SPECIFICATIONS
Voltage .................................................................................. 24VDC
Maximum wire length to controller ................................ 150’ (45.72m)
Maximum switches per controller ......................................................4
Environment ............................................................ 32-139ºF (0-60ºC)
5-95% relative humidity non-condensing
DESCRIPTION
The LS-3C is a low voltage wall switch used with a LightSaver
LCO-203 daylighting controller. It allows occupants to temporaily
override automatic ON/OFF daylighting control provided by the
multizone controller.
OPERATION
The LS-3C has two operating buttons (Automatic and On/Off). An LED
indicates whether the controller is operating the lights automatically or
is being manually overridden. Pressing the On/Off button temporarily
puts the controller into manual mode and switches the lights ON
or OFF. Pressing the Auto button switches the controller back into
automatic operation.
When the controller is connected to an occupancy sensor, the manual
override terminates when occupancy ends. When occupancy resumes,
the controller reverts to automatic control.
INSTALLATION
The switch is made up of two primary parts: the
cover plate and the back containing the buttons,
electrical components, wire terminals and mounting
strap. It mounts to a standard single-gang box.
Removing the Screwless Cover Plate
1. Press the black tab at the bottom edge of
the cover plate.
2. Pull the lower edge of the cover plate away
from the back.
3. Lift the cover plate up and off as shown in
Figure 1.
Figure 1: Removing the screwless cover plate
Replacing the Screwless Cover Plate
To replace the cover plate, place the hang bar at the top of the plate
onto the hang hook at the top of the switch base. Press the bottom in
place until it clicks.
On / Off
Auto
Screwless cover plate
Switch back
(buttons, mounting strap)
Hang bar
Hang hook
Mounting
screw holes
Side View
Screwless
cover plate
Switch back
(wire connections)
Figure 2: Replacing the screwless cover plate
LightSaver
®
LS-3C Wall Switch
Installation Instructions
On / Off
Auto
LCO-203
B
45678123
Wire colors shown are
Belden 8465 or equivalent
5-conductor 18 AWG cable
P2 (Red) to B8
S2 (White) to B4
S1 (Black) to B3
COM (Green) to B2
P1 (Brown) to B7
A
45678123
LS-3C
2800 De La Cruz Boulevard, Santa Clara, CA 95050
Technical Support: 800.879.8585 • 972.578.1699
www.wattstopper.com
08698r1 08/2007
Please
Recycle
Wiring
Maximum wire distance from the controller to the LS-3C is
150 feet. Wiring terminals are on the back of the switch.
Figure 3: Wiring to the LCO-203
Mounting
Secure the switch back to the wall box using the mounting
screw holes provided. Secure the screwless cover plate to
the switch back as shown in Figure 2.
  • Page 1 1

Legrand LightSaver® LS-3C Wall Switch Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI