Danfoss ECL Comfort 300 - C37 Operating instructions

Category
Thermostats
Type
Operating instructions
ECL COMFORT
ECL Comfort
Users Guide
C37
This guide is associated to ECL Card 087B4758
Installer:
By:
Date:
ECL COMFORT
ECL Comfort
Installation and
Maintenance
Mixing controller with ON/OFF controlled
hot-water charging
C37
VI.7C.E5.02
2002.02
Your personal week plan:
Heating 0 3 6 9 12 15 18 21 24
1 Monday
2 Tuesday
3 Wednesday
4 Thursday
5 Friday
6 Saturday
7 Sunday
Hot Water
0 3 6 9 12 15 18 21 24
1 Monday
2 Tuesday
3 Wednesday
4 Thursday
5 Friday
6 Saturday
7 Sunday
The factory setting is indicated in grey.
823-
5 - 8 18 - 22
6-8 16 - 22
823-
Table of Contents
Daily use
Section
1 Choose favourite display
2 Select controller mode
3 Adjust room and hot water temperature
4 Set personal daily plan
5 Advantages of the ECL Card
6 Hot points
7 Definitions
Installation and maintenance. Grey sections 10 and
onwards. Turn the guide over.
The documentation for the ECL Comfort controller is
composed of numbered sections. Only sections that are
relevant to your ECL Comfort controller are included here.
Daily use, turn the guide over sections 01 - 07
1 Choose favourite display
2 Select controller mode
3 Adjust room and hot water temperature
4 Set personal day plan
5 Advantages of the ECL Card
6 Hot points
7 Definitions
Table of Contents
Sections of the Installers part of this guide
The documentation for the ECL Comfort controller is
composed of numbered sections. Only sections that are
relevant to your ECL Comfort controller are included here.
Before you start
Installation
10 Identifying the system type
11 Mounting the ECL Comfort controller
12 Electrical connections 230 V a.c.
14 Placing the temperature sensors
15 Inserting the ECL Card
Basic Set-up
16 Adjusting the ECL Card settings
17 Setting the time and date - Line A
18 Monitoring temperatures and system units - Line B
19 Manual control - Line B
20 Setting the heat curve - Line C
21 Heating cut-out - Line 1
22 Flow temperature limits - Line 2
23 Room temperature influence - Line 3
26 Setting the PI-regulation - Line 4 - 7
27 Hot water controller - Line 1 and 2
Control & Overviews
29 Check list
30 ECL Card settings
31 Service parameters
Extended Service
32 Adjusting the service parameters
Miscellaneous
34 Copying with the ECL Card
Note:
The functions can only be realized as of ECL Card CI08 and
controller version V1.08.
The shown diagram is a fundamental and simplified
example and does not contain all components that are
necessary in heating systems.
If the system you are about to install is different than the
shown diagram of a standard heating system, feel free to
sketch an outline for comparison. Adaptation of heating
systems, See section 10.
List of components:
ECL Comfort 300
S1 Outdoor temperature sensor (ESM-10)
S2 Room temperature sensor (ESM-10) - circuit I
S3 Flow temperature sensor (ESM-) - circuit I
S4 Return temperature sensor (ESM-)
S5 Lower tank sensor (ESM-)
S6 Upper tank sensor (ESM-)
P1 Circulation pump for heating - circuit I
P2 Primary charging pump for hot water - circuit II
P3 Charging/circulation pump for hot water - circuit II
M1 Control valve with motor - circuit I (Heating)
Installation & maintenance
The ECL Card, grey side
for installation and maintenance.
Lines A to C, and lines 1 to
7 for basic settings, see overview
section 30.
Extended service parameters,
see section 31
The ECL Card: Installer’s
instruction
The grey side of the card must face
you when you change settings. For
daily use and during start-up the
yellow side of the card must face you.
Circuit indicator
Circuit
selector
Shift
button
Adjustment Controller
mode
The circuit indicator shows the selected circuit.
The ECL Card
For daily use and your personal adjustments the yellow side
of the ECL Card must be facing you.
The display
Each line, A, B, C, 1, 2 etc. of the ECL Card has its own
display. See section 1.
Controller mode
Manual operation (Used only at
maintenance and service)
Automatic operation
Constant comfort temperature
Constant reduced temperature
Standby mode
Arrow buttons. Switch between
the lines of the ECL Card.
Shift button. Switches between
temperatures, changeover points etc.
Adjust temperatures and values etc.
Circuit selector for switching between
heating and hot water circuit.
Room
temperature /
Hot water circuit II
Heating system
information
Today’s
programme
Day plans
A
B
C
1
2
3
4
5
6
7
Hot water - circuit IIHeating - circuit I
Line indicator
Circuit
6
036912
0
5
0
8
0 3 6 9 12 15 18 21
7
00
1
3
3
2
2
1
6
6
4
4
6
0369121
0
5
0
6
0 3 6 9 12 15 18 21
0
7
0
Controller mode
Manual operation (used only at
maintenance and service)
Automatic operation
Constant comfort temperature
Constant reduced temperature
Standby mode
Arrow buttons. Switch between
the lines of the ECL Card.
Shift button. Switches between
temperatures, changeover points etc.
Adjust temperatures and values etc.
Circuit selector for switching between
heating and hot water circuit.
55
A
52
1
2
ON
B
1
ON
3
ON
8
0 3 6 9 12 15 18 21 24
1
55
5
C
3
5
1
2
ON
036
B
1
ON
3
ON
8
0 3 6 9 12 15 18 21 24
1
913
5
C
3
913
0
A
2
8
9
10
199
Save energy - save money - improve your comfort
temperature
The ECL Comfort controller is designed by Danfoss for
temperature control of heating and hot water systems.
The ECL Comfort controller ensures you of the following;
Room and hot water temperatures will be adjusted to
your personal settings.
Lower temperatures and lower energy consumption
reduce costs and ensure optimum use of energy
resources.
The automatic pump motion program protects the
circulation pump against blocking.
Sketch an outline of your heating system
The ECL Comfort controller is designed for a wide range of
heating systems with different configurations and
capacities.
If your heating system differs from the diagrams shown in
section 10, you may want to sketch an outline of the
system about to be installed. This makes it easier to use
the Installer’s Guide, which will guide you step-by-step
from installation to final adjustments before the end-user
takes over.
Note!
The controller is pre-programmed with factory
settings which are shown in the relevant sections of this
guide.
However, you might come across some settings that
are not listed in this instruction. These settings are used in
connection with optional modules, and you can find a
description of the settings and the corresponding
parameters in the instruction for the optional module in
question.
How to use this guide
This guide is divided into two parts:
Daily Use (turn the guide over)
Yellow sections 1-7
Installation and maintenance:
Grey sections 10 and onwards
Before you start
VI.7C.E5.02
2002.02
Installation
Identifying the system type
10a
The ECL Comfort controller is a universal controller that
can be used for various heating systems. Based on the
shown standard systems, it is possible to configure
additional systems.
In this section you find the most frequently used systems. If
your system is not quite as shown below, find the diagram
which has the best resemblance with your system and
make your own combinations.
Installation
10b
Note:
The systems can only be realized with the ECL Card version
CI08 and controller version V1.08.
Note:
P2/M2*
For the control of the actuator use either relay output P2 or
Triac output M2, see section 12!
Note!
System diagrams in this instruction are principal drawings and
do not contain all components which are necessary in heating
systems.
Line 51 Water pump / change-over valve
Setting
OFF
Line 52 Closed valve / normal operation
Setting
OFF
Line 53 PI reference when heating HW
Setting
OFF
Line 90 P3 = hot-water circulation pump
Setting
OFF
Heating system type 1
Heating system and secondarily connected hot water
charging system
Line 51 Water pump / change-over valve
Setting
ON
Line 52 Closed valve / normal operation
Setting
OFF
Line 53 PI reference when heating HW
Setting
OFF
Line 90 P3 = hot-water circulation pump
Setting
OFF
Heating system type 2
Indirectly connected heating system and secondarily
connected hot water charging system
Heating system type 3
Indirectly connected heating system and secondarily
connected hot-water system with circulation pump
Line 51 Water pump / change-over valve
Setting
OFF
Line 52 Closed valve / normal operation
Setting
OFF
Line 53 PI reference when heating HW
Setting
OFF
Line 90 P3 = hot-water circulation pump Setting ON
Heating system type 4
Indirectly connected heating system and secondarily
connected hot-water system with circulation pump
Line 51 Water pump / change-over valve
Setting
ON
Line 52 Closed valve / normal operation
Setting
OFF
Line 53 PI reference when heating HW
Setting
OFF
Line 90 P3 = hot-water circulation pump
Setting
ON
Heating system type 5
Indirectly connected heating system and primarily
connected hot water system with circulation pump
Line 51 Water pump / change-over valve
Setting
ON
Line 52 Closed valve / normal operation
Setting
OFF
Line 53 PI reference when heating HW
Setting
ON
Line 90 P3 = hot-water circulation pump
Setting
ON
10c
Note:
The following heating systems can only be implemented with
the relay module ECA 80.
Note:
P2/M2*
For the control of the actuator use either relay output P2 or
Triac output M2, see section 12!
Heating system type 7
Indirectly connected heating system and secondarily
connected hot-water charging system with circulation
pump.
Line 51 Water pump / change-over valve
Setting
ON
Line 52 Closed valve / normal operation
Setting
OFF
Line 53 PI reference when heating HW
Setting
OFF
Line 90 P3 = hot-water circulation pump
Setting
ON
Heating system type 6
Indirectly connected heating system and secondarily
connected hot-water charging system with circulation
pump.
Line 51 Water pump / change-over valve
Setting
OFF
Line 52 Closed valve / normal operation
Setting
OFF
Line 53 PI reference when heating HW
Setting
OFF
Line 90 P3 = hot-water circulation pump
Setting
ON
Installation
Installation
Mounting the ECL Comfort
controller
11a
For easy access, you should mount the ECL Comfort
controller near the heating unit. Select one of the three
following methods:
Mounting on a wall
Mounting on a DIN rail
Mounting in a panel
Screws and rawlplugs are not supplied.
Mounting on a wall
Socket for mounting on wall: Order code No. 087B1149.
Mount the terminal box on a wall with a smooth surface.
Establish the electrical connections and position the
controller in the box. Secure the controller with the fixing
screw.
Mounting on a DIN rail
Mounting kit: Order code No. 087B1145.
A mounting kit is necessary to mount the box with the
controller on a DIN rail.
Mounting in a panel
Connector set: Order code No. 087B1148.
The panel plate thickness must not exceed 3 mm.
Prepare a cut-out with the dimensions 92 x 138 mm. Pull
off the right side of the lid by means of a screwdriver.
Insert the controller into the panel cut-out and fix it with the
two locks which are placed diagonally in two corners of the
controller.
Installation
Installation
11b
Installation
Installation
12a
Electrical connections
230 V a.c.
230 V a.c. connections - without safety thermostat
Establish these jumpers:
1 to 5, 5 to 8, 8 to 10, 10 to 12, 12 to 14 (optional: 14 to
26 and 26 to 29), and 2 to common N-terminal.
Establish these jumpers:
1 to 8, 8 to 10, 10 to 12, 12 to 14 (optional: 14 to 26
and 26 to 29).
Safety thermostat:
4, 5 and 10 with ST- (safety thermostat) and 2 to
common N-terminal.
230 V a.c. connections - with safety thermostat
(example M1)
Terminal Description Max. load
1 (L) Voltage supply
230 V a.c.
2 (N) Voltage supply
230 V a.c.
3 (M1) Gear motor 0.2A/230 V a.c.
- open
4 (M1) Gear motor
- close
Alternative:
Thermo actuator 0.2A/230 V a.c.
5 (M1) Phase for motor output
6 (M2) Gear motor 0.2A/230 V a.c.
- open
7 (M2) Gear motor 0.2A/230 V a.c.
- close
8 (M2) Phase for motor output
9 (P1) Circulation pump
for heating circuit 4(2)A/230 V a.c.
10 Phase for pump relay
- R1
11(P2)/(M2) Hot water pump - change-
over valve/ON/OFF-valve 4(2)A/230 V a.c.
12 Phase for pump/valve
output - R2
13(P3) Circulation pump ON/OFF 4(2)A/230 V a.c.
14 Phase pump relay - R3
This circuit diagram is only valid
if Danfoss actuators are used
Wire cross section: 0.75 - 1.5 mm
2
Total cable length: Max. 50 m
Cable type: Copper cable
Electrical connections
Max. 2 x 1.5 mm
2
wires can be inserted into each screw
terminal.
Note:
Incorrect connections can damage the TRIAC outputs. Max.
load (terminals 3, 4, 6 and 7) 0.2 A/230 V a.c.!
12b
Option:
Relay module ECA 80 (contacts: max. load 4(2)A/230 V a.c.)
25 (R4) Alarm relay
28 (R5) Control of the hot-water charging pump in heating
systems 6 and 7.
Note:
Relay module ECA 80 is only active when the outdoor
temperature sensor is connected.
Note:
P2/M2*
For the heating systems 2, 4, 5 and 7 it must be determined
whether the actuator is to be controlled by means of the
terminals 6 and 7 (M2) or the terminal 11, cf. section 10.
Terminals 6 and 7: Only control valves with 3-point control
Terminal 11: For change-over valves ON/OFF
Optional
Optional
Make sure that the surface of the pipe is clean at the area
where the sensor is mounted.
Return temperature sensor
(ESMU, ESM-11 or ESMC types)
The return sensor should always be placed max. 15 cm
from the mixing point. It should always be placed on a pipe
in which the water flow never stops.
Room temperature sensor
(ESM-10, ECA 60 and 61 remote control)
Place the room sensor in the room where the temperature
is to be controlled. Do not place it on outside walls or close
to radiators, windows or doors.
14
Placing the temperature
sensors
It is important that the sensors are mounted in the correct
position in your heating system.
Special attention should be paid to the following sensors:
Outdoor temperature sensor
(ESM-10 type)
The outdoor sensor should be mounted on the north side
of the building where it is less likely to be exposed to
direct sunshine. It should not be placed close to doors or
windows.
Flow temperature sensor
(ESMU, ESM-11 or ESMC types)
Place the sensor max. 15 cm from the mixing point. In
systems with heat exchanger, Danfoss recommends the
ESMU-type to be inserted into the exchanger flow outlet.
Installation
Installation
Hot water temperature sensor
(ESMU or ESMB types)
Place the hot water sensor according to the
manufacturer’s specification.
Connecting the temperature sensors
Terminal Description Type (recomm.)
15 and 16 System device bus
Connections for room panel/ ECA 60
remote control/relay module* ECA 61/ECA 80
17 and 16 Outdoor temp. sensor S1 ESM-10
18 and 16 Room temp. sensor S2 ESM-10
19 and 16 Flow temp. sensor S3 ESMU/ESM-11
ESMC
20 and 16 Return temp. sensor S4 ESMU/ESM-11/
ESMC
21 and 16 Hot-water tank temp. sensor ESMU/ESMB
- lower S5
22 and16 Hot-water tank temp. sensor ESMU/ESMB
- upper S6**
* The system device bus/room panel/remote control
is only active when the outdoor temperature sensor
is connected.
** If only
one hot-water temperature sensor is used, it
must be connected to terminal 22!
Wire cross section for sensor connections: Min. 0.4 mm
2
Total cable length: Max. 50 m (sensor and system device
bus).
Cable type: Copper cable
Note:
Cable lengths of more than 100 m may cause noise sensibility
(EMC).
12c
Note:
Valid for ESM-11: Do not move the sensor after it has been
fastened in order to avoid damage to the sensor element.
Understanding the ECL Card
The ECL Card contains factory settings for a standard
heating system. If the actual heating system differs from
the standard system, the controller must be adjusted
accordingly. After the adjustment, the new settings
should be stored on the ECL Card.
For ECL Card copying and daily use including
adjustment of temperatures and time periods, insert the
ECL Card with the yellow side facing you.
For system set-up adjustments, the grey side of the
ECL Card - the installer’s side - must be facing you.
As a main rule, the ECL Card should always remain in
the controller during service, maintenance and settings.
If the card is removed please note that:
The controller settings are locked after approx. 10
min.
The ECL Card must not be exposed to direct heat or
sunshine
If several controllers are installed in the heating system
you can write a title on the ECL Card with a permanent
ink pen.
15a
Inserting the ECL Card
How to insert your ECL Card the first time
After the power has been switched on, open the lid on the
front side of the controller.
Place the ECL Card with the yellow side facing you. This
enables the controller to read the ECL Card data.
The controller immediately starts to copy the factory
settings and heating system type from the ECL Card. After
copying, the display will show the heating system type the
controller is set to control. After approx. 10 sec. the display
will change to display line C.
The controller is now ready to be set to control your
heating system.
Installation
Installation
Software version
for ECL Card
Line
Circuit
Time
Outdoor
temperature
Desired
room
temperature
C
C99
Y
0
P
C73
08 108
8
0 3 6 9 12 15 18 21 24
1
913
5
C
3
Software version
for controller
15b
17
Setting the time and date -
Line A
In case of a power failure which lasts longer than 12
hours, the time and the date have to be set again.
All other settings are stored as programmed.
Go to line A.
Use the shift button to switch between minutes,
hours, year, month and day
Set the correct time and date
Use the yellow side of the ECL Card to enter the day
plan settings.
See User’s Guide, section 4.
16
Adjusting the ECL Card
settings
Update of the ECL Card after maintenance and service
All new settings can be stored on the ECL Card. For
details about copying, see section 34.
General principles
When the controller is connected and operating you can
check and adjust all or some of the basic settings on the
grey side of the ECL Card.
Use the arrow buttons to move from line to line
of the ECL Card, for example line 2:
Line
indicator
Settings to
be adjusted
Value in range in-
dicator
Circuit
1
1
ON
2
ON
09
2
04
3
ON
Use the minus/plus buttons to adjust the
settings.
In some displays more than one setting or value
can be adjusted. Use the shift button to switch
between the options.
The circuit selector shifts between circuit I
and II. You can adjust all settings and service
parameters individually in both circuits, ie.
circuit II.
Basic set-up
Basic set-up
01
01
90210
5
A
3
Actual time
Month, day
Year
The grey
side of the
ECL Card
The gear motor
opens or closes
the valve as long as the the relevant button is
pressed.
The thermo actuator
(according to version *)),
opens (NC) the valve as long as the
button is pressed.
*) NO - normally open
NC - normally closed
Pumps are switched off or on when the
relevant button is pressed.
19
Manual control - Line B
Basic set-up
Go to line B.
Shift to manual mode
Monitoring temperatures
and system units - Line B
18
Go to line B.
Note! This display also shows actual and reference values
of flow and return temperature during hot water charging.
The activity of the motorized valve is shown as arrows
below the valve symbol. When the circulation pump is
operating, it is indicated as ON below the pump symbol.
If a sensor is not mounted or is disconnected, the display
will indicate it as “- -”.
If the sensor is short-circuited, the display will indicate it as
- - - “.
If you are in doubt, remove the controller and check the
ohmic value between the relevant terminals.
Push the shift button to see:
- the calculated flow temperature
- the return temperature set points
Relationship between temperature and ohmic value
-50
800
900
1000
1100
1200
1300
1400
1500
1600
-25 0 25 50 75 100 125 150
Temperature
Ohm
Basic set-up
0360
B
3
ON
1
1
ON
2
ON
Controlled
units
Controller mode
0360
B
3
ON
1
1
ON
2
ON
Flow temperature
Return temperature
Select circuit II to see the actual temperatures of
upper and lower tank sensors.
35
B
52
3
ON
1
1
ON
2
ON
S6 actual
Upper tank sensor
S5 actual
Lower tank sensor
The grey
side of the
ECL Card
The grey
side of the
ECL Card
-10 °C 961 Ohm
0 °C 1000 Ohm
10 °C 1039 Ohm
20 °C 1078 Ohm
30 °C 1117 Ohm
40 °C 1156 Ohm
50 °C 1195 Ohm
60 °C 1234 Ohm
70 °C 1273 Ohm
80
o
C 1312 Ohm
90
o
C 1351 Ohm
100
o
C 1390 Ohm
110
o
C 1429 Ohm
Note!
During manual operation, the pump motion is OFF.
1
ON
1
Check the activation direction of the motorized valve either
by looking at it or by feeling whether the temperature of the
actual pipe changes as expected.
This operation applies to both circuits.
Select the unit you want to control. The selected
unit symbol will flash.
1
1
1
Floor heating systems
This controller is factory set for radiator systems, which are
typically high flow temperature systems.
To control floor heating systems, which are typically low flow
temperature systems, you need to change the heat curve
according to your type of system.
Setting the heat curve -
Line C
20a
Go to line C.
The symbol for the slope of the heat curve will
flash.
Make your adjustments.
8
C
1
3
ON
0
1
1
ON
2
ON
Slope
Displacement
Adjust the slope of the heat curve, if required.
If you want to adjust the parallel displacement of
the heat curve, push the shift button. The symbol
for the parallel displacement will flash.
Basic set-up
Basic set-up
20b
Slope
Circuit Setting range Factory setting
I 0.2 ... 3.4 1.8
Parallel displacement
Circuit Setting range Factory setting
I -9... +9 0
Parallel displacement
Circuit Setting range Typical setting
I -9... +9 0
Slope
Circuit Setting range Typical setting
I 0.2 ... 3.4 1.0
The grey
side of the
ECL Card
The grey
side of the
ECL Card
-20 -10 0 10 20-30
20
30
40
50
60
70
80
90
1.0
1.4
0.6
0.2
1.8 2.2 3.0 3.4
100
110
2.6
o
C
o
C
Flow temperature limits -
Line 2
22
Go to line 2.
The left end of the range indicator flashes.
Adjust the min. limit of your heating system.
Select the max. limit. The right end of the range
indicator flashes.
Adjust the max. limit.
Heating cut-out - Line 1
21
1
2
ON
8
1
1
1
ON
3
ON
Set the outdoor temperature limit at which you
want the heating system to stop.
Go to line 1.
Basic set-up
Basic set-up
This function can save energy by stopping the heating
system when the outdoor temperature gets above a set limit.
The heating system is activated again when the actual
outdoor and the accumulated temperatures get below the set
limit.
The accumulated T
out
symbolises the heat stored in the
building.
18 ˚C
Temp
Actual T
out
Accumulated T
out
Time
Heating
Heating off
Heating
1
1
ON
2
ON
09
2
04
3
ON
Max. flow
temperature
Min. flow
temper-
ature
Temperature
range for flow
temperature
1 Limit for heating cut-out
Circuit Setting range Factory setting
I 10 ... 30 °C 18 °C
2 Flow temperature min., max. limits
Circuit Setting range Factory setting
I 10 ... 110 °C min. 40 °C max. 90 °C
The grey
side of the
ECL Card
The grey
side of the
ECL Card
ON
OFF
Room temperature
influence - Line 3
23a
Basic set-up
Basic set-up
+
_
1
2
ON
0-4
0
3
1
ON
3
ON
The room sensor in the reference room
registers the difference between the desired
and the actual room temperature. The flow
temperature reference will be corrected to
eliminate this difference.
B: Reference room control
Used if your heating system is not equipped with radiator
thermostats and you select the room with room sensor as
a temperature reference for the rest of the rooms.
(However, should you have a few radiator thermostats
installed, make sure that they are fully open).
Set a positive value for min. influence and a
negative value for max. influence.
This section is only relevant if you have installed a room
sensor or ECA 60/61. There are two basic principles for
control of the room temperature influence:
A: Max. room temperature limitation
Use this limitation if your heating system is fully equipped
with radiator thermostats and you also want to obtain a
max. limitation of the room temperature. The controller will
allow for free heat gains, i.e. solar radiation or heat from a
fire place, etc.
The max. influence determines how much the
room temperature should influence the flow
temperature.
Go to line 3.
Select the max. influence.
The bar below the range indicator flashes in the
right side of the display.
Adjust the max. influence.
T
ROOM
Set
T
ROOM
Influence
Max. limitation
Min.
influence
Max.
influence
Example
The actual room temperature is 2
o
C too high.
The influence at max. limitation (right corner of the display) is
set to
-40.
The influence at min. limitation (left corner of the display) is
set to 0.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x
-40 x H x 0.1= -14.4
o
C.
Example 1
The actual room temperature is 2
o
C too low.
The influence at max. limitation (right corner of the display) is
set to
-20.
The influence at min. limitation (left corner of the display) is
set to 20.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x 20 x H x 0.1= 7.2
o
C
Example 2
The actual room temperature is 2
o
C too high.
The influence at max. limitation (right corner of the display) is
set to
-35.
The influence at min. limitation (left corner of the display) is
set to 35.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x (-35) x H x 0.1= -12.6
o
C.
23b
3 Room temperature influence
Circuit Setting range Factory setting
I 0 ... 99/-99 ... 0 min. 0 max. -40
The grey
side of the
ECL Card
The grey
side of the
ECL Card
+
_
Influence
Min. limitation
Max. limitation
T
ROOM
Set
T
ROOM
Setting the PI-regulation -
Line 4-7
(heating)
26a
Go to line 4.
1
2
ON
4
80
1
ON
3
ON
Setting to be adjusted
Line
indicator
Set the proportional band.
A higher value will result in a stable, but slow
regulation of the flow temperature.
Go to line 5.
Set a high integration time constant to obtain a
slow but stable reaction to deviations.
A small integration constant will make the
controller react fast but with less stability.
Go to line 6.
Set the running time of the motorized valve
according to the example on the opposite page.
This is the time it takes the valve to move from
closed to fully open position.
Go to line 7.
Set the neutral zone to a high value if you can
accept a high variation in flow temperature.
When the actual flow temperature is within the
neutral zone, the controller does not activate the
motorized valve.
Basic set-up
Basic set-up
If you want to tune the PI-regulation precisely, you can
use the following method:
Set the integration time (line 5) to its max. value (999 sec.).
Decrease the value for the proportional band (Line 4) until
the system starts hunting with a constant amplitude (it might
be necessary to force the system by setting an extreme
value).
Find the critical time period on the temperature recording or
use a stop watch.
This time period will be characteristic for the system, and you
can evaluate the settings from this critical period.
Integration time = 0.85 x critical time period
Proportional band = 2.2 x proportional band value in the
critical time period.
If the regulation seems to be too slow, you can decrease the
proportional band value by 10%.
Note!
Make sure there is a consumption when you set the
parameters.
How to calculate the running time of the motorized valve
The running time of the motorized valve is calculated using the
following methods:
Seated valves
Running time = Valve stroke (mm) x actuator speed (sec/mm)
Example: 5.0 mm x 15 sec/mm = 75 sec.
Rotating valves
Running time = Turning degrees x actuator speed (sec/degr.)
Example: 90 degrees x 2 = 180 sec.
VS2 15 3.0 AMV 100 90 270
VS2 15...25, VM2 15...25, AMV(E)
VB2 15...20 5.0 10, 20 15 75
VS2 15...25, VM2 15...25,
VB2 15...20 5.0 AMV(E) 30 3 15
VM2 32, VB2 25 7.0 AMV(E) 20 15 105
VM2 32, VB2 25 7.0 AMV(E) 30 3 21
Valve type Valve Actuator Actuator Running
stroke type speed time
(mm) (sec./mm) (sec.)
26b
4 Proportional band
Circuit Setting range Factory setting
I 1 ... 250 K 80 K
5 Integration time constant
Circuit Setting range Factory setting
I 5 ... 999 sec. 30 sec.
6 Running time of the motorized valve
Circuit Setting range Factory setting
I 5 ... 250 sec. 35 sec.
7 Neutral zone
Circuit Setting range Factory setting
I 0 ... 9 K 3 K
The grey
side of the
ECL Card
The grey
side of the
ECL Card
Time
Temp.
Critical time period
Note!
The neutral zone is symmetrical around the flow reference
value.
Cut-in and cut-out
temperature at hot-water
charging, Line 1 and 2
27a
The controller with the ECL Card C37 can control the hot
water temperature with either one or two sensor(s). The
controller will automatically register the number of
sensors.
Select circuit II
Note!
If only one sensor is mounted, the hot water temperature
difference is equal to the cut-out temperature minus the
cut-in temperature.
Example: 45 °C minus 40 °C = 5 K
Basic set-up
Basic set-up
Set the difference.
Example:
Desired hot water temperature 60 °C
Cut-out difference 15 K
Calculated cut-out temperature
(60-15 =) 45 °C
Set the difference.
Example:
Desired hot water temperature 60 °C
Cut-in difference 20 K
Calculated cut-in temperature
(60-20 =) 40 °C
--------------------------------
--------------------------------------
--------------------------------
Temp.
One sensor (S6)
Cut-out difference - line 1
Cut-in difference - line 2
Cut-out
Time
P2/P3
Desired hot
water tempera-
ture (charging
temp.)
S6
Two sensors (S5 + S6)
--------------------------------------
---------------------------------------
Temp.
Cut-out difference - line 1
Cut-in difference - line 2
Cut-in
Cut-out
Time
P2/P3
Desired hot
water tempera-
ture (charging
temp.)
S6
S5
27b
2 Difference 2, cut-in temperature - upper sensor
Circuit
Setting range Factory setting
II 1 ... 30 K 20 K
Set the difference between the desired tank temperature and cut-
in temperature during hot water charging.
1 Difference 1, cut-out temperature - lower sensor
Circuit
Setting range Factory setting
II 1 ... 30 K 15 K
Set the difference between the desired tank temperature and cut-
out temperature during hot water charging.
Cut-in
The grey
side of the
ECL Card
The grey
side of the
ECL Card
Go to line 1.
Go to line 2.
Adapting the ECL Comfort controller to the heating
system
29b
Check list
If your heating system differs from the diagram shown on
the overleaf of the cover, you should check and perhaps
alter the following service parameters.
To ensure that you have the correct settings see section 10
for examples of different heating systems.
Control & overviews
Turn the ECL Card so that the grey side faces
you.
Set the time and the date (Line A)
See section 17.
Check all settings referring to the grey side of
the ECL Card
See sections 20 to 27.
51 Water pump / change-over valve
52 Closed valve / normal operation
53 PI reference when heating hot water
90 P3 = hot-water circulation pump
Line
Check list
Is the ECL Comfort controller ready for use?
Make sure that the power supply is connected to
terminals 1 (Live) and 2 (Neutral).
See section 12.
Check that valves and pumps are connected to
the correct terminals.
See section 12.
Check that all sensors are connected to the
correct terminals.
Mount the controller, and switch on the power.
Insert the ECL Card with the yellow side facing
you and press
, if necessary.
See section 15.
Select manual operation in the controller mode.
See section 2
in the user’s guide.
Check that valves open and close, and that
pumps start and stop when operated manually.
See section 19.
Check that the temperatures shown in display A
and B match the actual sensors, both for circuit I
(heating) and circuit II (hot water).
See section 1
in the user’s guide.
Control & overviews
29a
ECL Card settings
(circuit II: Hot water service)
30b
Setting range Factory setting Your settings
1
Difference 1 - hot water temperature
1 ... 30 K 15 K
Cut-out condition,
see section 27.
2
Difference 2 - hot water temperature
1 ... 30 K 20 K
Cut-in condition,
see section 27.
ECL Card settings
(circuit I: Heating)
30a
A Time and date See sections 16 & 17
B System information See sections 18 & 19
C Heat curve See section 20
Heat curve - Slope
0.2 ... 3.4 1.8
Set the slope of the heat curve
,
see section 20
Heat curve - Parallel displacement
-9 ... +9 K 0 K
Set the parallel displacement of the
heat curve
, see section 20
1
Limit for heating cut-out
10 ... 30 °C 18 °C
Save energy by stopping the heating system
when the outdoor temperature gets above
a certain limit,
see section 21.
2
Flow temperature min.-/max. limits
10 ... 110 °C min. 40, max. 90 °C
The limits for min. and max. flow
temperature
, see section 22.
3
Room temperature influence
0 ... +99 / -99 ... 0 min. 0, max. -40
The room temperature’s influence on the
flow temperature control,
see section 23.
4
Proportional band
1 ... 250 K 80 K
Set the PI-regulation
, see section 26.
5
Integration time constant
5 ... 999 sec. 30 sec.
Set the PI-regulation,
see section 26.
6
Running time of motorized valve
5 ... 250 sec. 35 sec.
Set the PI-regulation,
see section 26.
7
Neutral zone
0 ... 9 K 3 K
Set the PI-regulation,
see section 26.
Setting range Factory setting Your settings
Control & overviews
Control & overviews
A Time and date See sections 16 & 17
B System information See sections 18 & 19
C
K
o
C
o
C
K
sec.
sec.
K
K
K
Control & overviews
Control & overviews
Service parameters (10-199)
31a
Service parameters (10-199)
31b
10 Choice of room panel/remote control
0 ... 5 0
11 Reduced temperature dependent
on outdoor temperature
OFF/-29 ... +10 °C -15 °C °C
12 Boost
0 ... 99% 0% %
13 Reference ramping
0 ... 99 Min. 0 min. min.
14 Optimising time constant
OFF/10 ... 59 OFF
15 Adaptive function of room
temperature
OFF/1 ... 30 OFF
17 Temperature reference feedback
OFF/1 ... 20 K OFF K
20 Optimisation based on room/
outdoor temperature
ON/OFF OFF
21 Total stop
ON/OFF OFF
22 Pump motion
ON/OFF ON
23 Valve motion
ON/OFF OFF
24 Gear motor/
thermo actuator
ON/OFF ON
31 Return temperature limitation
- upper limit (X)
-30 ... +15 °C +15 °C °C
32 Return temperature limitation
- lower limit (Y)
10 ... 110 °C 40 °C °C
33 Return temperature limitation
- upper limit (X)
-30 ... +15 °C -15 °C °C
34 Return temperature limitation
- lower limit (Y)
10 ... 110 °C 60 °C °C
35 Return temperature influence
- max.
-9,9 ... 0 ... +9,9 -2
36 Return temperature influence
- min.
-9,9 ... 0 ... +9,9 0
37 Adaptive function of return
limitation
OFF/1 ... 50 25
43 Priority or parallel operation
OFF/1 ... 99 K OFF K
52 Closed valve/normal operation
ON/OFF OFF
141 Override input selection
OFF/1 ... 6 OFF
Circuit I (heating)
Line Setting range Factory setting Your setting
Circuit I (heating)
Line Setting range Factory setting Your setting
147 Acceptable temperature deviation
below reference temperature (heat
curve)
DT1
ALARM
OFF/1 ... 30 K OFF K
148 Acceptable temperature deviation
above reference temperature (heat
curve)
DT2
ALARM
1 ... 30 K 5 K K
149 Time interval Dt
ALARM
before activation of alarm
function
1 ... 99 min. 10 min. min.
174 Motor protection
OFF/10...59 min. OFF
196 Service pin LON
ON/OFF OFF
197 LON reset
ON/OFF ON
198 Summer time change
ON/OFF ON
199 Slave address
0 ... 9 15
Service parameters (10-199)
31c
Circuit II (hot-water service)
Line Setting range Factory setting Your setting
16 Frost protection by circulation pump
ON/OFF OFF
30 Return temperature limitation (hot-water
charging)
10 ... 110 °C 60 °C °C
40 Hot-water pump post run
(P2)
0 ... 9 min. 1 min.
41 Hot-water charging pump post run
(P3)
0 ... 9 min. 1 min.
44 Max. hot-water charging time
OFF/1 ... 100 min. OFF min.
45 Hot-water charging deactivation
0 ... 250 min. 0 min. min.
51 Hot-water pump/change-over valve
ON/OFF OFF
53 Reference temperature at S3
when charging hot water
ON/OFF OFF
55 Activation/deactivation of
circulation pump during
hot-water charging
ON/OFF OFF
78 Reference temperature for
anti-bacteria function
OFF/1 ... 100
o
C OFF
o
C
80 Anti-bacteria function period
5 ... 250 min. 120 min. min.
90 P3 = hot-water circulation pump
ON/OFF OFF
141 Override input selection
OFF/1 ... 6 OFF
Control & overviews
Control & overviews
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39

Danfoss ECL Comfort 300 - C37 Operating instructions

Category
Thermostats
Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI