Page4
ExampleofaStatusReturnWhenUsinga“Zero”Command:
ThecompletelistofallindividualcommandstatusescanbefoundintheUserManual.
TheDefaultState:
Uponfirststartup,“16#0000_0000”isenteredintotheoutputcommandfieldbydefault.Itisavalid
command.ItistheREADPARAMCMDforthefirstchannel.
OUTPUTTABLE
Thiswillcommandtheunittoreadthe“Parameter_ID”tagfromtheoutputtable.Inthedefaultstatethereis
noparameternumberentered.ParameterIDstoentercanbefoundintheUserManualandanexampleis
downbelow.
OUTPUTTABLE
ThentheHI6600willreturnthatparameter’svaluebackintothe“Parameter_Value”tagintheinputtable.
INPUTTABLE
Iftheparametervalueisafloatingpoint,aCOPinstructionmustbeusedtoconverttheincomingDINTto
floatingpointREALdatatype.
COPYCOMMANDREQUIREDFORDINT>REAL
(RefertothemanualforthecompletelistofparameterIDs.)
ReadParameterExample:
IfaCommandof0000_0000andParameter_IDof0000_2082weresetintheOUTPUTtabletothemodule,
thenthe“Parameter_Value”INPUTtabletagwouldbethenumberofaveragesfromthefirstchannel.
ChangingtheCommandto0100_0000wouldrequestthesameinformationfromthesecondchannelandso
on.