McQuay MicroTech MAG Protocol Manual

Category
Water heaters & boilers
Type
Protocol Manual
Open Protocol Data Information Packet
Version 2.0
Group
: Controls
Date
: January 1998
© 2002 McQuay International
MicroTech
®
Absorption Chiller
Open Protocol
Data Communications
Proprietary Information - Subject to Change McQuay International
MicroTech Absorption Chiller Open Protocol Data Information 2
- C O N F I D E N T I
A L -
This Document may not be
copied or reproduced in any
way without the express
written consent of McQuay
International.
NOTICE
Copyright 1994,1998
McQuay International,
Minneapolis MN
All rights reserved
throughout the world.
McQuay International
reserves the right to change
any information contained
herein without prior notice.
No guarantees are given as to
the accuracy of information
provided.
McQuay International Proprietary Information - Subject to Change
3 MicroTech Absorption Chiller Open Protocol Data Information
Contents
Revision History ................................................................................................................................... 3
This is the first release. All information is new.Overview................................................3
Purpose.................................................................................................................................................. 4
MicroTech Absorption Gateway ..........................................................................................5
Purpose.................................................................................................................................................. 5
Components ..........................................................................................................................................5
Connecting to the MicroTech Absorption Gateway .............................................................................5
Converting between a Direct Connect and a Network MAG................................................................ 5
Diagnostic Variables ............................................................................................................................. 6
McQuay Absorption Chiller Variables .................................................................................8
Memory Map......................................................................................................................................... 8
Analog Data .......................................................................................................................................... 8
Digital Input Data................................................................................................................................ 10
Digital Output Data............................................................................................................................. 14
SW3 Status..........................................................................................................................................16
Start/Stop Data .................................................................................................................................... 17
Operating Time (Hours)...................................................................................................................... 17
Operating Time (Minutes/Seconds) .................................................................................................... 18
ID Code/PID Sampling/Data Pointer(s).............................................................................................. 19
Data Setting......................................................................................................................................... 21
Alarm Data.......................................................................................................................................... 23
Glossary of Terms ...............................................................................................................39
Index .....................................................................................................................................40
Revision History
Revisions
Version 2.0
Removed Network and Gateway diagrams which are now available in CD 573875Y, Open Protocol
Certified Drawings.
Version 1.5
This version includes the LC type absorption chiller unit.
Version 1.1
This is a formatting revision.
Version 1.0
This is the first release. All information is new.Overview
Proprietary Information - Subject to Change McQuay International
MicroTech Absorption Chiller Open Protocol Data Information 4
Purpose
The purpose of the McQuay International Open Protocol
for McQuay
absorption chillers is to
allow other automation integrators the ability to communicate with a McQuay absorption chiller.
Communications will be established through a MicroTech
interface panel that will communicate
with the McQuay Absorption Chiller. This interface panel is called the MicroTech Absorption
Gateway (MAG). Licensed BAS companies will be allowed to communicate with the MAG to
retrieve information about the McQuay absorption chiller via Open Protocol.
The results of Open Protocol can be summarized as follows:
Reading of the following Analog Information
Chilled Water Inlet & Outlet Temperatures
Hot Water Inlet & Outlet Temperatures
Low & High Temperature Generator Temperatures
Cooling Water Inlet & Outlet Temperatures
Condensation Temperature
Remote Reset Setting
Exhaust Gas Temperature/Steam Condensate Temperature
Fuel Control Valves 1 & 2 Position
Inverter Output Signal
Steam Control Valve Output Signal
Reading of the following Digital Output Information
Absorbent Solution Pumps
Refrigerant Pump
Ignition Signal
Heating, Cooling, Simultaneous, and Alarm Indicators
SVRP and SVRU valves
Cooling Main / Heating Main
Reading of the following Digital Input Information
Alarms
Starts/Stops of pumps and blowers
Combustion Signal
Remote Start/Stop Signal
Access to the absorptio
n
McQuay International Proprietary Information - Subject to Change
5 MicroTech Absorption Chiller Open Protocol Data Information
MicroTech Absorption Gateway
Purpose
The purpose of the MicroTech Absorption Gateway (MAG) is to read data from the McQuay
absorption chiller and store it so that automation integrators can read the status of the McQuay
absorption chiller. The automation integrators will get their data from the MAG and not directly
from the McQuay absorption chiller. The MAG continuously updates its information about the
status of the McQuay absorption chiller. All data from the MAG that comes directly from the
McQuay absorption chiller is read only; no data point can be changed through Open Protocol.
Components
This section will be used to explain the MAG hardware components. The components needed will
depend upon the number of McQuay chillers. A MAG that is in a network of two or more McQuay
Absorption Gateways and an OPM Panel will be referred to as a "Network MicroTech Absorption
Gateway." A MAG that is not in a network with an OPM Panel and other MAGs will be referred to
as "Direct Connect MicroTech Absorption Gateway". The generic name of "MicroTech Absorption
Gateway " (“MAG”) will be used when describing features that are common to both the Network
MAG and the Direct Connect MAG.
Connecting to the MicroTech Absorption Gateway
Network MAG
A Network MAG will be used whenever an Open Protocol Master (OPM) Panel is used. The OPM
provides a single communications port entry into a MicroTech network. The OPM consists of an
EnergyLine model 120 controller. The automation integrator at a licensed BAS company connects to
Comm Port A of the OPM, which is preconfigured for Open Protocol communications at 9600 baud.
Comm Port B of the OPM is a daisy chained, multidrop, 9600 baud, RS-485, proprietary McQuay
International Protocol Port. Comm Port B of the OPM will be connected to a MicroTech network.
The only way to read information from a Network MAG is through an OPM Panel. Direct
connection to a Network MAG is not possible because Comm Port B is configured for SLAVE, 9600
baud and Comm Port A, which is dedicated to receiving data from the McQuay absorption chiller, is
configured as USER, 4800 baud.
Direct Connect MAG
A Direct Connect MAG can be used whenever a single McQuay absorption chiller is used with Open
Protocol. A Direct Connect MAG cannot be used with an OPM Panel or in a MicroTech network.
A Direct Connect MAG’s Comm Port A is used to communicate with the automation integrator, and
Comm Port B is used to communicate with the Absorption Chiller Controller. Comm Port A, which
is the automation control integrator's Open Protocol communications port, is preconfigured for TTY,
Open Protocol communications at 9600 baud. Comm Port B, which is dedicated to receiving data
from the McQuay absorption chiller, is configured for USER, 4800 baud.
Converting between a Direct Connect and a Network MAG
Overview
Converting from either a Direct Connect MAG to a Network MAG or a Network MAG to a Direct
Connect MAG is done by downloading controller code to the MAG. In either case, monitor package
will be used to make the conversion.
The Network MA
G
Connect MAG each c
o
c
Proprietary Information - Subject to Change McQuay International
MicroTech Absorption Chiller Open Protocol Data Information 6
Direct Connect MAG to a Network MAG
The Direct Connect MAG can be direct connected to through its Comm Port A. Once Network
MAG controller code has been downloaded, the communications lines must be changed and its
address changed to the location the controller will occupy in the MicroTech network. The
communications line that is connected to the Absorption Unit Controller must be moved from Comm
Port B to Comm Port A on the Network MAG.
Network MAG to a Direct Connect MAG
The only way to direct connect to a Network McQuay Gateway is to change the controller address to
FF and reset power. This will change Comm Port B to 9600 baud TTY and direct connection will be
possible. During this time, communications with the McQuay absorption chiller will be lost. Once
Direct Connect MAG controller code has been downloaded, the communications lines must be
changed and the address set to 00. The communications line that is connected to the Absorption Unit
Controller must be moved from Comm Port A to Comm Port B on the Direct Connect MAG.
OPM
Network
Network
MAG
Comm Port B
Comm Port B
McQuay
Comm Port A
Network Sanyo Gateway
TC
Comm
Device
Comm Port A
Comm Port B
Direct
C
onnect
S
anyo
Gateway
Communications Line to Change
MAG
Absorption
Chiller
McQuay
Absorption
Chiller
Chiller
Absorption
McQuay
MAG
Direct
Connect
Diagnostic Variables
Following is a list of diagnostic memory locations that can be read in the MAG.
Description Address Range Conversion
Communications Check Output
0700 0-255 See Below
Sending or Receiving Data Output
0701 0-255 See Below
Processing Data Output
0702 0-255 See Below
Processing Alarm Data Output
0703 0-255 See Below
Communications Error
040D 0, 1 0= OK
1 = Comm
Error
McQuay International Proprietary Information - Subject to Change
7 MicroTech Absorption Chiller Open Protocol Data Information
Communications Check Output 0700
This is the memory location that contains the status of digital output 0. A 0 indicates the output is off
and a 1-255 indicates the output is on. This output is on for one second and off for one second if
communications exist between the MAG and the Absorption Unit Controller. The output is on for
two-tenths of a second and off for two-tenths of a second if communications do not exist between the
MAG and the Absorption Unit Controller. This location is a countdown timer for how long the
output has left to be on. If the location has a value of 9, the output has nine-tenths of a second left to
be on. A value of 0 means that the output is off.
Sending or Receiving Data Output 0701
This is the memory location that contains the status of digital output 1. A 0 indicates the output is off
and a 1-255 indicates the output is on. This output is on if the MAG is either sending or receiving
data to or from the Absorption Unit Controller. This output is off if the MAG is not communicating
with the Absorption Unit Controller. This output cycles off and on as the MAG communicates with
or processes data from the Absorption Unit Controller. When this output is on, the Processing Data
and Processing Alarm Data Outputs will be off. The MAG will either communicate with or process
data from the Absorption Unit Controller. Communication and processing will not occur at the same
time.
Processing Data Output 0702
This is the memory location that contains the status of digital output 2. A 0 indicates that output is
off and a 1-255 indicates the output is on. This output is on when the MAG is processing non-alarm
data it has received from the Absorption Unit Controller. Alarm data processing is indicated by
another output. This output is off if the MAG is not processing data from the Absorption Unit
Controller. This output cycles off and on as the MAG communicates with or processes data from the
Absorption Unit Controller. When this output is on, the Sending or Receiving Data and Processing
Alarm Data Outputs will be off. The MAG will either communicate with or process data form the
Absorption Unit Controller. Communication and processing will not occur at the same time.
Processing Alarm Data Output 0703
This is the memory location that contains the status of digital output 3. A 0 indicates that output is
off and a 1-255 indicates the output is on. This output is on when the MAG is processing alarm data
it has received from the Absorption Unit Controller. Non-alarm data processing is indicated by
another output. This output is off if the MAG is not processing alarm data from the Absorption Unit
Controller. This output cycles off and on as the MAG communicates with or processes data from the
Absorption Unit Controller. When this output is on, the Sending or Receiving Data and Processing
Data Outputs will be off. The MAG will either communicate with or process data form the
Absorption Unit Controller. Communication and processing will not occur at the same time.
Proprietary Information - Subject to Change McQuay International
MicroTech Absorption Chiller Open Protocol Data Information 8
McQuay Absorption Chiller Variables
Memory Map
All of these memory locations are in the MAG. All of the following memory locations are in
hexadecimal notation. Memory location 1342 will actually be $1342 (Hexadecimal memory
location 1342).
Table Heading Definitions
Description - This is the terminology used to describe the data point.
Address - This is the memory location(s) that holds the information for the data point.
Range - This can contain either a description of the address locations or a numerical range the
location(s) will contain.
Conversion - This is how the raw data needs to be converted to get the correct data reading.
DCH - If this area contains an "X", this data point is applicable for DC-H units.
DCS - If this area contains an "X", this data point is applicable for DC-S units.
DCU - If this area contains an "X", this data point is applicable for DC-U units.
NCU - If this area contains an "X", this data point is applicable for NC-U units.
LCU - If this area contains an "X", this data point is applicable for LC-U units.
Analog Data
Description Address Range Units
D
C
H
D
CS
D
C
U
N
C
U
L
C
U
Chilled Water Inlet Temperature
(Only while in Cooling or
Simultaneous units)
11B2
11B3
Hi Byte
Lo Byte
0.1*X+0=°F
X X X X X
Chilled Water Outlet Temperature
(Only while in Cooling or
Simultaneous units)
11B0
11B1
Hi Byte
Lo Byte
0.1*X+0=°F
X X X X X
Condensed Refrigerant Temperature
11C2
11C3
Hi Byte
Lo Byte
0.1*X+0=°F
X X X X X
Cooling Water Inlet Temperature
11BE
11BF
Hi Byte
Lo Byte
0.1*X+0=°F
X X X X X
Cooling Water Outlet Temperature
11C0
11C1
Hi Byte
Lo Byte
0.1*X+0=°F
X X X X X
Exhaust Gas Temperature (DC-*) or
Steam Condensate Temperature
(NC-U)
11C6
11C7
Hi Byte
Lo Byte
0.1*X+0=°F
X X X X
Fuel Control Valve 1 (%)
119A
119B
Hi Byte
Lo Byte
0.1*X+0=%
X X X
Fuel Control Valve 2 (%)
119C
119D
Hi Byte
Lo Byte
0.1*X+0=%
X
High Temperature Generator
Temperature
11C4
11C5
Hi Byte
Lo Byte
0.1*X+0=°F
X X X X X
Hot Water Inlet Temperature
(Only while in Heating)
11B8
11B9
Hi Byte
Lo Byte
0.1*X+0=°F
X
McQuay International Proprietary Information - Subject to Change
9 MicroTech Absorption Chiller Open Protocol Data Information
Description Address Range Units
D
C
H
D
CS
D
C
U
N
C
U
L
C
U
Hot Water Inlet Temperature (Only
for DC-S & DC-H units)
11BA
11BB
Hi Byte
Lo Byte
0.1*X+0=°F
X X
Hot Water Outlet Temperature
(Only while in Heating)
11B4
11B5
Hi Byte
Lo Byte
0.1*X+0=°F
X
Hot Water Outlet Temperature
(Only for DC-S & DC-H units)
11B6
11B7
Hi Byte
Lo Byte
0.1*X+0=°F
X X
Invertor Output Signal
119E 0-200 0.303*X+0 =Hz
X X X X X
Low Temperature Generator
Temperature
11BC
11BD
Hi Byte
Lo Byte
0.1*X+0=°F
X X X X
Remote Reset Current Signal
1196
1197
Hi Byte
Lo Byte
0.1*X+0=mA
X X X X X
Steam Control Valve Output Signal
11E0
11E1
Hi Byte
Lo Byte
0.1*X+0=%
X X
Chilled Water Inlet Temperature 11B2,11B3
This is the Chilled Water Inlet Temperature. These locations contain valid data only when the
Chiller/Heater is in the cooling mode or in the Simultaneous mode. This location is read by forming
the high byte (11B2) and the low byte (11B1) into a two byte number and dividing by 10 (0.1 * X +
0 = °F).
Chilled Water Outlet Temperature 11B0,11B1
This is the Chilled Water Outlet Temperature. These locations contain valid data only when the
Chiller/Heater is in the cooling mode or Simultaneous mode. These locations are read by forming
the high byte (11B0) and the low byte (11B1) into a two byte number and dividing by 10 (0.1 * X +
0 = °F).
Condensed Refrigerant Temperature 11C2,11C3
This is the Condensed Refrigerant Temperature. These locations are read by forming the high byte
(11C2) and the low byte (11C3) into a two byte number and dividing by 10 (0.1 * X + 0 = °F).
Cooling Water Inlet Temperature 11BE,11BF
This is the Cooling Water Inlet Temperature. These locations are read by forming the high byte
(11BE) and the low byte (11BF) into a two byte number and dividing by 10 (0.1 * X + 0 = °F).
Cooling Water Outlet Temperature 11C0,11C1
This is the Cooling Water Outlet Temperature. These locations are read by forming the high byte
(11C0) and the low byte (11C1) into a two byte number and dividing by 10 (0.1 * X + 0 = °F).
Exhaust Gas Temperature/Steam Condensate Temperature 11C6,11C7
This is the Exhaust Gas (DC-H, DC-S, DC-U) or Steam Condensate Temperature (NC-U). This
location is the Exhaust Gas Temperature for DC units or the Steam Condensate Temperature for NC
units. These locations are read by forming the high byte (11C6) and the low byte (11C7) into a two
byte number and dividing by 10 (0.1 * X + 0 = °F).
Fuel Control Valve 1 Output Signal 119A,119B
This is the Fuel Control Valve 1 Feedback Signal. These locations are read by forming the high byte
(119A) and the low byte (119B) into a two byte number and dividing by 10 (0.1 * X + 0).
Fuel Control Valve 2 Output Signal 119C,119D
This is the Fuel Control Valve 2 Feedback Signal. These locations are applicable on Simultaneous
units only (DC-S). These locations are read by forming the high byte (119C) and the low byte
(119D) into a two byte number and dividing by 10 (0.1 * X + 0).
High Temperature Generator Temperature 11C4,11C5
This is the High Temperature Generator Temperature. These locations are read by forming the high
byte (11C4) and the low byte (11C5) into a two byte number and dividing by 10 (0.1 * X + 0 = °F).
Proprietary Information - Subject to Change McQuay International
MicroTech Absorption Chiller Open Protocol Data Information 10
Hot Water Inlet Temperature 11B8,11B9
This is the Hot Water Inlet Temperature for DC-U units. These locations contain valid data only
when the Chiller/Heater is in the heating mode. These locations are read by forming the high byte
(11B8) and the low byte (11B9) into a two byte number and dividing by 10 (0.1 * X + 0 = °F).
Hot Water Inlet Temperature 11BA,11BB
This is the Hot Water Inlet Temperature. These locations are valid only for Simultaneous
Chiller/Heater units (DC-S) and Hot Water units (DC-H). These locations are read by forming the
high byte (11BA) and the low byte (11BB) into a two byte number and dividing by 10 (0.1 * X + 0
= °F).
Hot Water Outlet Temperature 11B4,11B5
This is the Hot Water Outlet Temperature for DC-U units. These locations contain valid data only
when the Chiller/Heater is in the heating mode. These locations are read by forming the high byte
(11B4) and the low byte (11B5) into a two byte number and dividing by 10 (0.1 * X + 0 = °F).
Hot Water Outlet Temperature 11B6,11B7
This is the Hot Water Outlet Temperature. These locations are valid only for Simultaneous
Chiller/Heater units (DC-S) and Hot Water units (DC-H). These locations are read by forming the
high byte (11B6) and the low byte (11B7) into a two byte number and dividing by 10 (0.1 * X + 0 =
°F).
Invertor Output Signal 119E
This is the output signal to the Invertor. This location is read by taking byte 119E and dividing by
3.3 (.30303 * X + 0 = Hz)
Low Temperature Generator Temperature 11BC,11BD
This is the Low Temperature Generator Temperature. These locations are read by forming the high
byte (11BC) and the low byte (11BD) into a two byte number and dividing by 10 (0.1 * X + 0 = °F)
Remote Reset Current Signal 1196,1197
This is the Remote Reset Current Signal from the BAS company. This is used to offset from the
heating or cooling setpoint, depending on the mode of the Chiller/Heater unit. These locations are
read by forming the high byte (1196) and the low byte (1197) into a two byte number and dividing
by 10 (0.1 * X + 0 = mA).
Steam Control Valve Output Signal 11E0,11E1
This is the output signal to the Steam Control Valve. This is only applicable on NC-U units. These
locations are read by forming the high byte (11E0) and the low byte (11E1) into a two byte number
and dividing by 10 (0.1 * X + 0 = %).
Digital Input Data
Description Address Range Units
D
C
H
D
C
S
D
C
U
N
C
U
L
C
U
Absorbent Pump 1 or Invertor
(Alarm)
1281
BIT 1
0=Normal
1=Alarm
X X X X
X
Absorbent Pump 1 (Off/On)
1282
BIT 7
0=Off
1=On
X X X X X
Absorbent Pump 2 (Alarm)
1281
BIT 2
0=Normal
1=Alarm
X X X X X
Absorbent Pump 2 (Off/On)
1283
BIT 0
0=Off
1=On
X X X X X
McQuay International Proprietary Information - Subject to Change
11 MicroTech Absorption Chiller Open Protocol Data Information
Description Address Range Units
D
C
H
D
C
S
D
C
U
N
C
U
L
C
U
Auto Restart after Power
Failure
1280
BIT 3
0=Disabled
1=Enabled
X X X X
Burner Signal
1280
BIT 0
0=Off
1=On
X X X
Chilled Water Flow Rate
1282
BIT 4
0=NoFlow
1=Flow
X X X X X
Chilled Water Pump Interlock
1281
BIT 7
0=Open 1=Closed
X X X X X
Control Valve 1
(DC-* units)
1280
BIT 7
0=Auto 1=Manual
X X X
Control Valve 1
(Automatic) (NC-U)
1284
BIT 0
0=Not in Auto
1= Auto
X X
Control Valve 1
(Manual Close) (NC-U)
1284
BIT 1
0=Not Mnl Close
1= Mnl Close
X
Control Valve 1
(Manual Open) (NC-U)
1284
BIT 3
0=Not Mnl Open
1=Mnl Open
X
Control Valve 1
(Manual Stop) (NC-U)
1284
BIT 2
0=Not Mnl Stop
1= Mnl Stop
X
Control Valve 2
1281
BIT 0
0=Auto 1=Manual
X
Cooling Mode
1280
BIT 4
0=No Cooling
1=Cooling
X X X X X
Cooling Water Flow Rate
1282
BIT 6
0=NoFlow
1=Flow
X X X X X
Cooling Water Pump Interlock
1282
BIT 1
0=Open 1=Closed
X X X X X
Flame Failure
1283
BIT 5
0=Normal
1=Alarm
X X X
Heating Mode
1280
BIT 5
0=No Heating
1=Heating
X X X
High Temperature Generator
Low Solution Level
1280
BIT 2
0=Normal
1=Alarm
X X X
High Temperature Generator
Pressure
1282
BIT 3
0=Normal
1=Alarm
X X X X
Hot Water Pump Interlock
1282
BIT 0
0=Open 1=Closed
X X
Purge Pump
1283
BIT 2
0=Off
1=On
X X X X
Proprietary Information - Subject to Change McQuay International
MicroTech Absorption Chiller Open Protocol Data Information 12
Description Address Range Units
D
C
H
D
C
S
D
C
U
N
C
U
L
C
U
Refrigerant Pump (Alarm)
1281
BIT 6
0=Normal
1=Alarm
X X X X X
Refrigerant Pump (Off/On)
1283
BIT 4
0=Off
1=On
X X X X X
Remote Start/Stop Signal 1
1284
BIT 6
0=Stop
1=Start
X X X X X
Simultaneous Mode
1280
BIT 6
0=No Simul
1=Simul
X
Absorbent Pump 1 or Invertor (Alarm) 1281, BIT 1
This is the alarm status of Absorbent Pump 1 or the Invertor. A 0 indicates normal operation and a 1
indicates an alarm condition.
Absorbent Pump 1 (Off/On) 1282, BIT 7
This is the off/on status of Absorption Pump 1. A 0 indicates the pump is off and a 1 indicates the
pump is on.
Absorbent Pump 2 (Alarm) 1281, BIT 2
This is the alarm status of Absorbent Pump 2. A 0 indicates normal operation and a 1 indicates an
alarm condition.
Absorbent Pump 2 (Off/On) 1283, BIT 0
This is the off/on status of Absorption Pump 2. A 0 indicates the pump is off and a 1 indicates the
pump is on.
Auto Restart after Power Failure 1280, BIT 3
This is the status of the Auto Restart after Power Failure. A 0 indicates the Auto Restart after Power
Failure is disabled and a 1 indicates that it is enabled.
Burner Signal 1280, BIT 0
This is the off/on signal of the Burner Signal for DC units. A 0 indicates an off signal and a 1
indicates an on signal.
Chilled Water Flow Rate 1282, BIT 4
This is the status of the Chilled Water Flow Rate switch. A 0 indicates no flow and a 1 indicates
flow.
Chilled Water Pump Interlock 1281, BIT 7
This is the status of the Chilled Water Pump Interlock. A 0 indicates an open interlock and a 1
indicates a closed interlock.
Control Valve 1 1280, BIT 7
This is the auto/manual status of Control Valve 1 for DC units (DC-*). A 0 indicates Auto mode and
a 1 indicates Manual Mode.
Control Valve 1 (Automatic) 1284, BIT 0
This is the Automatic control of Control Valve 1 for Steam units (NC-U). A 0 indicates the control
valve is not in the automatic mode and a 1 indicates the control valve is in the automatic mode.
Control Valve 1 (Manual Close) 1284, BIT 1
This is the Manual Close control of Control Valve 1 for Steam units (NC-U). A 0 indicates the
control valve is not in the manual close mode and a 1 indicates the control valve is in the manual
close mode.
McQuay International Proprietary Information - Subject to Change
13 MicroTech Absorption Chiller Open Protocol Data Information
Control Valve 1 (Manual Open) 1284, BIT 3
This is the Manual Open control of Control Valve 1 for Steam units (NC-U). A 0 indicates the
control valve is not in the manual open mode and a 1 indicates the control valve is in the manual
open mode.
Control Valve 1 (Manual Stop) 1284, BIT 2
This is the Manual Stop control of Control Valve 1 for Steam units (NC-U). A 0 indicates the
control valve is not in the manual stop mode and a 1 indicates the control valve is in the manual stop
mode.
Control Valve 2 1281, BIT 0
This is the auto/manual status of Control Valve 2. This location is applicable only for Simultaneous
units (DC-S). A 0 indicates Auto mode and a 1 indicates Manual mode.
Cooling Mode 1280, BIT 4
This indicates the unit is in the Cooling mode. A 0 indicates that chiller is not in Cooling and a 1
indicates that the unit is in Cooling.
Cooling Water Flow Rate 1282, BIT 6
This is the status of the Cooling Water Flow Rate. A 0 indicates no flow and a 1 indicates flow.
Cooling Water Pump Interlock 1282, BIT 1
This is the status of the Cooling Water Pump Interlock. A 0 indicates an open interlock and a 1
indicates a closed interlock.
Flame Failure 1283, BIT 5
This is the alarm status of the Flame Failure for DC units. A 0 indicates normal operation and a 1
indicates an alarm condition.
Heating Mode 1280, BIT 5
This indicates the unit is in the Heating mode. A 0 indicates that chiller is not in Heating and a 1
indicates that the unit is in Heating.
High Temperature Generator Low Solution Level 1280, BIT 2
This is the alarm status of the Low Solution Level in the High Temperature Generator for DC units.
A 0 indicates normal operation and a 1 indicates an alarm condition.
High Temperature Generator Pressure 1282, BIT 3
This is the alarm status of the High Temperature Generator Pressure. A 0 indicates normal operation
and a 1 indicates an alarm condition.
Hot Water Flow Rate 1282, BIT 5
This is the status of the Hot Water Flow Rate for Simultaneous units (DC-S) and Hot Water units
(DC-H). A 0 indicates no flow and a 1 indicates flow.
Hot Water Pump Interlock 1282, BIT 0
This is the status of the Hot Water Pump Interlock. A 0 indicates an open interlock and a 1 indicates
a closed interlock.
Purge Pump 1283, BIT 2
This is the off/on status of the Purge Pump. A 0 indicates the pump is off and a 1 indicates the
pump is on.
Refrigerant Pump (Alarm) 1281, BIT 6
This is the alarm status of the Refrigerant Pump. A 0 indicates normal operation and a 1 indicates an
alarm condition.
Refrigerant Pump (Off/On) 1283, BIT 4
This is the off/on status of the Refrigerant Pump. A 0 indicates the pump is off and a 1 indicates the
pump is on.
Remote Start/Stop Signal 1 1284, BIT 6
This is the first of the start/stop signals. This is the input that will be used for remote start/stop of the
chiller. A 0 indicates a stop signal and a 1 indicates a start signal.
Proprietary Information - Subject to Change McQuay International
MicroTech Absorption Chiller Open Protocol Data Information 14
Simultaneous Mode 1280, BIT 6
This indicates the unit is in the Simultaneous mode. A 0 indicates that chiller is not in Simultaneous
and a 1 indicates that the unit is in Simultaneous mode.
Digital Output Data
Description Address Range Units
D
C
H
D
C
S
D
C
S
N
C
U
L
C
U
Absorbent Pump 1
1286
BIT 1
0=Disabled
1=Enabled
X X X X X
Absorbent Pump 2
1286
BIT 2
0=Off 1=On
X X X X
Alarm Indication
1285
BIT 2
0=No Alm
1=Alarm
X X X X X
Answer Back Signal
1287
BIT 4
0=Off 1=On
X X X X X
Burner Controller Signal
1286
BIT 5
0=Disabled
1=Enabled
X X X
Burner Signal
1286
BIT 6
0=Off 1=On
X X X
Chilled and/or Hot Water Pump
Signal
1287
BIT 6
0=Off 1=On
X X X X X
Cooling Main/Heating Main
1285
BIT 4
0=Htg 1=Clg
X
Cooling Mode Indication
1287
BIT 7
0=Off 1=On
X X X X X
Cooling Water Pump Signal
1287
BIT 5
0=Off 1=On
X X X X X
Fuel Input Valve/Cooling Main
Mode (Close)
1287
BIT 1
0=Off 1=On
X X X X
Fuel Input Valve/Cooling Main
Mode (Open)
1287
BIT 0
0=Off 1=On
X X X X
Fuel Input Valve/Heating Main Mode
(Close)
1287
BIT 3
0=Off 1=On
X
Fuel Input Valve/Heating Main Mode
(Open)
1287
BIT 2
0=Off 1=On
X
Heating Mode Indication
1285
BIT 0
0=Off 1=On
X X X
Operation Indication
1286
BIT 0
0=Off 1=On
X X X X X
Refrigerant Pump Automatic
Function
1286
BIT 3
0=Disabled
1=Enabled
X X X X X
Refrigerant Pump Manual Function
1286
BIT 4
0=Disabled
1=Enabled
X X X X X
Simultaneous Mode Indication
1285
BIT 1
0=Off 1=On
X
SVRP valve (open/close)
1285
BIT 3
0=Off 1=On
X
SVRU valve (open/close)
1286
BIT 7
0=Off 1=On
X
McQuay International Proprietary Information - Subject to Change
15 MicroTech Absorption Chiller Open Protocol Data Information
Absorbent Pump 1 1286, BIT 1
This is the enable/disable signal to Absorbent Pump 1. A 0 indicates an the pump is disabled and a
1 indicates the pump is enabled.
Absorbent Pump 2 1286, BIT 2
This is the status of the on/off signal to Absorbent Pump 2. A 0 indicates an the pump is off and a 1
indicates the pump is on.
Alarm Indication 1285, BIT 2
This is the status of the Alarm Indication. A 0 indicates normal (no alarm) operation and a 1
indicates an alarm condition.
Answer Back Signal 1287, BIT 4
This is the status of the Answer Back Signal. This is used to confirm a start signal that has been
accepted. A 0 indicates an off condition and a 1 indicates a start or running condition.
Burner Controller Signal 1286, BIT 5
This is the status of the Burner Controller Signal. This is used to prevent burner operation in an
alarm condition. A 0 indicates either an off or alarm condition (disabled) and a 1 indicates that the
burner is able to operate normally (enabled).
Burner Signal 1286, BIT 6
This is the output to the Burner Controller. This location is applicable only for DC units. A 0
indicates an off signal and a 1 indicates an on signal.
Chilled and/or Hot Water Pump Signal 1287, BIT 6
This is the status of the Chilled and/or the Hot Water Pump Signal. A 0 indicates a pump off signal
and a 1 indicates a pump on signal.
Cooling Main/Heating Main 1285, BIT 4
This is the status of the Cooling Main/Heating Main indication output. This location is applicable
only for Simultaneous units (DC-S). A 0 indicates the unit is in heating main and a 1 indicates that
the unit is in cooling main.
Cooling Mode Indication 1287, BIT 7
This is the status of the Cooling Mode Output. A 0 indicates the unit is not in the Cooling mode and
a 1 indicates the unit is in the Cooling mode. This output is used as an indicator to remote systems.
Cooling Water Pump Signal 1287, BIT 5
This is the status of the Cooling Water Pump Signal. A 0 indicates a pump off signal and a 1
indicates a pump on signal.
Fuel Input Valve/Cooling Main Mode (Close) 1287, BIT 1
This is the status of the Fuel Input Valve/Cooling Main Mode close output. A 0 indicates the valve
is not closing (off) and a 1 indicates the valve is closing (on).
Fuel Input Valve/Cooling Main Mode (Open) 1287, BIT 0
This is the status of the Fuel Input Valve/Cooling Main Mode open output. A 0 indicates the valve is
not opening and a 1 indicates the valve is opening.
Fuel Input Valve/Heating Main Mode (Close) 1287, BIT 3
This is the status of the Fuel Input Valve/Heating Main Mode close output. This location is
applicable only for Simultaneous units (DC-S). A 0 indicates the valve is not closing (off) and a 1
indicates the valve is closing (on).
Fuel Input Valve/Heating Main Mode (Open) 1287, BIT 2
This is the status of the Fuel Input Valve/Heating Main Mode open output. This location is
applicable only for Simultaneous units (DC-S). A 0 indicates the valve is not opening (off) and a 1
indicates the valve is opening (on).
Heating Mode Indication 1285, BIT 0
This is the status of the Heating Mode Output. This location is applicable only for DC units. A 0
indicates the unit is not in the Heating mode and a 1 indicates the unit is in the Heating mode. This
output is used as an indicator to remote systems.
Proprietary Information - Subject to Change McQuay International
MicroTech Absorption Chiller Open Protocol Data Information 16
Operation Indication Contact 1286, BIT 0
This is the status of the chiller. A 0 indicates the unit is off and a 1 indicates the unit is on even
during the dilution cycle.
Refrigerant Pump Automatic Function 1286, BIT 3
This is the automatic start/stop of the Refrigerant Pump. A 0 indicates the automatic function is
disabled and a 1 indicates the automatic function is enabled.
Refrigerant Pump Manual Function 1286, BIT 4
This is the manual start/stop mode of the Refrigerant Pump. A 0 indicates the manual function is
disabled and a 1 indicates the manual function is enabled. The microprocessor can still stop the
pump while in the Manual Start mode.
Simultaneous Mode Indication 1285, BIT 1
This is the status of the Simultaneous Mode Output. This location is applicable only for
Simultaneous units (DC-S). A 0 indicates the unit is not in the Simultaneous mode and a 1 indicates
the unit is in the Simultaneous mode. This output is used as an indicator to remote systems.
SVRP Valve 1285, BIT 3
This valve is used for simultaneous chiller/heaters to drain refrigerant from the condenser sump.
SVRU Valve 1286, BIT 7
This valve is used for simultaneous chiller/heaters to drain refrigerant from the evaporator sump.
SW3 Status
Description Address Range Units
DC
H
DC
S
DC
U
NC
U
LC
U
Unit Model Type
1381
BITS 0-3
See long
description for
Model Types
Model Type
X X X X X
The following is a diagram of the layout of the SW3 switches:
10 þÿ Clock Speed
9 þÿ Data Sampling Time
8 þÿ Undefined
7 þÿ Remote Signal Polarity
6 þÿ Remote Start/Stop
5 þÿ Controller System
4 þÿ Unit Type (BIT 3)
3 þÿ Unit Type (BIT 2)
2 þÿ Unit Type (BIT 1)
1 þÿ Unit Type (BIT 0)
Off On
Unit Model Type 1381, BITS 0-3
These bits are used to determine the Model Type to the chiller. The following show the relationship
between bit settings and model types:
BIT 0 BIT 1 BIT 2 BIT 3 Model
0 0 0 0 DC-S or DC-H (Gas Fired)
1 0 0 0 DC-S or DC-H (Oil Fired)
0 1 0 0 DC-U (Gas Fired)
1 1 0 0 DC-U (Oil Fired)
0 0 1 0 DC-U without heating mode (Gas)
1 0 1 0 DC-U without heating mode (Oil)
0 1 1 0 TC-U
1 1 1 0 NC-U
McQuay International Proprietary Information - Subject to Change
17 MicroTech Absorption Chiller Open Protocol Data Information
BIT 0 BIT 1 BIT 2 BIT 3 Model
0 0 0 1 TC-U for heavy duty
1 0 0 1 NC-U for heavy duty
0 1 0 1 LC-U
1 1 0 1 LC-U for heavy duty
Start/Stop Data
Description Address Range Units
DC
H
DC
S
DC
U
NC
U
LC
U
Absorbent Pump 1
1488-148B Highest Byte-
Lowest Byte
BCD
X X X X X
Burner
1484-1487 Highest Byte-
Lowest Byte
BCD
X X X
Refrigerant Pump
148C-148F Highest Byte-
Lowest Byte
BCD
X X X X X
Unit
1480-1483 Highest Byte-
Lowest Byte
BCD
X X X X X
Absorbent Pump 1 1488-148B
This is the amount of Absorbent Pump 1 starts and stops. This number is recorded in BCD format.
Byte 1488 is the highest byte of the BCD string and byte 148B is the lowest byte of the BCD string.
This is a literal string, no conversion is needed to read the Start/Stop Data. The following will
illustrate this:
Byte 1488 1489 148A 148B
00 00 15 76
This translates to 1576 Starts/Stops.
BCD = Binary Coded Decimal
Burner 1484-1487
This is the amount of starts and stops of the Burner. These locations are applicable only for DC
units. This number is recorded in BCD format. Byte 1484 is the highest byte of the BCD string and
byte 1487 is the lowest byte of the BCD string. The starts/stops are read the same way as the
starts/stops for Absorbent Pump 1.
Refrigerant Pump 148C-148F
This is the amount of Refrigerant Pump starts and stops. This number is recorded in BCD format.
Byte 148C is the highest byte of the BCD string and byte 148F is the lowest byte of the BCD string.
The starts/stops are read the same way as the starts/stops for Absorbent Pump 1.
Unit 1480-1483
This is the amount of Chiller/Heater unit starts and stops. This number is recorded in BCD format.
Byte 1480 is the highest byte of the BCD string and byte 1483 is the lowest byte of the BCD string.
The starts/stops are read the same way as the starts/stops for Absorbent Pump 1.
Operating Time (Hours)
Description Address Range Units
D
C
H
D
C
U
D
C
S
N
C
U
L
C
U
Absorbent Pump 1 Operation
1588-
158B
Highest Byte-
Lowest Byte
BCD
X X X X X
Proprietary Information - Subject to Change McQuay International
MicroTech Absorption Chiller Open Protocol Data Information 18
Description Address Range Units
D
C
H
D
C
U
D
C
S
N
C
U
L
C
U
Burner Operation
1584-1587 Highest Byte-
Lowest Byte
BCD
X X X
Refrigerant Pump Operation
158C-158F Highest Byte-
Lowest Byte
BCD
X X X X X
Unit Operation
1580-1583 Highest Byte-
Lowest Byte
BCD
X X X X X
Absorbent Pump 1 Operation 1588-158B
This is the amount of Absorbent Pump 1 operating hours. This number is recorded in BCD format.
Byte 1588 is the highest byte of the BCD string and byte 158B is the lowest byte of the BCD string.
This is a literal string, no conversion is needed to read the Operating Time (Hours). The following
will illustrate this:
Byte 1488 1489 148A 148B
00 05 32 48
This translates to 53,248 hours.
BCD = Binary Coded Decimal
Burner Operation 1584-1587
This is the amount of Burner operating hours. These locations are applicable only for DC units.
This number is recorded in BCD format. Byte 1480 is the highest byte of the BCD string and byte
1483 is the lowest byte of the BCD string. The operating hours are read the same way as the
operating hours for Absorbent Pump 1.
Refrigerant Pump Operation 158C-158F
This is the amount of Refrigerant Pump operating hours. This number is recorded in BCD format.
Byte 1480 is the highest byte of the BCD string and byte 1483 is the lowest byte of the BCD string.
The operating hours are read the same way as the operating hours for Absorbent Pump 1.
Unit Operation 1580-1580
This is the amount of Chiller/Heater unit operating hours. This number is recorded in BCD format.
Byte 1480 is the highest byte of the BCD string and byte 1483 is the lowest byte of the BCD string.
The operating hours are read the same way as the operating hours for Absorbent Pump 1.
Operating Time (Minutes/Seconds)
Description Address Range Units
D
C
H
D
C
S
D
C
U
N
C
U
L
C
U
Absorbent Pump 1 Operation
1684-1685 Hi Byte Lo
Byte
In Seconds
X X X X X
Burner Operation
1682-1683 Hi Byte Lo
Byte
In Seconds
X X X
Refrigerant Pump Operation
1686-1687 Hi Byte Lo
Byte
In Seconds
X X X X X
Unit Operation
1680-1681 Hi Byte Lo
Byte
In Seconds
X X X X X
McQuay International Proprietary Information - Subject to Change
19 MicroTech Absorption Chiller Open Protocol Data Information
Absorbent Pump 1 Operation 1684-1685
This is the operating minutes and seconds of Absorbent Pump 1. This works with the Operating
Hours of Absorbent Pump 1 to present the total operating time of Absorbent Pump 1. Memory
location 1684 represents the high byte and memory location 1685 represents the low byte. These
memory locations store the Operating Time (Minutes and Seconds) in seconds. Therefore, to
determine the Operating Time (Minutes and Seconds), divide the number stored in bytes 1684 and
1685 by 60. This will give the Operating Minutes and the remainder will be the Operating Seconds.
Byte 1684 1685
$03 $7A
$037A = 890
890 / 60 = 14 (minutes), remainder of 50 (seconds)
Burner Operation 1682-1683
This is the operating minutes and seconds of the Burner. These locations are applicable only for DC
units. This works with the Operating Hours of the Burner to present the total operating time of the
Burner. Memory location 1684 represents the high byte and memory location 1685 represents the
low byte. These memory locations store the Operating Time (Minutes and Seconds) in seconds.
Therefore, to determine the Operating Time (Minutes and Seconds), divide the number stored in
bytes 1684 and 1685 by 60. This will give the Operating Minutes and the remainder will be the
Operating Seconds. See the above example for Absorbent Pump 1 for more details of determining
Operating Time (Minutes and Seconds).
Refrigerant Pump 1686-1687
This is the operating minutes and seconds of the Refrigerant Pump. This works with the Operating
Hours of the Refrigerant Pump to present the total operating time of the Refrigerant Pump. Memory
location 1684 represents the high byte and memory location 1685 represents the low byte. These
memory locations store the Operating Time (Minutes and Seconds) in seconds. Therefore, to
determine the Operating Time (Minutes and Seconds), divide the number stored in bytes 1684 and
1685 by 60. This will give the Operating Minutes and the remainder will be the Operating Seconds.
See the above example for Absorbent Pump 1 for more details of determining Operating Time
(Minutes and Seconds).
Unit Operation 1680-1681
This is the operating minutes and seconds of the Chiller/Heater unit. This works with the Operating
Hours of the Chiller/Heater unit to present the total operating time of the Chiller/Heater unit.
Memory location 1684 represents the high byte and memory location 1685 represents the low byte.
These memory locations store the Operating Time (Minutes and Seconds) in seconds. Therefore, to
determine the Operating Time (Minutes and Seconds), divide the number stored in bytes 1684 and
1685 by 60. This will give the Operating Minutes and the remainder will be the Operating Seconds.
See the above example for Absorbent Pump 1 for more details of determining Operating Time
(Minutes and Seconds).
ID Code/PID Sampling/Data Pointer(s)
Description Address Range Units
DCH DCS DCU NCU LCU
Alarm Pointer
168C See Below
X X X X X
PID Sampling
168D 5-30 Seconds
X X X X X
Unit Serial Number
1689-168B BCD
X X X X X
Alarm Pointer 168C
This location contains the data pointers for the Abnormal (Alarm) Data. The McQuay Controller
contains three alarm buffers. Each of these buffers holds the operating conditions of the chiller when
an alarm condition occurred. These three buffers store the operating conditions in a circular buffer
pattern.
Proprietary Information - Subject to Change McQuay International
MicroTech Absorption Chiller Open Protocol Data Information 20
Pointers are used to indicate where the next data is to be written to and to indicate that the buffers are
full and the newest data is overwriting the oldest data.
The data pointers for the two items are located in byte 168C. The format for these pointers is as
follows:
BIT 7 6 5 4 3 2 1 0
BYTE 168C
Data Full
Flag
Position for
next
Abnormal
Data
Position for
next
Abnormal
Data
Position for
next
Abnormal
Data
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41

McQuay MicroTech MAG Protocol Manual

Category
Water heaters & boilers
Type
Protocol Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI