INSTRUCTION MANUAL
DISCRETE I/O EXTENSION UNIT
MODEL
R9WTU-ED
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
PACKAGE INCLUDES:
Discrete I/O extension unit .................................................(1)
Mounting adaptor ...............................................................(1)
MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
For detailed information of operation and configuration, re-
fer to the Instruction Manual of Multi Power Monitoring
Unit (model: R9xWTU).
POINTS OF CAUTION
POWER CONSUMPTION
AC: < 2VA
DC: < 1.5W
GENERAL PRECAUTIONS
Before you remove or mount the unit, turn off the power
supply and input signal for safety.
ENVIRONMENT
Indoor use.
Do not install the unit where it is directly exposed to rain,
water droplets or sunlight.
When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to90% RH
in order to ensure adequate life span and operation.
WIRING
Wiring to the unit must be conducted by qualified service
personnel.
Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
AND ....
The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
R9WTU-ED
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-6225 Rev.1 P. 2 / 4
COMPONENT IDENTIFICATION
Terminal Block, Discrete Outputs
Output Status Indicator LED
Input Status Indicator LED
Terminal Block, Discrete inputs
COM
COM
DI1
DI2
21
1110
COM
COM
DI3
DI4
43
1312
COM
COM
DI5
DI6
65
1514
COM
COM
DI7
DI8
87
1716
NC
NC
9
18
NC
DO8
+
NC
DO8
-
89
1718
DO7
+
DO6
+
DO7
-
DO6
-
67
1516
DO5
+
DO4
+
DO5
-
DO4
-
45
1314
DO3
+
DO2
+
DO3
-
DO2
-
23
1112
DO1
+
DO1
-
1
10
I/O STATUS INDICATOR LED
Discrete I/O extension units have LED indi-
cators showing I/O signal status.
Contact ON : LED ON
Contact OFF : LED OFF
TERMINAL ASSIGNMENTS
14
56
DI5
COM COM
15
DI6
16 17 18
789
DI7 DI8 NC
COM COM
10
12
DI1
COM COM
11
DI2
12 13
34
DI3 DI4
COM COM NC
ID
ID
1 COM Input comon 10 DI1 Input 1ch
2 COM Input comon 11 DI2 Input 2ch
3 COM Input comon 12 DI3 Input 3ch
4 COM Input comon 13 DI4 Input 4ch
5 COM Input comon 14 DI5 Input 5ch
6 COM Input comon 15 DI6 Input 6ch
7 COM Input comon 16 DI7 Input 7ch
8 COM Input comon 17 DI8 Input 8ch
9 NC Unused 18 NC Unused
DISCRETE INPUT
5
14 13
DO5–
DO5+ DO4+
4
DO4–
321
12 11 10
DO3– DO2– DO1–
DO3+ DO2+
9
18 17
NC
NC
DO8+
8
DO8–
76
16 15
DO7– DO6–
DO7+ DO6+ DO1+
ID
ID
1 DO1– Output 1ch– 10 DO1+ Output 1ch+
2 DO2– Output 2ch– 11 DO2+ Output 2ch+
3 DO3– Output 3ch– 12 DO3+ Output 3ch+
4 DO4– Output 4ch– 13 DO4+ Output 4ch+
5 DO5– Output 5ch– 14 DO5+ Output 5ch+
6 DO6– Output 6ch– 15 DO6+ Output 6ch+
7 DO7– Output 7ch– 16 DO7+ Output 7ch+
8 DO8– Output 8ch– 17 DO8+ Output 8ch+
9 NC Unused 18 NC Unused
DISCRETE OUTPUT
No.
FUNCTION FUNCTION FUNCTION FUNCTION
No. No. No.
INSTALLATION
WALL MOUNTING
Insert the provided mounting adaptors into upper side of
the unit, and pull out those on the lower side. Fasten the
M4 screw to the hole (4.5 mm dia.) of each adaptor. (torque
1.4 N∙m)
To remove the adaptor, pull it out while squeezing the latch-
es as shown in the figure below.
push push
DIN RAIL MOUNTING
Set the unit so that its mounting adaptors are at the bot-
tom. Position the upper hook at the rear side of the unit
on the DIN rail and push in the lower. When removing the
unit, push down the adaptors utilizing a minus screwdriver
and pull.
DIN Rail (35 mm wide)
Mounting Adaptor
R9WTU-ED
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-6225 Rev.1 P. 3 / 4
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
EXTERNAL DIMENSIONS unit: mm (inch)
93 (3.66)
6 (.24)
36−M3 SCREW TERMINAL
126 (4.96)
122 (DIN RAIL MOUNT)
115 (4.53)
140 (5.51)
DIN RAIL
35 mm wide
2 − 4.5 (.18) dia. MTG HOLE
[4 (.16)]
6.5 (.25)
80 (3.15)7 (.28)
CONNECTION DIAGRAM
1
5
10
2
6
4
7
13
8
14
12
15
11
16
17
COM
COM
COM
COM
COM
COM
DI2
DI1
DI3
DI4
DI5
DI6
DI7
DI8
Control
Circuit
INPUT
Excitation Supply
COM
3
1
5
10
2
6
4
7
13
8
14
12
15
11
16
17
3
COM
DO6+
DO6–
DO7+
DO7–
DO8+
DO8–
DO1–
DO1+
DO2+
DO2–
DO3+
DO3–
DO4+
DO4–
DO5–
DO5+
1
10
8
17
COM
DI1
DI8
COM
+
DISCRETE
INPUT
DISCRETE
OUTPUT
Control
Circuit
OUTPUT
10
1
DO1+
DO1–
17
8
DO8+
DO8–
EXTENSION CONNECTOR
1
10
1
10
Coil, etc.
Inductive loads
Varistor/CR Circuit
Refer to the figure below for Photo MOS Relay discrete protection and noise removal.
AC
Load
DC
Coil, etc.
Inductive loads
Varistor/CR Circuit
Load
U
R9WTU-ED
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-6225 Rev.1 P. 4 / 4
CONNECTING THE EXTENSION UNIT
1) Remove the cap.
2) Slide the two locks of the multi power monitoring unit to
the back position.
3) Connect the extension unit to the multi power monitor-
ing Unit.
4) Restore the two locks of the multi power monitoring unit
to the front position.
5) Mount the combined unit on a DIN rail.
Note: When you remove or mount the unit, turn off the power
supply and input signal for safety.
Lock
Cap
WIRING INSTRUCTIONS
SCREW TERMINAL
Torque: 0.5 N·m
SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd, Nichifu Co., Ltd
6 (.24) max
3.3 (.13) max
mm (inch)