Hardy HI6600 Reference guide

Type
Reference guide
Hardy Process Solutions • 9440 Carroll Park Drive, Ste. 150 • San Diego, CA 92121-5201
Tel 858.278.2900 • Fax 858.278.6700 • www.hardysolutions.com[email protected]
HI6600QuickReference
DetailedManual:
http://www.hardysolutions.com/tenants/hardy/documents/HI6600UserGuide%200717.pdf
OnlineUnit
http://hi6600.hardysolutions.com/index.cgi
DefaultIPAddress:
192.168.0.100
NOTE:Unitshaveaninternalwebpagetouse.
Page2
ErrorMessageDefinitions:
Tips:
‐GrossandNetweightscanbefoundintheinputtableofthePLCcontrollertags.
‐ThesystemmustbepowereddownpriortoaddingorremovinganyWPmodule.
‐ThedefaultIPaddressfortheHardyGatewayModuleis192.168.0.100
‐The“Identify”featureinthebrowserunderGatewayHome>HardyNetishelpfulforchannelverification.
‐The“Discover”featurediscoversmodulesintheorderinwhichtheyrespond.
‐HARDYbeginschannelnumbersat“1”onthewebserver.PLCscommonlybeginat“0”.
‐Hexadecimalcommandsarecommonlyused.“0x”and“16#”areusedtosignifyaHexvalue.
Example:AC2Calibratecommandof“0x66”wouldbeenteredas“16#0000_0066”intheoutputtable.
Page3
SendingCommands:
EXAMPLE:Thesecondchannel(01)receivingatarecommand(0002).
CommandStatus:
Thereturnstatusforcommandssent.Top2BITSincrement.14bitshaveafewstatuses.

Page4
ExampleofaStatusReturnWhenUsinga“Zero”Command:
ThecompletelistofallindividualcommandstatusescanbefoundintheUserManual.
TheDefaultState:
Uponfirststartup,“16#0000_0000”isenteredintotheoutputcommandfieldbydefault.Itisavalid
command.ItistheREADPARAMCMDforthefirstchannel.
OUTPUTTABLE
Thiswillcommandtheunittoreadthe“Parameter_ID”tagfromtheoutputtable.Inthedefaultstatethereis
noparameternumberentered.ParameterIDstoentercanbefoundintheUserManualandanexampleis
downbelow.
OUTPUTTABLE
ThentheHI6600willreturnthatparameter’svaluebackintothe“Parameter_Value”tagintheinputtable.
INPUTTABLE
Iftheparametervalueisafloatingpoint,aCOPinstructionmustbeusedtoconverttheincomingDINTto
floatingpointREALdatatype.
COPYCOMMANDREQUIREDFORDINT>REAL
(RefertothemanualforthecompletelistofparameterIDs.)
ReadParameterExample:
IfaCommandof0000_0000andParameter_IDof0000_2082weresetintheOUTPUTtabletothemodule,
thenthe“Parameter_Value”INPUTtabletagwouldbethenumberofaveragesfromthefirstchannel.
ChangingtheCommandto0100_0000wouldrequestthesameinformationfromthesecondchannelandso
on.

Page5
UsingaUSBtoSave,LoadorRestoreParameters
FromtheHI6600webpage:
USBWEBPAGE
InsertingaUSBandSavingparametersfromthewebpageordisplaycreatesaPARAMS.TXTfilewithinan
HI6600folderontheUSB.
RESTORE(read)theparametersviathewebpageordisplaywillloadandreplacethecurrentlyrunning
parameterswiththePARAMS.TXTparameters.
E.G.HI6600/PARAMS.TXT
PlacingaRESTORE.TXTfileintoafolderlabeledHI6600onaUSBandpopulatingthefilewithparameterswill
replacetherunningparametersuponeverypower‐up.
NOTE:ThefirstparameterlineofaRESTORE.TXTfileisignored.
Example:
ThisexampleisasetoftextthatissavedasaRESTORE.TXTfileintheHI6600folderofaUSB:
00007985FirmwareRevision=HI66002.0.4.0
00003107DHCP=0[OFF]
00003101FixedIP=192.168.0.100
Inthisexample,thefirstlinewouldbeignored,theDHCPwouldbeturnedoffandthefixedIPwouldbesetto
192.168.0.100.