Ascon tecnologic KR1E Quick start guide

Category
Measuring, testing & control
Type
Quick start guide

Ascon tecnologic KR1E is a panel mounting, Class II instrument designed to comply with European directives. It is used for temperature control in various industrial applications, including wine cooling and reheating. The controller features:

  • Dual setpoints for heating and cooling
  • Relay outputs for controlling heating and cooling elements
  • Configurable digital inputs for remote control or alarm functions
  • Modbus RTU communication for remote monitoring and control
  • Easy-to-use interface with a backlit LCD display and intuitive menu structure.

Ascon tecnologic KR1E is a panel mounting, Class II instrument designed to comply with European directives. It is used for temperature control in various industrial applications, including wine cooling and reheating. The controller features:

  • Dual setpoints for heating and cooling
  • Relay outputs for controlling heating and cooling elements
  • Configurable digital inputs for remote control or alarm functions
  • Modbus RTU communication for remote monitoring and control
  • Easy-to-use interface with a backlit LCD display and intuitive menu structure.
viale Indipendenza 56, 27029 - Vigevano (PV) - ITALY
Tel.: +39 0381 698 71, Fax: +39 0381 698 730
internet site: www.ascontecnologic.com
ube
WINE
CONTROLLER
78 x 35 mm
Model KR1E
22/03 - Code: ISTR_Q_KR1E_E_06_--
DECLARATION OF CONFORMITY AND
MANUAL RETRIEVAL
KR1E is a panel mounting, Class II instrument designed to comply
with European directives. All information about the controller use
can be found in the “Engineering Manual”.
The Declaration of Conformity and the manual of the controller
can be downloaded (free of charge) from the web-site:
www.ascontecnologic.com
Once connected to the web-site, search: KR1E
then click on KR1E.
In the lower part of the product page (in any language) is present
the download area with links to the documents available for the
controller (in the available languages).
Warning!
- Whenever a failure or a malfunction of the device may cause
dangerous situations for persons, things or animals, please
remember that the plant must be equipped with additional
devices which will guarantee safety.
-
We warrant that the products will be free from defects in material and
workmanship for 18 months from the date of delivery. Products
and components that are subject to wear due to conditions of
use, service life and misuse are not covered by this warranty.
Disposal
The appliance (or the product) must be disposed
of separately in compliance with the local
standards in force on waste disposal.
KR1E
PV
AT
Access to:
- Operator Commands
- Parameters
- Configuration
Access to:
-
Operator additional information
- Set Point
Increase the displayed
value/Selects the para-
meters list next element
Decrease the displayed
value or select the
previous element
Exit from Operator
commands/Parameter
setting/Configuration
Programmable key:
Start the programmed function
(Autotune, Auto/Man, Timer ...)
Access to:
- Set Point
Operator Mode Editing Mode
Confirm and go to
Next parameter
These 2 keys, pressed in sequence, allow to toggle
between MANual and AUTO modes.
+
Process Value
(in eng. units)
Output LEDs
Manual mode
Alarm active
Unit (°C/°F)
Autotune in progress
(flashing)
DISPLAY AND KEYS
Set Point (auto mode)
Output Value (manual mode)
Parameter value or State/
Function selected
(editing mode)
MODEL CODE
The Hardware resources are identied by the following Model Code.
KR1E A B C D E F G H
Model:
Supply voltage: 100... 240 Vac/
18... 28 Vac/
20... 30 Vdc
ELECTRICAL CONNECTIONS
RS485
DI1
OP3 OP2
NO NOCC
CN
ONF
Pt100
Pt1000/NTC/PTC
OP4
(note)
DI2
(note)
Ananogue Input
12 Vdc
(note)
12 Vdc
(note)
PV
PV
4... 20 A
3 wire transmitter
2 wire
transmitter
OP1
TERMINALS
Note: Terminal 4 can be programmed as:
- Digital Input (DI2) connecting a free of voltage contact between terminals 4 and 11;
- 0... 12 V SSR Drive Output (OP4) connecting the load between terminals 4 and 11;
- 12 Vdc transmitter power supply connecting the 2 wire transmitter between terminals 4 and 1;
for 3 wire transmitter connect terminal 4 to transmitter power supply input and terminal 1 and 2 to transmitter signal output.
: Out4 has a Logic Level 1 of: 12 VDC ±20%, 20 mA max.
mA
L
Pin:
q
2.5 mm (0.1 in.) max.
Stripped wire: L 5.5 mm (0.21 in.)
Neutral Line
Power supply
MOUNTING
DIMENSIONS
Overall dimensions (L x H x D):
78 x 35 x 69.5 mm
(3.07 x 1.37 x 2.73 in.)
Panel Cut-out (L x H):
71+0.6 x 29+0.6 mm
(2.79+0.023 x 1.14+0.023 in.)
Attention
The controller can be installed using 2 different types of brackets.
Follow the sequence 1, 2a, 3a for the screw bracket (collar
bracket for IP65), the sequence 1, 2b, 3b for the “butterfly”
brackets (2 pieces).
2a
2a
3b
3b
1
3a
3a
1
2b
2b
KR1E KR1EKR1E
Press for 2 seconds
the key
PARAMETERS SETTING
CONTROLLER DISPLAY
Increases the displayed value
Confirm value and pass to the next parameter
Decreases the displayed value
Parameter setting
To exit the parameters configuration procedure, press
for 3 seconds or wait for the end of the delay
(about 10 seconds)
The KR1E-xDRRRDxx controller is pre-configured (default
configuration) for wine applications where there is the
need to cool or reheat in thermostatic mode (on/off with
hysteresis) a tank with a PT100 probe in mono relay
output (Heat and Cool on OP1).
Heat mode
The controller action type can be identified by the color of the upper display (measurement):
Red: Heat mode only
Green: Cool mode only
Orange: The controller responds to temperature changes and selects the appropriate control mode
by operating the appropriate control output and displaying the setpoint to be reached.
The numbered red LEDs indicate, when lighted, the active (on) state of the corresponding relay output.
Cool mode Automatic Heat/Cool
selection
2 s
KR1E
KR1E
KR1E
KR1E
Line KR1E
Power Supply A
24Vac (-25... +12%) or 24Vdc (-15... +25%) L
100... 240 Vac (-15... +10%) H
Input + Ditigal input1 B
PT100, PT1000, mA + Digital Input 1 D
PTC, NTC, mA + Digital Input 1 P
Output OP1 (control output) C
Relay (1 SPST NO, 4 A/250 Vac) R
Output OP2 (control output) D
Relay SPST NO 2 A/250 Vac (resistive load) R
Output OP3 (alarm output) E
None -
Relay SPST NO 2 A/250 Vac (resistive load) selectable if Output 1 is present
R
Output OP4 (congurable) F
Digital I/O (see the Electrical Connections paragraph for details) D
Serial Communications G
TTL Modbus -
RS485 Modbus S
Terminal Type H
Standard (screw type non removable terminal blocks) -
With plug-in screw type terminal blocks E
With plug-in clamp type terminal blocks M
With plug-in terminal blocks (xed part only) N
Model Code example: KR1E-LDRRRD-E
KR1E controller for Wine applications
- Power supply: 24Vac/dc,
- Inputs: PT1000 or 4... 20 mA;
- Digital Input 1,
- 3 Relay Outputs (OP1: Alarm, OP2: Cold, OP3 Alarm),
- Conigurable OP4: Digital Input 2 or Transmitter power supply,
- TTL Port,
- Removable screw type terminals.
Parameters List (PASS: 30)
Group Param. Description
Value range or selection list
Default User
selection Note
inp
node Control mode selection
1 Heat
(SP on Out1)
or Cool
(SP2 on Out1)
,
2
Heat (SP on Out1) or Cool (SP2 on Out2),
3 Heat (SP on Out1) and Cool
(SP2 on Out2),
4 Heat(SP on Out1) or Cool(SP2 on Out2) or
Heat (SP on Out1) and Cool (SP2 on Out2)
,
5 Heat
(SP on Out1)
or Cool
(SP on Out1)
,
6 Heat
(SP on Out1)
or Cool
(SP on Out2)
,
7 Heat
(SP on Out1)
and Cool
(SP on Out2)
,
8 Heat
(SP on Out1)
or Cool
(SP on Out2)
or
Heat
(SP on Out1)
and Cool
(SP on Out2)
.
1
sEns Measurement input type Pt1 Pt100
Pt10 Pt1000
4.20 4… 20 mA Pt1
dp Decimal point position 0... 3 0
diF1 Digital input 1 function Stby Mode Standby (transition)
Stb2 Mode Standby (status)
HC.tr Heat <-> Cool (transition)
HC.St Heat <-> Cool (status)
nonE
diF2 Digital input 2 function nonE
di.a Digital Inputs Action 0... 3 0
See the manual for details
Pan usrb Key function
Stby Standby Mode
1H2C Heat <-> Cool toggle
HC.Sb Heat <-> Cool and
Auto <-> Standby
Auto
If HC.Sb: a 1 s pressure
toggles between
Heat <-> Cool mode.
A 5 s pressure puts the
controller in standby
ser
Add Controller Modbus address 1... 254 1 Modbus RTU slave
Protocol
bAud Modbus transmission speed 1200, 2400, 9600 baud,
19.2, 38.4 kbaud 9600
Notes: 1. Several successive pressures on the key allow the various groups of parameters to be scrolled.
2. A long pressure on the key allows to exit the Conguration mode and return to the operator mode
Parameters List (PASS: 20)
Param. Description
Value range or selection list
Default User
selection Note
OpEr Operative mode selection reg Auto,
stby Standby reg st.by: Control action stopped
reg: Control action running
SP Set point 1 -1999... +9999 (Engineering Unit) 0
SP2 Set point 2 -1999... +9999 (Engineering Unit) 0
HstH Heat Hysteresis 0... 9999 (Engineering Unit) 1
HstC Cool Hysteresis 0... 9999 (Engineering Unit) 1
AL1 Alarm 1 threshold (Low) AL1L... AL1H 0
AL2 Alarm 2 threshold (High) AL2L... AL2H 80
dP Decimal point position 0... 3 0
SPLL Setpoint Low Limit From 0 to the SPHL value 0
SPHL Setpoint High Limit From the value of SPLL to 1999 90
FiL Digital lter on the measured value 0 oFF
0.1... 20.0 s 1.0
HAL1 Alarm 1 Hysteresis 0...9999 (Engineering Unit) 1
HAL2 Alarm 2 Hysteresis 0...9999 (Engineering Unit) 1
Al.o Adjust Low Offset -300…+300 (Engineering Unit) 0
Note: Several successive pressures on the key allow to scroll the available Control parameters.
m Pressing no keys for 5 s, the controller automatically exits PASS20 menu and returns to the standard display and the current measurement.
KR1E KR1E KR1E
Operative Set Point Operative Set Point Changed
CONTROLLER OPERATION
To directly access the Operative Set Point change procedure, press the key (SP is displayed).
The variations to the Set Point value are made by pressing the / keys.
Wait for the timeout to store the new Operative Set Point and return to operator mode.
How to change the Operative Set Point
1 s
KR1E
KR1E KR1E
KR1E
KR1E KR1E KR1E KR1E
KR1E KR1E KR1E KR1E
Heat Cool mode
Control Mode Selection (PASS: 30)
Cool ModeHeat Mode
Heat (SP su Out1) or
Cool (SP2 su OUT1) Heat (SP and OUT1) or
Cool (SP2 and OUT2) Heat (SP and OUT1) and
Cool (SP2 and OUT2) Heat (SP and OUT1) and/or
Cool (SP2 and OUT2)
Heat (SP su Out1) or
Cool (SP su OUT1) Heat (SP and OUT1) or
Cool (SP and OUT2) Heat (SP and OUT1) and
Cool (SP and OUT2) Heat (SP and OUT1) and/or
Cool (SP and OUT2)
The change of the control direction between heating and
cooling is done by pressing the key for at least 1 s.
When the upper display flashes once (indicating that the
command has been accepted), release the key. The
instrument points out the selected action by changing
the color of the upper display.
Note: Active if USrb = 1H2C
Not active in Mode 3 and Mode 7
(Automatic Heat Cool toggle)
In 30, the navigation between the different groups is
carried out by means of the key . To access the
parameters of the selected group, press the key and
modify the value using the / keys. A brief pressure
on the key is used to exit the group, a long one to exit
the configuration menu.
KR1E KR1E
KR1E
Press the key or wait
for the timeout to store the
new Setpoints and return
to Operator Mode
Separate Heating (SP) and Cooling (SP2) Setpoints
Heat
Setpoint change Cool
Setpoint change
2 s
KR1E
KR1E KR1E KR1E
KR1E KR1E KR1E
2 s
Limits of the Setpoint values
Setting the lower limit of
the desired Setpoint
Validate the lower limit of
the desired Setpoint
Exit the setting mode
Setting the higher limit
of the desired Setpoint
Validate the higher limit
of the desired Setpoint
Exit the setting mode
Heat output
Hysteresis in °C Cool output
Hysteresis in °C
Setting the Hysteresis of Heat and Cool control outputs
KR1E
KR1E
KR1E
KR1E
2 s 2 s
KR1E
KR1E KR1E
KR1E
KR1E KR1E KR1E KR1E
DI1/DI2 Digital Input functions (pass = 30)
2 s
Standby mode activation
at input state transition
The 1st contact closure
switches the controller
to Standby.
The 2nd one reactivates
the Automatic mode.
Standby mode activation
at input state change
Close contact: Standby.
Open contact:
Automatic mode.
Control mode selection
at input state transition
Each contact closure
reverses the control mode
and the associated
setpoint.
Heat (SP) Cool (SP2)
Control mode selection
at input state change
Contact open:
HEAT mode with SP.
Contact close:
COOL mode with SP2.
or dif2or dif2or dif2or dif2
KR1E
KR1E
KR1E
KR1E
Setting the temperature alarm thresholds
2 s 2 s
Low alarm
threshold in °C High alarm
threshold in °C
KR1E
KR1E
KR1E
KR1E
2 s 2 s
Hysteresis of the
Low Alarm in °C Hysteresis of the
High Alarm in °C
Setting the hysteresis of temperature alarms
KR1E KR1E
KR1E
2 s
KR1E
KR1E KR1E
USrb Functions of the key (pAss 30)
To access the selected group
settings press the key
.
With PASS = 30, the navigation
between the different groups is
carried out by means of the key
.
To changhe the value press
the keys /
. A short
pressure on the key
allows to exit the group; a
long pressure allows to exit
the configuration menu.
Standby mode activation
The 1st pressure switches
the controller to Standby.
The 2nd one reactivates
the Automatic mode.
Heat Cool selection
Short pressures change
from Heat with SP
to Cool with SP2
(without Standby mode).
Heat or Cool or Standby
Short pressures change
the action Heat Cool.
The long pressures switch
the control Auto Standby.
It is possible to reset the controller to factory parameters (default parameters).
To load the default parameter values, press the
key for about 2 to display
PASS, set the PASS value to -481 and confirm with the key
.
The device restarts in its initial configuration with the default settings shown in
the table at page 1.
RESET THE CONTROLLER TO FACTORY PARAMETERS
2 s
KR1E
  • Page 1 1
  • Page 2 2

Ascon tecnologic KR1E Quick start guide

Category
Measuring, testing & control
Type
Quick start guide

Ascon tecnologic KR1E is a panel mounting, Class II instrument designed to comply with European directives. It is used for temperature control in various industrial applications, including wine cooling and reheating. The controller features:

  • Dual setpoints for heating and cooling
  • Relay outputs for controlling heating and cooling elements
  • Configurable digital inputs for remote control or alarm functions
  • Modbus RTU communication for remote monitoring and control
  • Easy-to-use interface with a backlit LCD display and intuitive menu structure.