Zone Disable and Indicator Module
Installation Guide Item Numbers: 4310-0087
MAN3035
Page 1
WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS
Ampac Technologies Australia Tel: +61 8 9201 6100 Europe Tel: +44 (0) 1302 833 522 New Zealand Tel: +64 9 443 8072 www.ampac.net
Description:
Monitors and Disables Zones
Eight push on / push off switches per card
Two Zone status indicators per switch (Alarm & Fault /
Isolate)
The Zone Disable and Indicator Card Kit consists of;
1 x Zone Disable Module
1 x 220mm RJ45 Comms cable.
1 x 350mm RJ45 Comms cable
Installation:
Observe anti-static precautions at all times
1. Unclip the PCB Assembly from the plastic housing
2. Slide in Zone Labels. Use LAB3100 label template.
3. Mount the plastic housing in the next free ancillary
cutout in the Fire Alarm Control Panel.
4. Clip the PCB assembly back into the plastic
housing
Card & PCB Securing Tabs
( Top & Bottom )
PCB
Clear Plastic Clip In Label
Clip on
Plastic Surround
( Push down here and pull
out to remove and insert labels )
Sli p In Label
Note: As per AS 1668
lettering on any of the
slip in labels must be
at least 5mm in height.
Windows for
Slip in Label
WI NDOWS FOR
SLIP IN LABEL
Figure 1: Zone Disable and Indicator Card (See
LAB3100.doc for Slip In Label)
Termination Link
In Out
Address
Switch
Set to 1
1 2 3 4
ON
C
N
1
C
N
2
CN1: Communications & 27V IN
from CN2 off the previous Front
Panel Card or CN9 on the Main Card
CN2: Communications & 27V OUT to Next Front Panel Card.
If Unsed the Termination Link Must be Inserted.
Top Card &
PCB Securing Clips
Bottom Card &
PCB Securing Clips
Figure 2: Zone Disable and Indicator Card PCB Layout
Connecting to the FACP
1. Power down the FACP
2. Set the required Address using the 4 way dip
switch (Figure 2)
3. If fitted as the last module the EOL link needs to be
fitted (Figure 2)
4. Using the supplied RJ45 cable connect the module
to the applicable Fire Alarm Control Panel (FACP)
(see Figure 3 & 4)
5. Power up the FACP
6. Using the applicable Configuration tool
ConfigManager (FireFinder/Plus) or LoopMaster
(LoopSense) configure the Zone Disable and
Indicator Module as follows:
LoopMaster.
Add the module in the panel add ons section
Then configure the applicable zones (Defaults
Zones 1 – 8)
Configmanager
On the Controller Configuration panel select the
Zone Cont
Then configure the applicable zones on the Zone
Controller viewing pane
NOTE: A Maximum of 15 Cards can be fitted to the
LoopSense Plus and FireFinder Plus panel range