Danfoss ECL Comfort 300 - C47 Operating instructions

Type
Operating instructions
C47
C47
VI.7C.Q2.02
2005.09
VI.7C.Q2.02
2005.09
www.danfoss.com
User's Guide
Installer's Guide
www.danfoss.com
ECL Comfort
Installer's Guide
ECL Comfort
User's Guide
*087R8073*
*VI7CQ202*
*087R8073*
*VI7CQ202*
Mixing and DHW controller
The shown diagram is a fundamental and simplified example and
does not contain all components that are necessary in a system.
If the system you are about to install differs from the shown
diagram of a standard heating system, feel free to sketch an outline
for comparison. Adaptation of systems, see section 10.
List of components:
ECL Comfort 300
S1 Outdoor temperature sensor
S2 Flow temperature sensor, circuit I
S3 Return temperature sensor, circuit I
S4 Flow temperature sensor, circuit II
S5 Return temperature sensor, circuit II or
DHW tank temperature sensor, lower, circuit I
S6 DHW tank temperature sensor, upper
P1 Circulation pump, heating, circuit I
P2 Charging pump, DHW, circuit II
P3 Circulation pump, DHW, circuit II
M1 Motorized control valve, heating, circuit I
M2 Motorized control valve, DHW, circuit II
Circuit
indicator
Circuit
selector
Shift
button
Adjust-
ment
Controller
mode
Controller mode
Manual operation (used only at maintenance
and service)
Scheduled operation
Constant comfort temperature
Constant setback temperature
Standby mode
Arrow buttons. Switch between the lines of the ECL
Card.
Shift button. Switches between temperatures,
changeover points etc.
Adjust temperatures and values etc.
Circuit selector for switching between the circuits.
Safety Note
To avoid injury of persons and damages to the device, it is
absolutely necessary to read and observe these instructions
carefully.
Necessary assembly, start-up, and maintenance work must be
performed by qualified and authorized personnel only.
This guide is associated with ECL Card 087B4821
Installer:
By:
Date:
Table of Contents
Sections in the Installers Guide
The documentation for the ECL Comfort controller is
composed of numbered sections. Only sections relevant to
your ECL Comfort controller are included here.
Before you start
Installation
10 Identifying the system type
11 Mounting the ECL Comfort controller
12 Electrical connections 230 V a.c.
13 Electrical connections 24 V a.c.
14 Connecting and placing the temperature sensors
15 Inserting the ECL Card
Basic Set-up
16 Adjusting the ECL Card settings
17 Setting the time and date - line A
18 Monitoring temperatures and system units - line B
19 Manual control - line B
20 Setting the heat curve - line C
21 Heating cut-out - line 1
22 Flow temperature limits - line 2
23 Room temperature influence - line 3
26 Control parameters - lines 4-7
27 Cut-in and cut-out temperature at DHW charging
- lines 1-2, circuit II
Control & Overviews
29 Check list
30 ECL Card settings
31 Service parameters
Extended Service
32 Adjusting the service parameters
Miscellaneous
34 Copying with the ECL Card
User's Guide (turn the guide over for sections 1-7)
1 Choose your favorite display
2 Select circuit mode
3 Set your room and DHW charging temperature
4 Set your personal schedule
5 Advantages of the ECL Card
6 Hot points
7 Definitions
VI.7C.Q2.02
Card C47
2005.09
Sketch your application
The ECL Comfort controller series is designed for a wide
range of heating, hot-water and cooling systems with
different configurations and capacities.
If your system differs from the diagrams shown in section
10, you may want to make a sketch of the system about to
be installed. This makes it easier to use the Installer’s Guide,
which will guide you step-by-step from installation to final
adjustments before the end-user takes over.
The controller is pre-programmed with factory settings that are
shown in the relevant sections of this guide.
However, you might come across some settings that are not listed
in this instruction. These settings could be related either to recent
updates or the use of optional modules (which are described in
the instructions in question).
How to use this guide
This guide is divided into two parts:
Users Guide: Yellow sections 1-7
Installer's Guide: Grey sections 10 and onwards
The application C47 is very flexible. These are the basic
principles:
Heating:
Typically, the flow temperature is always adjusted according to
your requirements.
The flow temperature sensor (S2) is the most important sensor.
The desired flow temperature at S2 is calculated in the ECL
controller, based on the outdoor temperature (S1). The lower the
outdoor temperature, the higher the desired flow temperature.
The motorized control valve (M1) is opened gradually when the
flow temperature is lower than the desired flow temperature and
vice versa.
The return temperature (S3) to the district heating supply should
not be too high. If so, the desired flow temperature can be
adjusted (typically to a lower value) thus resulting in a gradual
closing of the motorized control valve.
If the measured room temperature does not equal the desired
room temperature, the desired flow temperature can be adjusted.
DHW:
If the measured DHW temperature is lower than the desired DHW
heating temperature minus the cut-in difference, the desired flow
temperature at S4 is kept in order to heat the DHW.
Before you start
Installation
The ECL Comfort controller is a universal controller that can
be used for various systems. Based on the shown standard
systems, it is possible to configure additional systems.
In this section you find the most frequently used systems. If
your system is not quite as shown below, find the diagram
which has the best resemblance with your system and make
your own combinations.
The functions can only be realized with ECL Comfort 300 and as of
controller version 1.08.
10.1 Indirectly connected heating system with
mixing loop and secondarily connected
storage tank with built-in heating coil
System settings
Circuit Line Description Recomm.
setting
I 17
Influence on desired flow
temperature
3
II 52 Closed valve / normal operation ON
II 83
Internal relationship between
circuit I and II
4
II 84
Pump P2 in DHW circuit, primary
side
OFF
II 140
Function of temperature sensor
S5
OFF
System diagrams in this instruction are principal drawings and do
not contain all components which are necessary in your systems.
Identifying the system type
10a
Installation
10.2 Indirectly connected heating system and
primarily connected storage charging
system
System settings
Circuit Line Description Recomm.
setting
II 52 Closed valve / normal operation ON
II 84
Pump P2 in DHW circuit, primary
side
OFF
10.2a Indirectly connected heating system and
primarily connected storage charging
system
System settings
Circuit Line Description Recomm.
setting
II 52 Closed valve / normal operation OFF
II 84
Pump P2 in DHW circuit, primary
side
OFF
10b
Installation
10.3 Indirectly connected heating system and
primarily connected storage tank with built-
in heating coil
System settings
Circuit Line Description Recomm.
setting
II 52 Closed valve / normal operation ON
II 84
Pump P2 in DHW circuit, primary
side
OFF
10c
Installation
10d
The following heating systems are only applicable with relay
module ECA 80
10.4 Indirectly connected heating system with
mixing loop and secondarily connected
storage charging system
System settings
Circuit Line Description Recomm.
setting
I 17
Influence on desired flow
temperature
3
II 52 Closed valve / normal operation ON
II 83
Internal relationship between
circuit I and II
4
II 84
Pump P2 in DHW circuit, primary
side
OFF
II 140
Function of temperature sensor
S5
OFF
Installation
10e
10.5 Indirectly connected heating system and
secondarily connected storage charging
system with mixing loop
System settings
Circuit Line Description Recomm.
setting
I 17
Influence on desired flow
temperature
3
I 43
Parallel operation of DHW and
heating circuits
OFF
II 52 Closed valve / normal operation ON
II 83
Internal relationship between
circuit I and II
2
II 84
Pump P2 in DHW circuit, primary
side
OFF
II 140
Function of temperature sensor
S5
OFF
Installation
10.6 Indirectly connected heating system and
primarily connected storage charging
system with pre-controlled circuit
System settings
Circuit Line Description Recomm.
setting
II 52 Closed valve / normal operation ON
II 84
Pump P2 in DHW circuit, primary
side
OFF
10.6a Indirectly connected heating system and
primarily connected storage charging
system with pre-controlled circuit
System settings
Circuit Line Description Recomm.
setting
II 52 Closed valve / normal operation OFF
II 84
Pump P2 in DHW circuit, primary
side
ON
10f
Installation
For easy access, you should mount the ECL Comfort
controller near the system. Select one of the three
following methods:
Mounting on a wall
Mounting on a DIN rail
Mounting in a panel
Screws and rawlplugs are not supplied.
Mounting on a wall
Socket for mounting on wall: Order code No. 087B1149.
Mount the terminal box on a wall with a smooth surface.
Establish the electrical connections and position the
controller in the box. Secure the controller with the fixing
screw.
Mounting on a DIN rail
Mounting kit: Order code No. 087B1145.
A mounting kit is necessary to mount the box with the
controller on a DIN rail.
Mounting in a panel
Connector set: Order code No. 087B1148.
The panel plate thickness must not exceed 3 mm.
Prepare a cut-out with the dimensions 93 x 139 mm. Pull off
the right side of the lid by means of a screwdriver.
Insert the controller into the panel cut-out and fix it with the
two locks which are placed diagonally in two corners of the
controller.
Mounting the ECL Comfort
controller
11a
Installation
11b
Installation
12a
Electrical connections -
230 V a.c. - in general
230 V a.c. connections - without safety thermostat
Optional
P2 / M2*
For the heating systems 2, 4, 5 and 7 it must be determined
whether the actuator is to be controlled by means of the terminals
6 and 7 (M2) or the terminal 11, cf. section 10.
Terminals 6 and 7: Only control valves with 3-point control
Terminal 11: For change-over valves ON / OFF
Establish these jumpers:
1-5-8-10-12-14
and jumper 2 to common N-terminal.
If an ECA 80 module is to be applied, the jumpers 14-26-29
must be established additionally.
230 V a.c. connections - with safety thermostat
Optional
This circuit diagram is only valid if Danfoss actuators are used
Establish these jumpers:
1-10-12-14
Safety thermostat:
4, 5 and 10 with ST- (safety thermostat)
and jumper 2 to common N-terminal.
If an ECA 80 module is to be applied, the jumpers 14-26-29
must be established additionally.
Installation
12b12b
Terminal Description Max. load
1 (L) Supply voltage 230 V a.c.
2 (N) Supply voltage 230 V a.c.
3 M1 Actuator - open, circuit I 0.2 A / 230 V a.c.
4 M1
Actuator - close, circuit I
alt. thermo actuator
0.2 A / 230 V a.c.
5
230 V a.c. supply for motor
output, circuit I
6 M2 Actuator - open, circuit II 0.2 A / 230 V a.c.
7 M2
Actuator - close, circuit II
alt. thermo actuator
0.2 A / 230 V a.c.
8
230 V a.c. supply for motor
output, circuit II
9 P1
Circulation pump for heating
circuit
4 (2) A / 230 V a.c.
10
230 V a.c. supply for pump
relay R1
11 P2
DHW charging pump for DHW
circuit II
4 (2) A / 230 V a.c.
12
230 V a.c. supply for pump
relay R2
13 P3
Circulation pump for DHW
circuit II
4 (2) A / 230 V a.c.
14
230 V a.c. supply for pump
relay R3
Wire cross section: 0.75 - 1.5 mm
2
Electrical connections
Max. 2 x 1.5 mm
2
wires can be inserted into each screw terminal.
Incorrect connection can damage the TRIAC outputs. Max. load
(terminals 3, 4, (6 and 7)) 0.2 A / 230 V a.c.!
Option:
Relay module ECA 80 (contacts: max. load 4 (2) A / 230 V a.c.)
25 (R4) Alarm relay output
28 (R5) Control of the DHW charging pump in heating
systems 4, 5, 6 and 6a.
Installation
13a
Electrical connections -
24 V a.c. - in general
24 V a.c. connections - without safety thermostat
Optional
Establish these jumpers:
1-5-8-10-12-14
and jumper 2 to common N-terminal.
If an ECA 80 module is to be applied, the jumpers 14-26-29
must be established additionally.
24 V a.c. connections - with safety thermostat
Optional
This circuit diagram is only valid if Danfoss actuators are used
Establish these jumpers:
1-10-12-14
Safety thermostat:
4, 5 and 10 with ST- (safety thermostat)
and jumper 2 to common N-terminal.
If an ECA 80 module is to be applied, the jumpers 14-26-29
must be established additionally.
Installation
Terminal Description Max. load
1 (L) Supply voltage 24 V a.c.
2 (N) Supply voltage 24 V a.c.
3 M1 Actuator - open, circuit I 1.0 A / 24 V a.c.
4 M1
Actuator - close, circuit I
alt. thermo actuator
1.0 A / 24 V a.c.
5
24 V a.c. supply for motor
output, circuit I
6 M2 Actuator - open, circuit II 1.0 A / 24 V a.c.
7 M2
Actuator - close, circuit II
alt. thermo actuator
1.0 A / 24 V a.c.
8
24 V a.c. supply for motor
output, circuit II
9 P1
Circulation pump for heating
circuit I
4 (2) A / 24 V a.c.
10
24 V a.c. supply for pump
relay R1
11 P2
DHW charging pump for DHW
circuit II
4 (2) A / 24 V a.c.
12
24 V a.c. supply for pump
relay R2
13 P3
Circulation pump for DHW
circuit II
4 (2) A / 24 V a.c.
14
24 V a.c. supply for pump
relay R3
Wire cross section: 0.75 - 1.5 mm
2
Electrical connections
Max. 2 x 1.5 mm
2
wires can be inserted into each screw terminal.
Incorrect connection can damage the TRIAC outputs. Max. load
(terminals 3, 4, (6 and 7)) 1 A / 24 V a.c.!
Option:
Relay module ECA 80 (contacts: max. load 4 (2) A / 230 V a.c.)
25 (R4) Alarm relay output
28 (R5) Control of the DHW charging pump in heating
systems 4, 5, 6 and 6a.
13b
Installation
Connecting the temperature sensors and the bus
Terminal Description Type (recomm.)
15 and 16 System device bus*,
connections for room
panel** / remote control** /
(relay module)
ECA 60 / 62
ECA 61 / 63
17 and 16 S1 Outdoor temperature
sensor
ESMT
18 and 16 S2 Flow temperature sensor **,
circuit I
ESM-11 / ESMC /
ESMU
19 and 16 S3 Return temperature sensor,
circuit I
ESM-11 / ESMC /
ESMU
20 and 16 S4 Flow temperature sensor,
circuit II
ESM-11 / ESMC /
ESMU
21 and 16 S5 Return temperature sensor,
circuit II or
lower DHW tank
temperature sensor, circuit II
ESM-11 / ESMC /
ESMU
ESMB
22 and 16 S6 Upper DHW tank
temperature sensor***
ESMB / ESMU
* The system device bus / room panel / remote control is only active
when the outdoor temperature sensor is connected.
** Either room temperature sensor or room panel / remote control
*** If only one DHW tank temperature sensor is used, it must be connected
to terminal 22
Establish the jumper from 16 to common terminal.
Wire cross section for sensor connections:
Min. 0.4 mm
2
Total cable length: Max. 125 m (all sensors incl. system device
bus)
Cable lengths of more than 125 m may cause noise sensibility
(EMC).
Connecting and placing the
temperature sensors
14a
Installation
It is important that the sensors are mounted in the correct
position in your system.
The temperature sensor mentioned below are sensors used
for the ECL Comfort 200 and 300 series which not all will be
needed for your application!
Outdoor temperature sensor (ESMT)
The outdoor sensor should be mounted on that side of the
building where it is less likely to be exposed to direct
sunshine. It should not be placed close to doors, windows or
air outlets.
Flow temperature sensor (ESMU, ESM-11 or ESMC)
Place the sensor max. 15 cm from the mixing point. In
systems with heat exchanger, Danfoss recommends that the
ESMU-type to be inserted into the exchanger flow outlet.
Make sure that the surface of the pipe is clean and even
where the sensor is mounted.
Return temperature sensor (ESMU, ESM-11 or ESMC)
The return sensor should always be placed in / on a pipe with
return water flow.
Room temperature sensor (ESM-10, ECA 60 / 62 room
panel or ECA 61 / 63 remote control)
Place the room sensor in the room where the temperature is
to be controlled. Do not place it on outside walls or close to
radiators, windows or doors.
DHW temperature sensor (ESMU or ESMB-12)
Place the DHW temperature sensor according to the
manufacturers specification.
Boiler temperature sensor (ESMU, ESM-11 or ESMC)
Place the sensor according to the boiler manufacturers
specification.
Flow / air duct temperature sensor (ESM-11, ESMB-12,
ESMC or ESMU types)
Place the sensor so that it measures a representative
temperature.
Surface temperature sensor (ESMB-12)
Place the sensor in the surface of the floor.
Valid for ESM-11: Do not move the sensor after it has been
fastened in order to avoid damage to the sensor element.
14b
Installation
14c
Connecting the room panel / remote control
The ECA 60 / 61 / 62 / 63 is activated by the setting in line 10
(section 32).
The ECA 60 / 61 / 62 / 63 is powered by the system device bus
which means that the bus must be active. The bus is activated by
setting the controller address to 15 (section 32, line 199).
Override
For an active override, you have to choose the mode
“scheduled operation”! Input S1 ... S6 (ECL Card C14 only uses
S5) can be used for override purposes (section 32, line 141).
Connection example without ECA 9010
If the override switch has goldplated contacts, you can
choose one of the following solutions or a combination of
both:
(C14 = 21 only) (C14 = 21 only)
Closed switch: Closed switch:
Comfort temperature Setback temperature
Open switch: Open switch:
Scheduled operation Scheduled operation
Connection example with ECA 9010
The ECA 9010 module is powered by the system device bus,
which means that the bus must be active. The bus is activated
by setting the controller address to 15 (line 199). To avoid
influence from contact resistance, the use of ECA 9010 is
recommended.
Comfort Setback
Red
Brown
Green S1 ... S6 (C14 = S5 only)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88

Danfoss ECL Comfort 300 - C47 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI