Retrofit Installation
Field Adjustable Wattage and CCT
Wiring Diagram 1 Wiring Diagram 2
1Kelvin and wattage can be
adjusted using the dip switches
located on the driver.
2Select the desired kelvin and
wattage by sliding the dip switch.
Gnd Green
AC Line
To 0–10V
Dimmer
Black
White
ACL
ACN
Dim +
LED +
Dim -
LED -
LED Driver
Green (Gnd)
White (Neutral)
Purple
(Dim + )
Dimming wire
to 0–10V IEC
compliant control
Lead Wire to
LED Load
Pink
(Dim - ) Blue ( - ) Red ( + )
120–277V
Black (Line)
CCT Switch
Wattage Switch
2Cut apart and install the included
brackets as shown. For the 8ft
fixture, use the larger center bracket to
join the fixture halves.
1Disconnect and remove the
existing ballast cover, ballast,
socket bars, and wiring. 3Make electrical connections as
shown in Wiring Diagrams 1 and 2.
Install the LED retrofit assembly.
Brackets
Safety Cable
4Install optional lens. Restore
power and turn on.
860 SERIES
Strip Retrofit Installation Guide Page 1 of 1
WARNING
1. To avoid electric shock, disconnect power at source prior to installation.
2. The installation should be performed by qualified electricians or lighting technicians.
3. Before conducting any installation, maintenance, or removal, disable all power.
4. Do not touch the fixture while it is in service.
5. If there is any problem with the fixture, turn off power and DO NOT attempt repair unless
you are a qualified technician or the customer service member.