitter board 3-As81N, 3-As81D4,
Explosion Hazard - Do not disconnect equipment unless area is known to be non-hazardous.
Substitution of the following components may impair suitability for Division 2 :
or; read, understand and adhere to the manufacturer's live maintenance procedures.
To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing,
*Only CSA and FM
Substitution of components may impair Intrinsic Safety.
Warnings:
Non-Incendive:
Further requirements for FM:
- Associated apparatus manufacturer's installation drawing must be followed when installing this equipment.
- The Entity Concept allows interconnections of intrinsically safe apparatus with associated apparatus when the following is true:
Vmax or Ui larger than Voc, Vt or Uo;
Imax or Ii larger than Isc, It or Io
Pmax or Pi larger than Po
Ca larger than Ci + Ccable
La larger than Li + Lcable
- Dust-Tight conduit seal must be when installed in Class II and Class III environments.
- Control equipment connected to Associated Apparatus must not use or generate more than 250 Vrms or Vdc.
- Resistance between Intrinsically Safe Ground must be less than 1,0 Ohm.
- Installation should be in accordance with ANSI/ISA-RP12.06.01 "Installation of Intrinsically Safe Systems for Hazardous (Classified) Locations" and the National
Electric Code (ANSI/NFPA 70).
- The associated apparatus must be FM approved.
- The associated apparatus must be a resistively limited by a single or multiple channel FM Approved Associated apparatus having parameters less than those quoted,
and for which the output and the combinations of output is non-ignition capable for the Class, Division and Group of use.
Model no:
Logix 8xx-02-xxxxxx-xx1-xxx
D3Ixx-xxxxxx-xxSx
Model no:
Logix 8xx-02-xxxxxx-xx2-xxx
D3Ixx-xxxxxx-xxPx
Model no:
Logix 8xx-02-xxxxxx-xx3-xxx
D3Ixx-xxxxxx-xxNx
Model no:
Logix 8xx-02-xxxxxx-xx4-xxx
D3Ixx-xxxxxx-xx4x
Model no:
Logix 8xx-02-xxxxxx-xx5-xxx
D3Ixx-xxxxxx-xx5x
Model no:
Logix 8xx-02-xxxxxx-xx6-xxx
3-As81D5, 3-As81D6, 3-As81P, D3-As38E N, D3-As38E D4, D3-As38E D5, D3-As38E D6 and D3-As38E P.
Pin 2: Irtn
Positioner
/PA
Safety Barrier
/PA
Pin 1;2
1+
2-
HAZARDEOUS AREA
Ui : 28V
Ii : 93mA
Pi : 653mW
Ci : 11,3 nF
Li : 11,3 µH
Pin 1: Isrc
UNCLASSIFIED AREA
µH changed to µH; Ci: 35 nF cha nged to Ci: 40 nF.
8. Switch 2 COM
1. Input signal
12. Alarm Output -
11. Alarm Output +
10. 4-20 mA -
9. 4-20 mA +
7. Switch 2 NC
6. Switch 2 NO
5. Switch 1 COM
4. Switch 1 NC
3. Switch 1 NO
2. Input signal
4-20mA input signal
Mechanical or Proximity switches
NAMUR switches
D3Ixx-xxxxxx-xx4x/Logix 8xx-02-xxxxxx-xxx-xx4
Model no: D3Ixx-xxxxxx-x4xx/Logix 81x-02-xxxxxx-xxx-xxx
Model no: D3Ixx-xxxxxx-xxNx/Logix 8xx-02-xxxxxx-xxx-xx3
D3Ixx-xxxxxx-x5xx/Logix 82x-02-xxxxxx-xxx-xxx
D3Ixx-xxxxxx-xx5x/Logix 8xx-02-xxxxxx-xxx-xx5
D3Ixx-xxxxxx-xx6x/Logix 8xx-02-xxxxxx-xxx-xx6
Model no: D3Ixx-xxxxxx-xxSx/Logix 8xx-02-xxxxxx-xxx-xx1
D3Ixx-xxxxxx-xxPx/Logix 8xx-02-xxxxxx-xxx-xx2
Model no: D3Ixx-Mxxxxx-xxxx/Logix 8xx-02-xxxxxx-xMx-xxx
D3Ixx-Pxxxxx-xxxx/Logix 8xx-02-xxxxxx-xPx-xxx
to the Notified body
D3Ixx-Rxxxxx-xxxx/Logix 8xx-02-xxxxxx-xRx-xxx
D3Ixx-Qxxxxx-xxxx/Logix 8xx-02-xxxxxx-xQx-xxx
D2xIxx-xxxxxx-x4xxx
D2xIxx-xxxxxx-xxNxx
D2xIxx-xxxxxx-xxSxx
D2xIxx-xxxxxx-x5xxx
D2xIxx-xxxxxx-xx4xx
D2xIxx-xxxxxx-xx6xx
D2xIxx-xxxxxx-xx5xx
D2xIxx-xxxxxx-xxPxx
D3Ixx-xxxxxx-xxPx/Logix 8xx-02-xxxxxx-xxx-xx2
D2xIxx-xxxxxx-xxPxx
D2xIxx-xxxxxx-xxSxx
Model no: D3Ixx-xxxxxx-xxSx/Logix 8xx-02-xxxxxx-xxx-xx1
Mechanical or Proximity switches
D2xIxR-xxxxxx-xxxxx
No modification permitted without reference
7
Tested according to withstand dielectric strength requirement IEC EN 60079-11 6.3.12
Ingress Protection IP 66, NEMA 4X
Schedule drawing
5 5
5
5
5
5
5
5
5 55
5
5
5
5
5
5
5
5
7
Remote unit
5
5
6
7
5
6
7 77777
7
7
7
7
7
7
7
7
7
7
7