Danfoss mixing module FH-MJA Installation guide

Type
Installation guide
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
The FH-MJA mixing module is designed for con-
nection to the boiler loop of low temperature
heating systems, e.g. underfloor and wall heating
systems.
FH-MJA is a low-noise, compact mixing module,
designed for installation in the manifold cabinet.
For multi-family houses the feed temperature can
be selected individually for each apartment.
1. High efficiency circulator pump
2. Floor heating loop feed side
3. Floor heating loop return side
4. Control valve with mechanical actuator (20-55 °C)
5. Presetting knob for control valve
6. Bypass valve (keep closed)
7. Integrated check valve
8. Boiler loop feed side
9. Boiler loop return side
10. Ball valve boiler loop feed side
11. Ball valve boiler loop return side
12. Control knob pump
13. Automatic air vent
14. Safety temperature thermostat
15. Bleeding valve
16. Filling valve
Application
Instruction
Installation and operation manual
for mixing module FH-MJA
Danfoss HES VI.UL.R1.02 © Danfoss 06/2009 1
Function
Floor heating loop
The pump (1) circulates the water through •
the floor heating feed connection and the
floor heating loops to the floor heating return
connection.
Mixing
When the control valve (4) opens, boiler loop •
feed water (8) is mixed to the floor heating
loop feed side and the same amount of water is
returned from the floor heating return side (3)
to the boiler loop return side (9).
The control valve adjusts the quantity of water •
coming from the boiler loop to control the
desired floor heating feed temperature.
Control and safety device
The mixing unit has both integrated, a feed •
temperature control (setting range 20-55 °C)
and a safety temperature device (20-90 °C). In
the unlikely case of an overtemperature situ-
ation, the safety temperature device switches
the pump off.
Please consider, that the setting of the safety •
device must be minimum 8° higher, than the
setting of the wished feed temperature.
The wished feed temperature is set by the •
mechanical feed thermostat, which setting
range is 1-9 (= 20-55 °C).
Thermostat display Feed temperature
1 20 °C
2 26 °C
3 30 °C
4 34 °C
5 38 °C
6 42 °C
7 46 °C
8 50 °C
9 55 °C
Control
18 16
17
8 10 14 2
5 4 7
1
12
6
15
9 11 3
13
Instruction Installation and operation manual for mixing module FH-MJA
2 VI.UL.R1.02 © Danfoss 06/2009 Danfoss HES
Wiring diagram
Feed safety temperature
thermostat (20-90 °C)
Presetting knob for control valve 5
With this knob you can adjust the resistance •
value of the FH-MJA control valve.
This controls the maximum amount of water •
which enters the FH-MJA from the boiler loop
with the control valve fully open.
Use this knob to adapt the mixing unit to the •
heating system and to optimize the control
characteristics.
It is especially important to adjust the presetting •
knob correctly if several Floortec stations are
attached to one boiler loop. This ensures that
all stations will get a sufficient amount of water
from the boiler loop.
Setting:
Use the diagram below for setting the presetting •
knob correctly. It shows the differential pressure
vs. flow rate for the boiler side of the mixing
unit including control valve.
First, determine the amount of boiler water •
needed during peak heat demand. Using the
amount of water and the differential pressure
available during peak heat demand, you find
the appropriate setting of the knob in the
diagram.
Close the presetting knob completely (turn •
right until full stop). Open counter clockwise the
number of turns shown in the diagram.
kPa
300
100
10
1
0,03 0,1
1 3 m
3
/h
0,75 1 1,5 2 3 4
Bypass for step-down control
If the bypass valve (6) is opened, a small quantity •
of boiler feed water will run constantly through
the mixing module. The unit is shipped with the
bypass valve closed. We recommend to keep
this valve closed.
Fill and drain valves
If you fill the system from the fill valve (12), the •
check valve (7) will close. In this way, the water
will flow through the floor heating loops and
not through the mixing module. Excess water
drains through the drain valve of the manifolds
return.
Function
1. Circulator
2. Feed for floor heating circuit
3. Return for floor heating circuit
4. Control valve
5. Presetting knob for control valve
6. Adjustable bypass valve
7. Check valve for filling of floor
heating loops
8. Boiler feed connection
9. Boiler return connection
10. Ball valve of boiler feed connection
11. Ball valve of boiler return
connection
12. Fill valve
13. Drain valve
14. Sensor for floor heating feed
temperature
15. Sensor for floor heating return
temperature
16. Sensor for safety temperature
17. Sensor for boiler feed
temperature
18. Space for calorimeter dip tube
Grommet Mounting bracket
[large hole spacing]
Spacer 20 mm
Spacer 22 mm
Spacer 5 mm
Grommet
Instruction Installation and operation manual for mixing module FH-MJA
Danfoss HES VI.UL.R1.02 © Danfoss 06/2009 3
Presetting knob for control valve
The control valve is equipped with a presetting •
knob 5, with which the maximum amount of
water from the boiler loop can be reduced.
The unit is shipped with the presetting knob
completely open.
Bypass for step-down control
If the bypass valve 6 is opened, a small quantity •
of boiler feed water will run constantly through
the mixing module. This is necessary for a
step-down control, which derives its outside
temperature information from the boiler feed
temperature. The unit is shipped with the by-
pass valve opened 1/2 turn.
Fill and drain valves
If you fill the system from the fill valve 12, the •
check valve 7 will close. In this way, the water
will flow through the floor heating loops and
not through the mixing module. Excess water
drains through the drain valve 13.
Sensor positions integrated in the base module
Floor heating feed temperature 14.•
Floor heating return temperature 15.•
Safety temperature 16.•
Boiler feed temperature 17.•
Dip tube for calorimeter sensor 18.•
Installation options
The FH-MJA station can be installed in two dif-
ferent ways. The mounting hardware required for
both ways is included with the station.
Parallel installation:• the floor heating pipes
are guided parallel to the wall. At the place
were the pipes leave the floor, they have to be
fastened to ensure that they come straight up
into the manifold.
Angled installation:• in this case the FH-MJA
unit is installed at an angle of approximately
eight degrees, so that the floor heating pipes
are guided to the wall at that angle and enter
the floor directly at the wall.
The part of the grommets facing the wall has to have its thickest part facing downward.
On delivery, the FH-MJA is attached to a wooden
base. Re-use the hardware for mounting of the
mixing module.
The picture below shows the parallel installation
with the mounting hardware attached accord-
ingly.
Use the 20 mm spacer at the upper mounting •
eyelet.
Use the 22 mm and the 5 mm spacer at the •
lower mounting eyelet.
Turn the rubber grommets in such a way that •
they are parallel to the wall.
Fix the manifold by attaching the side of the •
mounting bracket with the large hole spacing
to the manifold.
Parallel installation
Grommet Mounting bracket
[large hole spacing]
Spacer 20 mm
Spacer 22 mm
Spacer 5 mm
Grommet
Instruction Installation and operation manual for mixing module FH-MJA
4 VI.UL.R1.02 © Danfoss 06/2009 Danfoss HES
Start-up
Preconditions
The system boiler loop must be filled properly.•
The floor heating system must be filled properly.•
A suitable control for the mixing module must •
be in place.
The bypass valve must be closed.•
The presetting knob must be set correctly for •
the system.
The heating loops must be open.•
The connection to the boiler loop (ball valves 10 •
and 11) must be open.
Start-up
Switch on the pump by turning the pump’s •
control knob to step 7.
The first heating up of a floor heating system •
can take a long time since the floor can absorb
a lot of heat. Additionally, in new constructions,
the high humidity in the slab can delay the heat
up process.
Caution! Operation without the integrated control •
can result in overheating of the underfloor heating
system.
The picture below shows the angled installation
with the mounting hardware attached accordingly.
Use the 20 mm and the 22 mm spacer at the •
upper mounting eyelet.
Use the 5 mm spacer at the lower mounting •
eyelet.
Turn the rubber grommets in such a way that •
they are parallel to the wall.
Fix the manifold by attaching the side of the •
mounting bracket with the small hole spacing
to the manifold.
Angled installation
Attach the manifold (see previous chapter).•
Install the station directly on the wall or in a suf-•
ficiently large cabinet.
Use the two eyelets of the base module for •
installation.
Use the spacers, the grommets and the washers.•
In addition, attach the manifolds before mount-•
ing the module in a cabinet.
If you purchased the base
module without manifold
Avoid any metal contact between the base •
module and the wall.
Avoid any metal contact between the manifold •
and the wall.
Use rubber grommets at all mounting points on •
both sides to avoid metal contact between the
mounting screws and base module or manifold
(the rubber grommets and washers for the
mounting eyelets of the FH-MJA are supplied
with the station).
Important advice for
avoiding noise problems
Technical data
Floor Heating loop Boiler loop
Maximum pressure 6 bar 6 bar
Maximum temperature 55 °C (70 °C thermostat available) 105 °C
Connections 1” male thread ¾” female thread
Circulator see diagram -
kPa
40
30
20
10
0
0,5 1,0 1,5 2,0 2,5 m
3
/h
7
6
5
4
3
2
1
Instruction Installation and operation manual for mixing module FH-MJA
Danfoss HES VI.UL.R1.02 © Danfoss 06/2009 5
The pump curve shows the hy-
draulic performance available at
the manifold connections.
Use the control knob (12) of the
pump to set its speed:
pos. 1 = min. performance.•
pos. 7 = max. performance.•
end pos. anti-clockwise = pump •
switched off.
Pump curve
Pump setting
Add the maximum operation point (mop) value
of the system into the diagram on the top. The
mop is a resulkt of the max. pressure loss, which
usually is caused by the one longest loop of the
ufh system and the max. required total flow for
all loops.
Then set the pump to the value, which is verti-
cally closest to the mop.
Example:
An ufh-system requires a total flow (when all loops
are open) of let’s say 1000 l per hour. With reference
to the pressure loss, the worst loop (usually the long-
est one) creates a pressure loss of let’s say 10 kPa (=
1.0 mWS = 100 mbar).
If you add this value to the diagram on the top the
nearest curve in vertical direction is curve no. 3. So
please set pump to setting 3.
Troubleshooting
Pump is not running
Possibly the safety temperature device has •
tripped and shut off the pump.
If not, the pump may be clogged by dirt. •
Remove the circulator to inspect it.
Heating performance is insufficient
The presetting knob is turned in too far.•
The bypass valve is opened too far.•
The system is just being put into service, in •
which case it may take longer to heat the floor
for the first time. As long as the floor heating
return temperature is still cold, the feed tem-
perature also cannot increase independently
since most of the feed water comes from the
floor heating return and only a small portion is
boiler water!
LED indication
of the pump
Theres a green LED in the centre of the pump’s
control knob showing the operating state:
LED on: Pump is switched on and operating •
properly.
LED off: Wrong wiring or missing voltage.•
Flashing LED:
1 short, 1 long: Incoming voltage below 200 V •
or pump switched off by control konob being
set anti-clockwise to end position.
3 short, 1 long: Processor temperature of pump •
is too hot. Please check allowed max. tempera-
ture of the pumped medium.
5 short, 1 long: Rotor blocked due to dirt. •
System and pump need to be cleaned.
N L
N
L
230 V ~
N
1
2
L
N
1
2
L
N
1
2
L
Instruction Installation and operation manual for mixing module FH-MJA
6 VI.UL.R1.02 © Danfoss 06/2009 Danfoss HES
Wiring with
Danfoss zone module
1 2 3 4 5 6 7 8 9 10
L N
230 V ~
L
N
1
2
Instruction Installation and operation manual for mixing module FH-MJA
Danfoss HES VI.UL.R1.02 © Danfoss 06/2009 7
Wiring with Danfoss
wireless zone module
Instruction Installation and operation manual for mixing module FH-MJA
8 VI.UL.R1.02 © Danfoss 06/2009 Danfoss HES
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Danfoss mixing module FH-MJA Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI