A. Case :
Overload
Possible causes: the output power exceeds the machine tolerance range
Solution:
1: Reduce the load or disconnect the equipment that causes overload
2: When the inverter is turned off, due to overload, the machine will
be Locked in the off state, you need to manually turn off the switch and
then turn it back on again
B. Case :
Undervoltage
Possible causes of the problem:
the battery voltage is too low
DC input line is too thin and too long higher capacity load, or input line and
battery connection loosened.
The battery is too old, aging seriously.
The battery capacity is not enough to push the higher capacity load.
Use alligator clips to connect the battery. Resulting in insufficient power supply
Solution:
1: Please charge the battery
2: Use a thicker wire between the battery and the inverter and tighten
all DC input connections
3: Check if the battery is normal
4: Make sure the battery capacity is sufficient to run your device.
5: Use bolted connections and make sure the connections are secure
and tight.