M-system MD7G is a terminal block for grounding that can be used to connect shield wires and cross wires of protected devices to a DIN rail. It is designed for indoor use and can withstand temperatures from -25 to 85°C (-13 to 185°F) and relative humidity from 30 to 90%. It has 8 M3 Euro terminals and can accommodate wires with a cross-sectional area of 0.2 to 2.5 mm2. The stripped length of the wires should be 8 mm. The unit is easy to install and remove from a DIN rail, and it comes with a DIN rail mounting adaptor for grounding.

M-system MD7G is a terminal block for grounding that can be used to connect shield wires and cross wires of protected devices to a DIN rail. It is designed for indoor use and can withstand temperatures from -25 to 85°C (-13 to 185°F) and relative humidity from 30 to 90%. It has 8 M3 Euro terminals and can accommodate wires with a cross-sectional area of 0.2 to 2.5 mm2. The stripped length of the wires should be 8 mm. The unit is easy to install and remove from a DIN rail, and it comes with a DIN rail mounting adaptor for grounding.

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8065 Rev.2 P. 1 / 2
INSTRUCTION MANUAL
TERMINAL BLOCK FOR GROUNDING
(ultra-slim)
MODEL
MD7G
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
PACKAGE INCLUDES:
Terminal block .....................................................................(1)
MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation and connection.
POINTS OF CAUTION
ENVIRONMENT
•Indoor use.
•When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
•Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
•Environmental temperature must be within -25 to +85°C
(-13 to +185°F) with relative humidity within 30 to 90%
RH in order to ensure adequate life span and operation.
•This unit needs a DIN rail as earth grounding bar. Ox-
ide coating of an aluminium rail may lower the electric
conductivity between this module and the ground. Use a
steel or copper rail.
COMPONENT IDENTIFICATION
Body
Spring Loader
DIN Rail Mounting
Adaptor (for grounding)
Connection
Diagram
(left side)
Model No.
Indication
INSTALLATION
Mount the unit on a DIN rail. Once installed, do not move
it to another DIN rail.
MOUNTING THE UNIT ON A DIN RAIL
A) Hang the upper hook of the DIN rail mounting adaptor at
the rear side of unit, on the DIN rail.
B) Push in the lower in keeping pressing the unit to the DIN
rail.
C) DIN rails generally have slight individual variability in
size. If you find it difficult to push in the lower part, go
back to (A) and hang the upper part more deeply onto the
rail and try (B) again.
A
DIN Rail
B
REMOVING THE UNIT
A) Push down the spring loader utilizing a minus screwdriv-
er.
B) Confirm that it is pulled enough down and pull out the
lower part of the unit.
C) Detach the upper part from the DIN rail.
A
B
Spring Loader
C
MD7G
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8065 Rev.2 P. 2 / 2
TERMINAL CONNECTION
Connect the unit as in the diagram below.
Be sure to ground the DIN rail on which the unit is mounted.
This unit, designed to connect shield wires and cross wires of the protected devices to a DIN rail, is NOT used to ground the
DIN rail.
EXTERNAL DIMENSIONS unit: mm (inch)
8
6
5
4
1
2
3
7
4
1
5
2
6
3
8
7
95 (3.74)
7
(.28)
98 (3.86)
[1.5 (.06)]
8–M3 EURO
TERMINAL
DIN RAIL
(35 mm wide)
DIN RAIL
ADAPTOR
WIRE INSERTION ANGLE: approx. 20°
57 (2.24)
1.9 (.07)
CONNECTION DIAGRAM
2 5
3 6
8
7
1 4
DIN RAIL ADAPTOR
(for grounding)
DIN RAIL
Grounding
DO NOT connect to unused terminals.
*1. Oxide coating of an aluminium rail may lower the electric conductivity
between this module and the ground. Use a steel or copper rail.
*2. Be sure to ground the DIN rail.
Recommended grounding resistance ≤100Ω
*2
*1
WIRING INSTRUCTIONS
EURO TERMINAL
Torque: 0.3 N·m
Applicable wire size: 0.2 – 2.5 mm
2
Stripped length: 8 mm
CAUTION WHEN WIRING
Hold the module steady at the front when you
tighten/loosen screw terminals.
  • Page 1 1
  • Page 2 2

M-system MD7G User manual

Type
User manual

M-system MD7G is a terminal block for grounding that can be used to connect shield wires and cross wires of protected devices to a DIN rail. It is designed for indoor use and can withstand temperatures from -25 to 85°C (-13 to 185°F) and relative humidity from 30 to 90%. It has 8 M3 Euro terminals and can accommodate wires with a cross-sectional area of 0.2 to 2.5 mm2. The stripped length of the wires should be 8 mm. The unit is easy to install and remove from a DIN rail, and it comes with a DIN rail mounting adaptor for grounding.