Signet Pulse 2.200 LS Operation & Instruction Manual

Category
Video switches
Type
Operation & Instruction Manual

Signet Pulse 2.200 LS is a dual 200W 100V line amplifier with monitoring capabilities, suitable for professional audio applications. It features independent amplifier modules with Main and Aux inputs, allowing for mixing and monitoring. Comprehensive fault monitoring ensures system reliability, detecting issues like load impedance deviations, tone fail, and earth faults. The amplifier provides status indicators on the front panel for each module and the power supply, making it easy to identify and troubleshoot any problems.

Signet Pulse 2.200 LS is a dual 200W 100V line amplifier with monitoring capabilities, suitable for professional audio applications. It features independent amplifier modules with Main and Aux inputs, allowing for mixing and monitoring. Comprehensive fault monitoring ensures system reliability, detecting issues like load impedance deviations, tone fail, and earth faults. The amplifier provides status indicators on the front panel for each module and the power supply, making it easy to identify and troubleshoot any problems.

Page 1 of 12 DocNo.DCP0001326 DSM 06/01/05 rev7
Features
The P2.200 LS amplifier contains two identical independent amplifier modules. Each has one Main and one
Aux. input. Routing logic allows the Main and Aux. to mix; this allows the monitoring tone to pass at all times
and the monitoring system to operate. If the PTT is operated, the Main input overrides the Aux.
Each modules status is displayed on the front panel along with an output level bar graph and status
indicators. All sections of the amplifier and charger are constantly monitored for faults or abnormal operation:
1 The load monitoring checks the power absorbed by the loudspeaker load at 22 kHz and compares this
with the threshold and window levels set at installation. If the power drawn deviates outside the window a
fault is indicated on the front and rear of the unit and signalled to other equipment via the relevant fault
outputs.
2 If the impedance monitoring tone is not being received by the amplifier, both the Load Hi and Load Low
front LEDs light and the rear Tone Fail light shows.
3 Should either leg of the loudspeaker wiring short to system earth this will also light the Load Hi and Load
Low LEDs on the front panel, along with the Earth Fault LED on the rear.
4 Mains power status is also monitored, along with the internal fuses, to give a complete picture of the state
of the amplifier.
The load monitoring system also provides an output to drive a hot swap automatic amplifier replacement
system, via the HSP port, on failure of the amplifier only. Should a load fail short or open circuit but the
amplifier is still OK, the hot swap output will not operate. This means that any loudspeakers that can be
driven will operate and leaves the hot swap amplifier available for use on another potential failure.
The output from each module is presented on a three-way socket and is fully floating. The standard output
voltages are 50V and 100V, allowing two modules to be connected in series to give 400W at 100V line.
The power supply has a 24 Vd.c. battery input and an onboard battery charger.
Technical Description
Amplifier Modules
The Aux. and Main line level inputs are de-balanced and pass via level controllers and an analogue switch
into a summing amplifier where they are mixed. If the contact input is asserted (470 ohms to ground) a logic
circuit disconnects the aux. input.
The protect circuit disconnects the output transformer when the voltage rails fall below 22 Volts, exceed 36
Volts, or when a d.c. offset is present on the output rails. The signal then passes through to the output stage,
which is a feed-forward current-mode bridge circuit and the output level meter monitors the level at this stage.
The output current is passed through the primary of the output transformer and through a low value output-
sensing resistor. The output of the transformer is tapped at 50 and 100 Volts. If the 50 Volt taps are
connected in series the unit provides a single 400 Watt output at 100 V line.
Power Supply
A large capacitor reservoir provides a very smooth output, even under large current surges. Two separate
internal 10 Amp fused outputs connect to the two amplifier modules.
A separate low-current feed passes via the sleep enable selector link into the sleep timer section. Another
feed passes, via the Aux. on LED (this shows that the Aux. power is available on the rear connector) through
a 3 Amp fuse to the Aux. power connector. With mains voltage operation this unregulated output is at
approximately 32 Vd.c. When mains has failed, this output is connected to the battery and therefore operates
at battery voltage level.
A 27.6 Volt regulator is also taken off this line and used to charge external batteries via a 20 Amp fuse.
PSU and amplifier faults are returned into the monitoring circuit from both amplifiers, slugged to prevent false
faults being reported externally, and passed to the open collector fault outputs on the SIP port. A fourth open
collector output is normally set as OK (normally closed) and opens when any fault occurs.
Operation Instruction Manual
Pulse 2.200 LS Dual 200W 100V line Amplifier with Monitoring
Page 2 of 12 DocNo.DCP0001326 DSM 06/01/05 rev7
Block Diagrams Front panel indicators
DISPLAY
PSU/
CHARGER
P2.200LS OVERALL
BLOCK DIAGRAM
ISSUE 1.
AMP
MODULE A
AMP
MODULE B
AMP
MODULE A
AMP
MODULE B
230VAC
50/60Hz
~
AUX 27.6V
OUT
24V SEALED
LEAD-ACID BATTERY
FAULTS
SHOWS THE OVERALL CONFIGURATION OF PSU AND AMP MODULES PLUS DISPLAY
SIP
PORT
HOT SWAP PORT B
HOT SWAP PORT A
P2.200LS PSU MODULE BLOCK DIAGRAM
ISSUE 1.
5AMP
HBC
35A
BATTERY
20A
20A
27.6 V
REGULATOR
3A
AC IN
44000µF 3A
AMP
MODULE A
AMP
MODULE B
AMP
MODULE A
AMP
MODULE B
16 SECONDS ON
15 MINUTES OFF
SLEEP
ENABLE
AUX
ON
230VAC
50/60Hz
~
AUX 27.6V
OUT
MONITOR
GROUND
OKPSU
FAULT
DISABLE
DC IN
20A
3A
10A
10A
ALL FUSES AUTOMOTIVE BLADE
TYPE, EXCEPT MAINS INLET
FUSE
AMP A FAULT
AMP B FAULT
OK, SIP4PSU FAULT, SIP3
AMP B FAULT, SIP2
AMP A FAULT, SIP1
SLEEP
LINE
IN
(AUX)
0dB
LEVEL
P2.200LS AMPLIFIER MODULE BLOCK DIAGRAM.
TWO PER P2.200LS ISSUE 1
LINE
IN
(MAIN)
0dB
LEVEL
MONITOR
ANALOGUE
SWITCH
ANALOGUE
SWITCH
CONTROL
50 V
100V
0V
CONTACT
(PTT IN)
OPEN
CIRCUIT
FAULT
SHORT
CIRCUIT
FAULT
DETECT
FAULT
HSP2
LOAD
HIGH
FAULT
HSP1
LOAD
LOW
FAULT
HSP4
DETECT
Vp
FAULT
HSP3
WINDOW
THRESHOLD
TONE
FAIL
DETECTS CURRENT
THROUGH RESISTOR
EARTH
FAIL
PROTECT
SLEEP IN
-18 -6 -3 0
OUTPUT LEVEL
LOGIC
15V
REG
Vp out
+24 Vin
GROUND
+24V IN
OUTPUT
4TH ORDER BANDPASS
FILTER @ 22.05KHz
RLA1
RLA
1
OK HSP6
HSP5
IF LOAD LOW & TONE FAIL OR PROTECT THEN OK
HSP = HOT SWAP PORT.
CAN AVOID HOT SWAP IF NATURE OF
FAULT MEANS THERE IS NO POINT
AMP FAULT TO PSU
(OPEN CIRCUIT OR
SHORT CIRCUIT OR
LOAD HIGH OR LOAD
LOW OR TONE FAIL OR
EARTH FAULT)
Page 3 of 12 DocNo.DCP0001326 DSM 06/01/05 rev7
Each amplifiers current status is displayed on the front panel, along with output bar graphs for each channel,
and the access status. All indicators are in accordance with BS 5839: Part 4: 1988.
Each amplifier module has a separate indication on the front panel for the following states:
Name Function / Description
1
Output level A four-element moving dot display shows the current amplifier output
level in logarithmic steps with 0dB being full power.
2
Priority The control contact on the main input is closed.
3
Protect The onboard protection systems have been activated and the load is
now isolated.
4
Sleep This facility is not used as it does not comply with BS5839-8
5
Load Hi The load monitoring system has detected an open circuit or higher
impedance than was set at commissioning.
6
Load Low The load monitoring system has detected a closed circuit or lower
impedance than was set at commissioning.
7
Contact Fault The main input control contact or wiring is either open circuit or short
circuit.
8
Tone fail
(Load Hi and Load Low lit)
The amplifier cannot detect the 22 kHz monitoring tone.
The power supply unit also has front panel status indication for the following states:
Name Function / Description
1
AC in The AC mains supply is healthy.
2
DC in The reserve battery supply is in use.
3
PSU Fault The battery charger has detected either a short circuit or high
impedance battery.
4
Aux. on The auxiliary power supply for external equipment is available.
5
OK All the functions of the amplifier are normal.
Page 4 of 12 DocNo.DCP0001326 DSM 06/01/05 rev7
Name Function/Description
Name Function/Description
1
Switch Switches mains power
2
AC Input 6A IEC 3 pin connector
(Fuse: 5A 250V 20mm HBC)
3
Battery
Input
Rear of CliffCon 4
PC/P
Pin 1- : GND
Pin 1+ : +24V DC
@ 20A
8
Hot Swap
Port
4
Aux.
Power
9
Output See Output Connections
5
SIP Port See Internal Adjustments (page 9)
10
Level
control
Audio level control of
closest input.
6
Aux.
audio
input
11
LEDs
OC, The main input control wiring
is open circuit.
SC The main input control wiring is
short circuit.
E, Earth fault The 100V
loudspeaker line has a short to
ground.
Hi, Load High. Open circuit
detected, or a impedance higher
than commissioned.
TF, Tone Fail The monitor tone on
the input signal is not detected.
Lo, Load Low. Closed circuit
detected or lower impedance than
commissioned.
12
Window
13
Threshold
7
Main
audio
input
Switch: 470R to GND = on
6k8 to GND = off
See mix mute settings on page 9
14
Level
Used to set-up the fault
monitoring circuitry (see
page 6)
Rear panel controls & features
13
14
Page 5 of 12 DocNo.DCP0001326 DSM 05/01/05 rev7
Installation
Unpacking
On receipt of the amplifier shipment, please inspect for any damage incurred in transit. If damage is found,
please notify your supplier and the transport company immediately. State date, nature of damage and
whether any damage was present on the shipping container prior to unpacking. Please give the waybill
number of the shipping order.
This equipment is only suitable for installation in a well ventilated 19 inch equipment rack. Bottom and top
ventilation holes must not be blocked and air must be allowed to circulate freely through the internal
heatsinks.
If several P2.200LSs are installed in one rack, at least one U of rack space must be left between each
amplifier.
The unit should not be placed in areas;
1 with poor ventilation
2 exposed to direct sunlight
3 with high ambient temperature or adjacent to heat generating equipment
4 with high humidity or dust levels
5 susceptible to vibration
Caution To prevent electric shock do not remove the cover
AC power operation
Due to the size and inductance of the power transformer, depending on where in the cycle the power is
switched on, the inrush current that is drawn when this device is connected can be as much as 150 Amps!
It is therefore essential that mains power is only derived from an automatic soft start device such as SigNETs
SOFT4.
Connect the a.c. power cord to any one of the four IEC amplifier power outlets as described in the SOFT4
manual.
The unit complies with BS415.
AC power cord
The wires in the mains lead supplied with the unit are coloured in accordance with the following code.
Green and Yellow
Earth
Blue Neutral
Brown Live
As the colours of the wires in the mains lead of this unit may not correspond with the coloured markings
identifying the terminals in your plug, please connect as follows.
Wire
Plug terminal
Green and Yellow ‘E’ mark
‘EARTH symbol mark
GREEN mark
GREEN AND YELLOW mark
Blue N mark
‘BLACK’ mark
‘BLUE’ mark
Brown L mark
RED mark
‘BROWN mark
Caution To prevent electric shock do not remove the cover
Page 6 of 12 DocNo.DCP0001326 DSM 05/01/05 rev7
The P2.200LS is designed to operate with two 12 Volt VRLA batteries connected in series.
BS5839-8 1988 requires that batteries must be capable of operating the system according to the project
requirements (normally 24 Hours in a quiescent current state plus 30 minutes in full alarm). It also requires
that batteries be sized so as to provide 25% overcapacity to allow for loss of capacity over time.
It is also necessary to allow for the current drawn by any ancillary equipment connected to the Auxiliary power
output. Auxiliary devices should be connected to different P2.200LS amplifiers in order to spread the load as
evenly as is practical.
Quiescent Battery capacity
The current drawn in the quiescent state is 75 mA per amplifier module, 150 mA total.
The current drawn in the quiescent state with all fault indicators lit is 150 mA per module, 300 mA total.
Therefore, for worst case, the power drawn over 24 Hours is 7.2 AHr.
Alarm Condition Battery Capacity
It is difficult to predict the exact current drawn in alarm condition so the following approximation is used.
Emergency messages consist of a tone, silence, message and silence.
The average power content of speech is approximately 5%.
The average power content of a tone is approximately 20%
The average power content of silence is nil.
A conservative estimate of current draw is therefore 10% of the peak.
The peak current drawn from each amplifier channel is 11 Amps, 22 Amps total.
10% of the peak value is therefore 2.2 Amps or, for 30 minutes, 1.1 AHr.
However, batteries must be de-rated by 50% at high discharge rates and so a figure of 2.2 AHr is taken
If 60 minutes in alarm is required, 4.4 AHr will be required.
Total Battery Capacity
Add alarm state battery capacity to the quiescent capacity and the capacity required is 9.4 AHr
Add 1/3 to allow for a 25% loss of capacity over time and the smallest battery that can be used is 12.5 AHr.
The smallest standard battery above this size is 18 AHr and 27 AHr gives even more spare capacity.
Additional battery capacity for ancillary equipment
Add the capacity required for any ancillary equipment, plus one third for battery aging. These figures do not
change in an alarm condition.
Worst case quiescent current drawn at 24V d.c.
SS2N = 75 mA = 1.84 AHr + 1/3 = 2.44 AHr
Psiren = 50 mA = 1.23 AHr + 1/3 = 1.63 AHr
FCB = 50 mA = 1.23 AHr + 1/3 = 1.63AHr
Integrity Mainframe = 300 mA = 7.35 AHr + 1/3 = 9.78 AHr
MP2 = 50 mA = 1.23 AHr + 1/3 = 1.60 AHr
MPP panel (any) = 150 mA (all LEDs lit) = 3.68 AHr + 1/3 = 4.89 AHr
Batteries must be connected via a suitable fuse. We recommend DIN mounted cartridge fuse holders ref
RS371-0340 and 20A RS230-3496 cartridge fuses.
Correct Power-up Sequence
Plug in mains connector
Make sure external battery fuse is out of circuit
Connect battery connector to amplifier
Switch on mains
Connect battery fuse
Power-related fault indicators should extinguish
If the batteries are connected before the mains supply is turned on the inrush current will weaken the internal
battery fuse.
DC power operation and Battery Calculation
Page 7 of 12 DocNo.DCP0001326 DSM 05/01/05 rev7
PTT monitoring
The contact input (PTT in) is monitored by a resistive potential divider as shown below;
6K8
470R
1K
27V6DC
0V
PTT Input
The terminal voltage here defines
the status of the PTT line:-
Open circuit fault
OK
Trigger
Short circuit fault
PTT Switch
The current drawn by the 6K8Ω resistor (in the
previously connected unit) proves that the PTT
line is intact. Open and short circuit faults are
separately detected and operation of the PTT is
detected by the change in voltage level at the
PTT input when the 470Ω is switched in.
Amplifier and Loudspeaker Circuit Monitoring
To monitor the amplifier and loudspeaker system, the voltage across the output sensing resistor is measured
and taken through a fourth order bandpass filter @ 22.05 kHz to a comparator which detects the power being
drawn at the monitoring tone frequency. The tone is injected into the amplifiers input from the previous
device in the chain (matrix).
The output from the comparator passes into a detector circuit, which compares its value with the threshold
set at installation. It also detects the absence of the tone and reports this to the tone fail output. The output
from the detector passes to a comparator, which drives the load high output. A window control between that
comparator and a second device connected to the load low output is used to adjust how much the impedance
can vary before a fault is flagged.
Loudspeaker Circuits
An end of line detection unit is supplied for each circuit (two per dual amplifier module). These must be fitted
at the end of each loudspeaker line so that the line can be monitored in accordance with BS5839 part 8,
which requires that loudspeaker line continuity be monitored, not the loudspeakers themselves.
Loudspeaker Spurs
Note that this implies that spurs are not allowed. If a loudspeaker output is to be split to drive two circuits this
is only possible using the SPLIT100 Line Splitter, which protects either circuit against a short circuit in the
other circuit. The SPLIT100 is provided with one EOL device so that one EOL can be used at the end of each
circuit. If the circuit is split more than once, it is not possible to detect circuit faults reliably and so this is not
allowed.
A detector circuit connected to the 50 Volt output transformer tap monitors the current flowing and any
imbalance must be due to a short to system earth so an earth fault is detected.
The load high, load low, earth fault and tone fail outputs are brought out separately (un-slugged) on the HSP
port.
Fault ports
There are three fault output ports; the SIP port, and two Hot Swap ports.
The SIP port is slugged to prevent false faults being passed on to the system and provides four open
collector outputs; Amp A fail, Amp B fail, and PSU fail (normally open) plus OK (normally closed). These
normally connect to pins 1 to 4 of the SIP port via an internal dual in-line header with four shorting links fitted.
This header can be reversed to bring the faults out on pins 5 to 8 instead. This allows faults from two dual
amps to be fed down a piece of flat ribbon cable to an SS2N.
The Hot Swap ports are not slugged so need to be gated with the SIP port to prevent false faults. They are
provided to allow detailed amplifier fault information thus; Earth Fault, Tone In Fail, Load Low, Load High,
plus an open collector output that only conducts if the fault is not Load Low or Tone Fail to prevent
unnecessary amplifier swapping.
A common fault output is also provided which is triggered by any or all of the six fault conditions already
described.
Fault Monitoring
Page 8 of 12 DocNo.DCP0001326 DSM 05/01/05 rev7
Input connections
Connecting the P2.200 to a SigNET iX LS
(prioritised mixer) including battery backup.
Important Note: When replacing P2.200
amplifiers on site it must be ensured that the
iX LS model uses a 22Khz monitoring tone.
This will be shown by a sticker on the unit.
iX LS units without a sticker must be
replaced with 22Khz units. (Older iX LS units
use a 20 Khz monitoring tone).
End of line units (supplied with the amplifier)
must also be fitted.
Connecting the P2.200 to a SigNET SS2n (Network station), including battery backup.
1. SS2n feeding both amplifier modules
2. SS2n feeding only one amplifier module
Connecting the P2.200 to an Integrity Mainframe.
Page 9 of 12 DocNo.DCP0001326 DSM 05/01/05 rev7
The amplifier may be used in conjunction with 100
Volt constant voltage loudspeaker systems. This
technique is ideal in public address applications
where it is necessary to operate loudspeakers
over a distance from the amplifier as it prevents
excessive line losses. Line matching transformers
must be installed at each loudspeaker to match them to the amplifier. Low ohm speakers will sound distorted.
This is similar in principle to mains electricity distribution where power is transformed to high voltages and
sent long distances over small conductors before being transformed down again at its destination(s).
These constant voltage outputs are most convenient for distribution of power when a number of speakers are
installed. Each loudspeaker must have a 100 Volt line transformer with a tap that gives the power desired for
that loudspeaker. The total number of power settings for all speakers should be equal to the amplifier power
rating or less. See the following diagrams.
100 Volt connection (200 Watt) 100 Volt connection (400 Watt)
Operation and Set-up
Once an amplifier is installed and powered up, it is necessary to adjust or verify the following
settings:
1. Ensure that an audio lead from a SigNET routing matrix is connected to both Main Inputs a.
2. Check that the monitoring tone is not disabled (the tone fail (TF) indicator is not lit).
3. No audio should be routed into the Main input except for the 22 kHz monitoring tone
4. Using an oscilloscope (e.g. Maplin Part No.IN02158) or true r.m.s voltmeter (RS218-0265) capable of
reading up to 25 kHz, connect to each 100V line output across 0V + 100V. Adjust the main level control
to give a reading of 6 Volts Peak to peak (2.12 Volts r.m.s)
NB Default factory setting is 0V (off), other than on full System deliveries.
5. Once set, this level control must not be adjusted again – all level adjustments must be carried out
by altering the levels from the source equipment (matrix).
Set-up the load monitoring circuit is as follows;
6. Turn the Threshold and Windows controls to minimum (anticlockwise). Ensure load and End of line
(EOL) unit are connected. If loudspeaker splitters are used there must be an end of line unit on each
spur. If more than two end of line units are fitted, the monitoring system will not operate reliably.
7. Turn up the threshold control clockwise until the Load Hi and Load low LEDs are just toggling.
8. Open window control fully (clockwise).
9. Remove the EOL unit. Load Hi should come, and remain on.
10. Refit EOL, Load Hi LED should extinguish.
Note Loudspeaker runs of more than 400m are not recommended, as faults cannot be reliably
detected.
Output connections
Output socket
Page 10 of 12 DocNo.DCP0001326 DSM 05/01/05 rev7
These adjustments should only be carried out by qualified personnel. The power lead and battery
supply must be disconnected before the top cover is removed.
The following adjustments involve removal of the top cover of the unit, remove the side and top screws then
lift lid off.
Mix / Mute (one per amp module)
Mix (Default) Used in life safety applications to allow the high frequency monitoring tone to pass. When
the Main input is not in use, the Main and Aux. inputs are mixed together (this gives the
monitor tone a path through the amp preventing monitor tone faults).
Mute Switch open (pin1 of main input) Main input is muted. Aux. input is accessed
Switch closed (pin1 of main input) Main input is accessed. Aux. input is muted
PSU Monitor
Enabled (default) Battery monitoring enabled.
Disabled Battery monitoring disabled, this removes the battery fault from the front panel if batteries
are not fitted.
Sleep Mode
Disabled (default) This facility is not used as it does not comply with BS5839-8
All other jumpers on the unit are all for SigNET’s internal use / test purposes only.
SIP port
These four fault outputs pass via a 16-pin dual in line socket containing a rewireable header to the top eight
pins of the SIP connector.
By default these are connected via wire links to pins 1 to 4 this used by SigNET to designate a node A
amplifier. With the header-reversed pins 5 to 8 are connected. This configuration is used by SigNET to
designate a node B amplifier.
The header can be rewired to allow any combination of the eight pins for custom wiring.
Node A amplifier
(default) (diagram
shows male
connector on back of
amplifier)
Node B amplifier
(with header
reversed) (diagram
shows male
connector on back of
amplifier)
Internal Adjustments
Page 11 of 12 DocNo.DCP0001326 DSM 05/01/05 rev7
Specification
Amplifier Performance Specification
Sensitivity
Impedance
CMRR
Switch input
Output power
Frequency Response
THD
SINAD
Regulation
Output voltage
Operational mode
Protection
Standby current
Full load current
0dB for both Main and Aux. Inputs
10K balanced (Main and Aux.)
better than 60dB
470 to GND = on
6k8 to GND = off
200W Continuous average power
30Hz to 20kHz -3dB +0dB
better than 0.1% , 1kHz
better than -80dB
better than 2dB
100V line
Current mode, feed forward system
Over voltage, under voltage, d.c. offset, short circuit,
thermal and safe operating area
75mA (150mA with fault lights lit and full load monitoring)
11A
Physical
Material
Colour
Width
Height
Depth
Weight
18swg Zintec sheet steel
Black (RAL 9500 semi-gloss)
430mm
88mm
315mm (behind front panel)
17kg
Power supply & charger
AC input
DC input
Charging voltage
Charging current
Monitoring
Aux. Supply
SIP Port
230 VAC +/- 20%
22 to 34 V DC
27.6 V DC
3A
Short circuit and battery high impedance
1A
User assignable faults for the SigNET network
Monitoring
Detection frequency
Detection type
Window
Sensitivity
End of Line units, one
required per channel.
22.05kHz
Window comparator system
5% to 20% user adjustable
-40dB to -10dB, user adjustable
0.047μF in series with 100Ώ RS365-7227
Fuses
Mains Inlet
Internal Automotive Blade
Amp feeds
Battery
Charger
Aux.
5A 250V 20mm HBC
10A x 2
20A x 1
3A x 1
3A x 1
Page 12 of 12 DocNo.DCP0001326 DSM 05/01/05 rev7
PSU pcb showing internal fuse locations
Fuses are commonly available automotive
blade types
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
SigNET (AC) Limited
6 Tower Road
Glover Estate,
Washington,
Tyne & Wear, NE37 2SH
Tel: +44 (0)191 417 4551
Fax: +44 (0)191 417 0634
info@signet-ac.com
www.signet-ac.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Signet Pulse 2.200 LS Operation & Instruction Manual

Category
Video switches
Type
Operation & Instruction Manual

Signet Pulse 2.200 LS is a dual 200W 100V line amplifier with monitoring capabilities, suitable for professional audio applications. It features independent amplifier modules with Main and Aux inputs, allowing for mixing and monitoring. Comprehensive fault monitoring ensures system reliability, detecting issues like load impedance deviations, tone fail, and earth faults. The amplifier provides status indicators on the front panel for each module and the power supply, making it easy to identify and troubleshoot any problems.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI