PRECISION DIGITAL PD6000 User manual

Type
User manual
PRECISION DIGITAL CORPORATION
233 South Street • Hopkinton MA 01748 USA
Tel (800) 343-1001 • Fax (508) 655-8990
www.predig.com
PD6000 Analog Input Process Meter
Instruction Manual
0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V Inputs
NEMA 4X, IP65 Front
Universal 85-265 VAC, or 12/24 VDC Input Power Models
Large Dual-Line 6-Digit Display, 0.60" & 0.46"
Dual-Scale for some Level Applications – Single Input
Sunlight Readable Display Models
Isolated 24 VDC Transmitter Power Supply
Signal Input Conditioning for Flow & Round Horizontal Tanks
Programmable Display & Function Keys
32-Point, Square Root, or Exponential Linearization
Multi-Pump Alternation Control
2 or 4 Relays + Isolated 4-20 mA Output Options
External 4-Relay & Digital I/O Expansion Modules
USB, RS-232, RS-485 Serial Communication Options
Tare Function
Modbus
®
RTU Communication Protocol Standard
Configure, Monitor, and Datalog from a PC with
Free MeterView
®
Pro Software
Model PD6000 Analog Input Process Meter Instruction Manual
2
Disclaimer
The information contained in this document is subject to change
without notice. Precision Digital makes no representations or
warranties with respect to the contents hereof and specifically
disclaims any implied warranties of merchantability or fitness for
a particular purpose.
CAUTION: Read complete
instructions prior to
installation and operation
of the meter.
WARNING: Risk of
electric shock or
personal injury.
Warning!
This product is not recommended for life support
applications or applications where malfunctioning
could result in personal injury or property loss.
Anyone using this product for such applications
does so at his/her own risk. Precision Digital
Corporation shall not be held liable for damages
resulting from such improper use.
Limited Warranty
Precision Digital Corporation warrants this product against defects in
material or workmanship for the specified period under
“Specifications” from the date of shipment from the factory. Precision
Digital’s liability under this limited warranty shall not exceed the
purchase value, repair, or replacement of the defective unit.
Registered Trademarks
PROVU
®
and MeterView
®
Pro are registered trademarks of Precision
Digital Corporation. All other trademarks mentioned in this document
are the property of their respective owners.
© 2013-2016 Precision Digital Corporation. All rights reserved.
www.predig.com
!
Model PD6000 Analog Input Process Meter Instruction Manual
3
Table of Contents
INTRODUCTION ------------------------------------------------------------ 6
ORDERING INFORMATION --------------------------------------------- 7
SPECIFICATIONS ---------------------------------------------------------- 8
General ------------------------------------------------------------------------------- 8
Process Input -------------------------------------------------------------------- 10
Relays ------------------------------------------------------------------------------ 10
Isolated 4-20 mA Transmitter Output ------------------------------------ 11
Modbus
®
RTU Serial Communications ---------------------------------- 12
COMPLIANCE INFORMATION ---------------------------------------------- 13
Safety ------------------------------------------------------------------------------- 13
Electromagnetic Compatibility --------------------------------------------- 13
SAFETY INFORMATION ------------------------------------------------ 14
INSTALLATION ------------------------------------------------------------ 14
Unpacking ------------------------------------------------------------------------- 14
Panel Mounting Instructions ------------------------------------------------ 15
Mounting Dimensions ------------------------------------------------------- 16
Configuration for 12 or 24 VDC Power Option ------------------------ 17
Connections ---------------------------------------------------------------------- 18
Connectors Labeling --------------------------------------------------------- 19
Power Connections ---------------------------------------------------------- 19
Signal Connections ---------------------------------------------------------- 20
Modbus RTU Serial Communications ----------------------------------- 21
Relay Connections ----------------------------------------------------------- 21
Switching Inductive Loads -------------------------------------------------- 22
F4 Digital Input Connections ----------------------------------------------- 23
4-20 mA Output Connections ---------------------------------------------- 23
Analog Output Transmitter Power Supply ------------------------------ 23
External Relays & Digital I/O Connections ----------------------------- 24
Interlock Relay Feature ----------------------------------------------------- 25
SETUP AND PROGRAMMING ---------------------------------------- 26
Front Panel Buttons and Status LED Indicators --------------------- 27
Display Functions & Messages -------------------------------------------- 28
Main Menu ------------------------------------------------------------------------ 31
Setting Numeric Values ------------------------------------------------------ 32
Setting Up the Meter (setup) ------------------------------------------------ 33
Setting the Input Signal (Input) ------------------------------------------ 34
Setting the Input Units or Custom Tags (units) ---------------------- 35
Model PD6000 Analog Input Process Meter Instruction Manual
4
Setting the Decimal Point (dEc pt) -------------------------------------- 36
Programming the Meter (prog) ------------------------------------------- 37
Program Menu for Single Scale Process --------------------------- 37
Program Menu for Dual-Scale Level Applications ---------------- 37
Multi-Point Calibration & Scaling -------------------------------------- 38
MeterView
®
Pro Software ----------------------------------------------- 38
Scaling the Meter (SCALE) ---------------------------------------------- 38
Dual-Scale for Level Application -------------------------------------- 39
Calibrating the Meter with External Source (Cal) ----------------- 41
Setting the Display Parameter & Intensity (dsplay) ----------------- 42
Display Setup Menu --------------------------------------------------------- 43
Setting the Relay Operation (relay) ------------------------------------- 44
Setting the Relay Action ---------------------------------------------------- 45
Programming Set and Reset Points ------------------------------------- 46
Setting Fail-Safe Operation ------------------------------------------------ 46
Programming Time Delay -------------------------------------------------- 46
Relay Action for Loss of 4-20 mA Input (Loop Break) --------------- 46
Relay and Alarm Operation Diagrams ----------------------------------- 47
High Alarm Operation (Set > Reset) ------------------------------------- 47
Low Alarm Operation (Set < Reset) -------------------------------------- 48
High Alarm with Fail-Safe Operation (Set > Reset) ------------------ 49
Low Alarm with Fail-Safe Operation (Set < Reset) ------------------- 50
Pump Alternation Control Operation ------------------------------------- 51
Relay Sampling Operation ------------------------------------------------- 52
Signal Loss or Loop Break Relay Operation --------------------------- 53
Time Delay Operation ------------------------------------------------------- 54
Relay Operation Details ------------------------------------------------------ 55
Overview ------------------------------------------------------------------------ 55
Relays Auto Initialization ---------------------------------------------------- 55
Fail-Safe Operation ---------------------------------------------------------- 55
Front Panel LEDs ------------------------------------------------------------- 56
Latching and Non-Latching Relay Operation -------------------------- 56
Non-Latching Relay (Auto) ------------------------------------------------- 57
Non-Latching Relay (A-man) -------------------------------------------- 57
Latching Relay (LatcH) ----------------------------------------------------- 57
Latching Relay (Lt-Clr) ---------------------------------------------------- 58
Acknowledging Relays ------------------------------------------------------ 58
Pump Alternation Control Applications (Altern) --------------------- 59
Setting Up the Interlock Relay (Force On) Feature ------------------ 62
Scaling the 4-20 mA Analog Output (Aout) ---------------------------- 63
Reset Menu (reset) ------------------------------------------------------------ 64
Control Menu (Contrl) -------------------------------------------------------- 64
Model PD6000 Analog Input Process Meter Instruction Manual
5
Setting Up the Password (pass) ------------------------------------------- 65
Protecting or Locking the Meter ------------------------------------------- 65
Making Changes to a Password Protected Meter -------------------- 66
Disabling Password Protection -------------------------------------------- 66
Advanced Features Menu ---------------------------------------------------- 67
Advanced Features Menu & Display Messages ---------------------- 68
Noise Filter (filter) -------------------------------------------------------- 71
Noise Filter Bypass (bypass) ---------------------------------------------- 71
Rounding Feature (round) ------------------------------------------------- 71
Modbus RTU Serial Communications (serial) ---------------------- 72
Select Menu (SElect) ------------------------------------------------------- 73
Signal Input Conditioning (Functn) -------------------------------------- 73
Low-Flow Cutoff (CutofF) -------------------------------------------------- 76
Analog Output Programming (AoutPr) ---------------------------------- 76
Programmable Function Keys User Menu (user) -------------------- 77
Tare (tare) --------------------------------------------------------------------- 78
Internal Source Calibration (ICAL) --------------------------------------- 79
Meter Copy Function (Copy) ----------------------------------------------- 81
METER OPERATION ----------------------------------------------------- 83
Front Panel Buttons Operation -------------------------------------------- 83
Function Keys Operation ---------------------------------------------------- 83
F4 Operation --------------------------------------------------------------------- 84
Maximum/Minimum Readings ---------------------------------------------- 84
TROUBLESHOOTING ---------------------------------------------------- 85
Diagnostics Menu (diag) ----------------------------------------------------- 85
Determining Software Version -------------------------------------------- 85
Reset Meter to Factory Defaults ------------------------------------------- 86
Factory Defaults & User Settings ----------------------------------------- 87
Troubleshooting Tips --------------------------------------------------------- 90
Alphabetical List of Display Functions & Messages --------------- 91
EU DECLARATION OF CONFORMITY ----------------------------- 99
Model PD6000 Analog Input Process Meter Instruction Manual
6
Table of Figures
Figure 1. 1/8 DIN Panel Cutout Dimensions ..................................... 15
Figure 2. Panel Mounting Details ...................................................... 15
Figure 3. Meter Dimensions - Side View ........................................... 16
Figure 4. Meter Dimensions - Top View ............................................ 16
Figure 5. Jumper Configuration for 12/24 VDC PowerTransmitter
Supply Voltage Selection (P+, P-) ............................................. 17
Figure 6. Transmitter Supply Voltage Selection .............................. 18
Figure 7. Connector Labeling for Fully Loaded PD6000 ................. 19
Figure 8. Power Connections ............................................................ 19
Figure 9. Transmitters Powered by Internal Supply ........................ 20
Figure 10. Transmitter Powered by Ext. Supply or Self-Powered .. 20
Figure 11. Voltage Input Connections .............................................. 21
Figure 12. Relay Connections ........................................................... 21
Figure 13. AC and DC Loads Protection ........................................... 22
Figure 14. Low Voltage DC Loads Protection .................................. 22
Figure 15. F4 Digital Input Connections ........................................... 23
Figure 16. 4-20 mA Output Connections .......................................... 23
Figure 17. Expansion Modules & DIN Rail Mounting Kit ................. 24
Figure 18. External Relays Module Connections ............................. 24
Figure 19. Digital I/O Module Connections ....................................... 25
Figure 20. Interlock Connections ...................................................... 25
Figure 21. Acknowledge Relays w/Function Key or Digital Input .. 58
Figure 22. 1/8 DIN Panel Cutout Template ........................................ 97
INTRODUCTION
The PROVU
®
PD6000 is a multi-purpose, easy to use digital process meter ideal for
level, flow rate, temperature, or pressure transmitter applications. It accepts current
and voltage signals (e.g. 4-20 mA, 0-10 V). Three of the front panel buttons can be
custom-programmed for a specific operation. The analog input can be scaled to
display the process in two different scales; for example, the main display could
indicate level in feet and the second display could indicate the volume in gallons.
The basic model includes an isolated 24 VDC transmitter power supply that can be
used to power the input transmitter or other devices. An additional isolated 24 VDC
power supply is included with the 4-20 mA output option. A digital input is standard.
A fully loaded PD6000 meter has the following: four SPDT relays, 4-20 mA output, and
two 24 VDC power supplies. The PD6000 capabilities may be enhanced by adding the
following external expansion modules: four SPST relays (creating an eight-relay process
meter), two digital I/O modules with four inputs and four outputs each, and USB, RS-232
or RS-485 communication adapters.
The eight relays can be used for alarm indication or process control applications such as
pump alternation control. The 4-20 mA isolated output, Modbus RTU serial
communications, and digital I/O options make the PD6000 an excellent addition to any
system.
Model PD6000 Analog Input Process Meter Instruction Manual
7
ORDERING INFORMATION
Standard Models
85-265 VAC
Model
12/24 VDC
Model
Options Installed
PD6000-6R0 PD6000-7R0 No options
PD6000-6R2 PD6000-7R2 2 relays (PD1102*)
PD6000-6R3 PD6000-7R3 4-20 mA output (PD1103*)
PD6000-6R4 PD6000-7R4 4 relays (PD1104*)
PD6000-6R5 PD6000-7R5 2 relays & 4-20 mA output (PD1105*)
PD6000-6R7 PD6000-7R7 4 relays & 4-20 mA output (PD1107*)
*Model number for replacement option card.
SunBright Display Models
85-265 VAC
Model
12/24 VDC
Model
Options Installed
PD6000-6H0 PD6000-7H0 No options
PD6000-6H2 PD6000-7H2 2 relays (PD1102*)
PD6000-6H3 PD6000-7H3 4-20 mA output (PD1103*)
PD6000-6H4 PD6000-7H4 4 relays (PD1104*)
PD6000-6H5 PD6000-7H5 2 relays & 4-20 mA output (PD1105*)
PD6000-6H7 PD6000-7H7 4 relays & 4-20 mA output (PD1107*)
*Model number for replacement option card.
Accessories
Model Description
PDA1002 DIN rail mounting kit for two expansion modules
PDA1004 4 SPST (Form A) relays
PDA1044 4 digital inputs & 4 digital outputs (2 may be connected)
PDA1200 Meter copy cable
PDA1232 RS-232 serial adapter
PDA1485 RS-485 serial adapter
PDA7485-I RS-232 to RS-422/485 isolated converter
PDA7485-N RS-232 to RS-422/485 non-isolated converter
PDA8008 USB serial adapter
PDA8232-N USB to RS-232 non-isolated converter
PDA8485-I USB to RS-422/485 isolated converter
PDA8485-N USB to RS-422/485 non-isolated converter
PDX6901
Suppressor (snubber): 0.01 µF/470 Ω, 250 VAC
Enclosures
Model Description
PDA2811 1 Meter Plastic NEMA 4X Enclosure
PDA2812 2 Meter Plastic NEMA 4X Enclosure
Model PD6000 Analog Input Process Meter Instruction Manual
8
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
DISPLAY Main display: 0.60" (15 mm) high, red LEDs
Second display: 0.46" (12 mm) high, red LEDs
6 digits each (-99999 to 999999), with lead zero blanking
DISPLAY
INTENSITY
Eight user selectable intensity levels
DISPLAY
UPDATE RATE
5/second (200 ms)
OVERRANGE
Display flashes
999999
UNDERRANGE
Display flashes
-99999
DISPLAY
ASSIGNMENT
The main (Big) and small (Little) displays may be assigned
to PV1, PV2, PCT, d r-u, d gross, d nt-g, max/min, max &
min, set points, units (small display only), or Modbus input.
PROGRAMMING
METHODS
Four front panel buttons, digital inputs, PC and MeterView Pro
software, Modbus registers, or cloning using Copy function.
NOISE FILTER Programmable from 2 to 199 (0 will disable filter)
FILTER BYPASS Programmable from 0.1 to 99.9% of calibrated span
RECALIBRATION All ranges are calibrated at the factory. Recalibration is
recommended at least every 12 months.
MAX/MIN
DISPLAY
Max/min readings reached by the process are stored until
reset by the user or until power to the meter is turned off.
PASSWORD
Three programmable passwords restrict modification of
programmed settings.
Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs and editing set/reset points
Pass 3: Restricts all programming, function keys, and digital inputs.
POWER
OPTIONS
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max
or jumper selectable 12/24 VDC ± 10%, 15 W max
ISOLATED
TRANSMITTER
POWER SUPPLY
Terminals P+ & P-: 24 VDC ± 10%. 12/24 VDC powered models
selectable for 24, 10, or 5 VDC supply (internal jumper J4).
ProVu Series (PD6000):
85-265 VAC models rated @ 200 mA max, 12/24 VDC powered
models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC
supply.
ProtEX-MAX (PD8 Series):
All models transmitter supply rated @ 25mA max.
Model PD6000 Analog Input Process Meter Instruction Manual
9
NON-VOLATILE
MEMORY
All programmed settings are stored in non-volatile memory
for a minimum of ten years if power is lost.
FUSE Required external fuse: UL Recognized, 5 A max, slow
blow; up to 6 meters may share one 5 A fuse
NORMAL MODE
REJECTION
Greater than 60 dB at 50/60 Hz
ISOLATION 4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply
OVERVOLTAGE
CATEGORY
Installation Overvoltage Category II:
Local level with smaller transient overvoltages than
Installation Overvoltage Category III.
ENVIRONMENTAL ProVu Series(PD6000):
Operating temperature range: -40 to 65°C
Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing
ProtEX-MAX (PD8 Series):
T6 Class operating temperature range Ta = -40 to 60°C
T5 Class operating temperature range Ta = -40 to 65°C
See LIM8 ProtEX-MAX instruction manual for additional
details.
MAX POWER
DISSIPATION
ProtEX-MAX (PD8 Series): Maximum power dissipation
limited to 15.1 W. See LIM8 ProtEX-MAX instruction
manual for additional details.
CONNECTIONS Removable screw terminal blocks accept 12 to 22 AWG
wire, RJ45 for external relays, digital I/O, and serial
communication adapters.
ENCLOSURE 1/8 DIN, high impact plastic, UL 94V-0, color: black
MOUNTING 1/8 DIN panel cutout required:
3.622" x 1.772" (92 mm x 45 mm)
Two panel mounting bracket assemblies are provided.
TIGHTENING
TORQUE
Screw terminal connectors: 5 lb-in (0.56 Nm)
OVERALL
DIMENSIONS
4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm)
(W x H x D)
WEIGHT 9.5 oz (269 g)
WARRANTY 3 years parts & labor
Model PD6000 Analog Input Process Meter Instruction Manual
10
Process Input
INPUTS Field selectable:
0-20, 4-20 mA, ±10 V (0-5, 1-5, 0-10 V), Modbus PV (Slave)
ACCURACY ±0.03% of calibrated span ±1 count,
square root & programmable exponent accuracy
range: 10-100% of calibrated span
TEMPERATURE
DRIFT
0.005% of calibrated span/°C max from 0 to 65°C ambient,
0.01% of calibrated span/°C max from -40 to 0°C ambient
SIGNAL INPUT
CONDITIONING
Linear, square root, programmable exponent, or
round horizontal tank volume calculation
MULTI-POINT
LINEARIZATION
2 to 32 points for PV or PV1
2 to 8 points for PV2 (Dual-scale Level feature)
PROGRAMMA-
BLE EXPONENT
1.0001 to 2.9999
ROUND H TANK Diameter & Length: 999.999 inch or cm calculates volume
in gallons or liters respectively.
LOW-FLOW
CUTOFF
0-999999 (0 disables cutoff function)
DECIMAL POINT Up to five decimal places or none:
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
CALIBRATION
RANGE Input Range
Minimum Span
Input 1 & Input 2
4-20 mA 0.15 mA
±10 V 0.01 V
An error message will appear if the input 1 and input 2
signals are too close together.
INPUT
IMPEDANCE
Voltage ranges: greater than 500 kΩ
Current ranges: 50 - 100 Ω
(depending on resettable fuse impedance)
INPUT
OVERLOAD
Current input protected by resettable fuse, 30 VDC max.
Fuse resets automatically after fault is removed.
F4 DIGITAL INPUT
CONTACTS
3.3 VDC on contact. Connect normally open contacts
across F4 to COM.
F4 DIGITAL INPUT
LOGIC LEVELS
Logic High: 3 to 5 VDC
Logic Low: 0 to 1.25 VDC
Relays
RATING 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A)
external; rated 3 A @ 30 VDC and 125/250 VAC resistive
load; 1/14 HP ( 50 W) @ 125/250 VAC for inductive loads
NOISE
SUPPRESSION
Noise suppression is recommended for each relay contact
switching inductive loads; see page 22 for details.
DEADBAND 0-100% of span, user programmable
Model PD6000 Analog Input Process Meter Instruction Manual
11
HIGH OR LOW
ALARM
User may program any alarm for high or low trip point.
Unused alarm LEDs and relays may be disabled (turn off).
RELAY
OPERATION
Automatic (non-latching) and/or manual reset
Latching (requires manual acknowledge) with/without clear
Pump alternation control (2 to 8 relays)
Sampling (based on time)
Off (disable unused relays and enable Interlock feature)
Manual on/off control mode
RELAY RESET User selectable via front panel buttons or digital inputs
1. Automatic reset only (non-latching), when the input
passes the reset point.
2. Automatic + manual reset at any time (non-latching)
3. Manual reset only, at any time (latching)
4. Manual reset only after alarm condition has cleared
(latching)
Note: Front panel button or digital input may be assigned to
acknowledge relays programmed for manual reset.
TIME DELAY 0 to 999.9 seconds, on & off relay time delays
Programmable and independent for each relay
FAIL-SAFE
OPERATION
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
AUTO
INITIALIZATION
When power is applied to the meter, relays will reflect the
state of the input to the meter.
Isolated 4-20 mA Transmitter Output
OUTPUT
SOURCE
Process variable (PV), max, min, set points 1-8, Modbus
input, or manual control mode
SCALING RANGE 1.000 to 23.000 mA for any display range
CALIBRATION Factory calibrated: 4.000 to 20.000 = 4-20 mA output
ANALOG OUT
PROGRAMMING
23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break
ACCURACY ± 0.1% of span ± 0.004 mA
TEMPERATURE
DRIFT
0.4 µA/°C max from 0 to 65°C ambient,
0.8 µA/°C max from -40 to 0°C ambient
Note: Analog output drift is separate from input drift.
Model PD6000 Analog Input Process Meter Instruction Manual
12
ISOLATED
TRANSMITTER
POWER SUPPLY
Terminals I+ & R: 24 VDC ± 10%. May be used to power the
4-20 mA output or other devices. Refer to Figure 5 on page
17 and Figure 16 on page 23.
ProVu Series (PD6000):
All models rated @ 40 mA max.
ProtEX-MAX (PD8 Series):
All models @ 25mA max.
EXTERNAL LOOP
POWER SUPPLY
35 VDC maximum
OUTPUT LOOP
RESISTANCE
Power supply Minimum Maximum
24 VDC 10 Ω 700 Ω
35 VDC (external) 100 Ω 1200 Ω
Modbus
®
RTU Serial Communications
SLAVE ID 1 – 247 (Meter address)
BAUD RATE 300 – 19,200 bps
TRANSMIT
TIME DELAY
Programmable between 0 and 199 ms
DATA 8 bit (1 start bit, 1 or 2 stop bits)
PARITY Even, Odd, or None with 1 or 2 stop bits
BYTE-TO-BYTE
TIMEOUT
0.01 – 2.54 second
TURN AROUND
DELAY
Less than 2 ms (fixed)
Note: Refer to the PROVU
®
Modbus Register Tables located at www.predig.com
for details.
Model PD6000 Analog Input Process Meter Instruction Manual
13
COMPLIANCE INFORMATION
Safety
UL & c-UL LISTED USA & Canada
UL 508 Industrial Control Equipment
UL FILE NUMBER E160849
FRONT PANEL UL Type 4X, NEMA 4X, IP65; panel gasket provided
LOW VOLTAGE
DIRECTIVE
EN 61010-1:2010
Safety requirements for measurement, control, and
laboratory use
Electromagnetic Compatibility
EMISSIONS
EN 55022:2010
Class A ITE emissions requirements
Radiated
Emissions
Class A
AC Mains
Conducted
Emissions
Class A
IMMUNITY
EN 61326-1:2013
Measurement, control, and laboratory equipment
EN 61000-6-2:2005
EMC heavy industrial generic immunity standard
RFI - Amplitude
Modulated
80 -1000 MHz 10 V/m 80% AM (1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
Electrical Fast
Transients
±2kV AC mains, ±1kV other
Electrostatic
Discharge
±4kV contact, ±8kV air
RFI - Conducted
10V, 0.15-80 MHz, 1kHz 80% AM
AC Surge
±2kV Common, ±1kV Differential
Surge
1KV (CM)
Power-Frequency
Magnetic Field
30 A/m 70%V for 0.5 period
Voltage Dips
40%V for 5 & 50 periods
70%V for 25 periods
Voltage
Interruptions
<5%V for 250 periods
Model PD6000 Analog Input Process Meter Instruction Manual
14
Note:
Testing was conducted on PD6000 meters installed through the
covers of grounded metal enclosures with cable shields grounded at
the point of entry representing installations designed to optimize
EMC performance.
Declaration of Conformity available at www.predig.com
SAFETY INFORMATION
CAUTION: Read complete
instructions prior to
installation and operation
of the meter.
WARNING: Risk of
electric shock or
personal injury.
Warning!
Hazardous voltages exist within enclosure.
Installation and service should be performed only by
trained service personnel.
INSTALLATION
There is no need to remove the meter from its case to complete the
installation, wiring, and setup of the meter for most applications.
Instructions are provided for setting up a 12/24 VDC powered meter to
operate from 12 VDC and for changing the transmitter power supply to
output 5 or 10 VDC instead of 24 VDC, see page 17.
Unpacking
Remove the meter from box. Inspect the packaging and contents for
damage. Report damages, if any, to the carrier.
If any part is missing or the meter malfunctions, please contact your
supplier or the factory for assistance.
!
Model PD6000 Analog Input Process Meter Instruction Manual
15
Panel Mounting Instructions
Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm x
45 mm). Refer to Figure 1 below, for more details.
Clearance: allow at least 6.0" (152 mm) behind the panel for wiring.
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X
rating: 0.06" (1.5 mm) steel panel, 0.16" (4.1 mm) plastic panel.
Remove the two mounting brackets provided with the meter (back-off the two
screws so that there is ¼" (6.4 mm) or less through the bracket. Slide the
bracket toward the front of the case and remove).
Insert meter into the panel cutout.
Install mounting brackets and tighten the screws against the panel. To
achieve a proper seal, tighten the mounting bracket screws evenly until
meter is snug to the panel along its short side. DO NOT OVER TIGHTEN,
as the rear of the panel may be damaged.
Figure 1. 1/8 DIN Panel Cutout Dimensions
Figure 2. Panel Mounting Details
Panel
Gasket
Mounting
Bracket
Mounting
Screw
Removable
Connectors
3.622" (92 mm)
1.772"
(45mm)
Panel Cutout
to DIN 43700
Square Corners to 0.060"
(1.5mm) Max Radius
A
B
Tolerances:
A
: +0.032 (+0.8mm)
-0.000 (-0.0mm)
B: +0.024 (+0.6mm)
-0.000 (-0.0mm)
Refer to page
16 for mounting
dimensions
Model PD6000 Analog Input Process Meter Instruction Manual
16
Mounting Dimensions
Figure 3. Meter Dimensions - Side View
Figure 4. Meter Dimensions - Top View
N
O
N
C
N
C
C
N
O
C
N
O
N
C
N
C
C
N
O
C
+
-
R
Model PD6000 Analog Input Process Meter Instruction Manual
17
Configuration for 12 or 24 VDC Power Option
Warning!
Do not exceed voltage rating of the selected
configuration.
Meters equipped with the 12/24 VDC power option are shipped
from the factory ready to operate from 24 VDC.
To configure the meter for 12 VDC power:
1. Remove all the connectors.
2. Unscrew the back cover.
3. Slide the back cover about 1 inch.
4. Configure the J9 jumper, located behind the power
connector, for 12 V as shown below.
Figure 5. Jumper Configuration for 12/24 VDC Power
MAIN BOARD
24 VDC
12 VDC
POWER
J9
12 V
24 V
J9 CONFIGURATION
Factory
Default
M-LINK
+
_
Model PD6000 Analog Input Process Meter Instruction Manual
18
Transmitter Supply Voltage Selection (P+, P-)
All meters, including models equipped with the 12/24 VDC power
option, are shipped from the factory configured to provide 24 VDC
power for the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation, the internal
jumper J4 must be configured accordingly.
To access the voltage selection jumper:
1. Remove all the wiring connectors.
2. Unscrew the back cover.
3. Slide out the back cover by about 1 inch.
4. Configure the J4 jumper, located behind the input signal
connector, for the desired excitation voltage as shown.
Figure 6. Transmitter Supply Voltage Selection
Connections
All connections are made to removable screw terminal connectors
located at the rear of the meter.
Use copper wire with 60°C or 60/75°C insulation
for all line voltage connections. Observe all safety
regulations. Electrical wiring should be performed
in accordance with all applicable national, state,
and local codes to prevent damage to the meter
and ensure personnel safety.
Model PD6000 Analog Input Process Meter Instruction Manual
19
Connectors Labeling
The connectors’ label, affixed to the meter, shows the location of all
connectors available with requested configuration.
Warning!
Do not connect any equipment other than
Precision Digital’s expansion modules, cables,
or meters to the RJ45 M-LINK connector.
Otherwise damage will occur to the equipment
and the meter.
Figure 7. Connector Labeling for Fully Loaded PD6000
Power Connections
Power connections are made to a two-terminal connector labeled
POWER on Figure 7 on page 19. The meter will operate regardless of DC
polarity connection. The + and - symbols are only a suggested wiring
convention.
Figure 8. Power Connections
AC or DC
POWER
Required External Fuse:
5 A max, 250 V Slow Blow
POWER
+
-
Model PD6000 Analog Input Process Meter Instruction Manual
20
Signal Connections
Signal connections are made to a six-terminal connector labeled
SIGNAL on Figure 7. The COM (common) terminal is the return for the
4-20 mA and the ±10 V input signals.
Current and Voltage Connections
The following figures show examples of current and voltage connections.
There are no switches or jumpers to set up for current and voltage inputs.
Setup and programming is performed through the front panel buttons.
Figure 9. Transmitters Powered by Internal Supply
Figure 10. Transmitter Powered by Ext. Supply or Self-Powered
The current input is protected against current overload by a resettable
fuse. The display may or may not show a fault condition depending on
the nature of the overload.
The fuse limits the current to a safe level when it detects a fault
condition, and automatically resets itself when the fault condition is
removed.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100

PRECISION DIGITAL PD6000 User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI