Ampac High Level Interface Expander Board Installation guide

Category
Fire protection
Type
Installation guide

Ampac High Level Interface Expander Board provides the ability for FireFinder Series II Fire Alarm Control Panels (FACP’s) to support various high-level interfaces, including Building Management Systems, Paging Systems, Nurse Call Systems, EV3000, SmartGraphics, and MODBUS. It features RS232 or RS485 physical interface, supports up to three HLI Expanders per FACP, and allows for individual interface configuration for each expander. The board requires the latest HLI Firmware and compatible FACP application software for optimal performance.

Ampac High Level Interface Expander Board provides the ability for FireFinder Series II Fire Alarm Control Panels (FACP’s) to support various high-level interfaces, including Building Management Systems, Paging Systems, Nurse Call Systems, EV3000, SmartGraphics, and MODBUS. It features RS232 or RS485 physical interface, supports up to three HLI Expanders per FACP, and allows for individual interface configuration for each expander. The board requires the latest HLI Firmware and compatible FACP application software for optimal performance.

ADVANCED WARNING
SYSTEMS
High Level Interface Controller
Installation Guide Item Numbers: 4310-0080
MAN2985-1
N1236
Page 1
WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS
Ampac Technologies Australia Tel: +61 8 9201 6100 Europe Tel: +44 (0) 1302 833 522 New Zealand Tel: +64 9 443 8072 www.ampac.net
Description:
The High Level Interface Expander provides the ability
for the FireFinder Series II Fire Alarm Control Panels
(FACP’s) to support a range of high level interface
options.
The physical interface between the FACP and
equipment can be RS232 or RS485.
Typical applications where the HLI Expander is used
are:
Building Management
Paging system
Nurse Call Systems
EV3000
SmartGraphics
MODBUS
The FireFinder Series II FACP can support up to three
HLI Expanders
Note: Each HLI Expander added to a system can
ONLY be configured for ONE individual interface type.
Introduction:
Observe anti-static precautions at all times
The High Level Interface Controller Fast Fit Kit consists
of:
1 x HLI Controller
1 x CAB2804 450mm RJ45M Comms
1 x ENC2704-F Loop/B Term/B Plate III White
8 x HW1585 M3 x 6mm screws (only required for
the metal cabinet)
4 x HW2520 20mm standoffs (only required for the
metal cabinet)
2 x CON2578 Jumper link
Installation:
Power down and disconnect the batteries
Mounting
1. If necessary fit the stand offs to the suitably spaced
captive nuts in the lower right hand side backpan
position
2. Mount the board onto the standoffs using the 4 M3
x 6mm screws
3. If required the ENC2704 can be fitted above the
Loop Termination Board to provide extra mounting
for the HLI Controller (SP1 cabinets)
Connecting to the FACP
1. Using the supplied Comms cable connect CN4 on
the HLI Board to CN20 (Comms Out) of the Main
Control Board or, the RS485 Comms out of the
previous internal backpan board.
2. Ensure LK1 and LK3 are fitted.
3. Ensure LK2 is installed if it is the last Add-On on
the bus.
4. Bring the field cabling into the FACP through a
suitable knockout and terminate to the required
Connectors. See Figure 2
5. Set Address SW (Addresses 1 to 4 can be used).
See Figure 2 ensuring it is the same as the config
6. Power up the panel and reconnect the batteries
7. HLI Expander is configured using the
ConfigManager Tool for FireFinder Series II (refer
ConfigManager V6 AS4428 manual (MAN2599))
8. Test
HLI Setup Checklist:
Ensure the latest HLI Firmware and compatible FACP
application software are used.
Try to avoid configuring too many other add-ons
(especially SmartTerminal’s) on the same node and
add-on bus as the HLI. The worst case add-ons with
respect to timing include the HLI and Smart Terminal.
Try to distribute add-ons evenly across nodes where
possible.
HLI EV3000 Specific Setup:
1. Ensure RS485 EOL jumper link (LK1) is fitted on
the HLI
2. Ensure FACP EOL jumper link (LK2) is fitted on the
HLI if it is the last connected add-on on the FACP
add-on bus
3. Ensure 0V on the HLI (SHD on RS485 TB1) is
connected to 0V on the EV3000.
HLI MODBUS Specific Setup:
1. Ensure PLC Address and Parity (EEPROM
locations 95 and 96 at the FACP) match on the
MODBUS and FACP.
2. Ensure the same baud rate is setup on the FACP
and MODBUS
3. Ensure the same physical interface
(RS232/RS485) is setup on the FACP and
MODBUS and the corresponding hardware is
physically setup correctly
4. Ensure the same handshaking
(None/Hardware/Software) is setup on the FACP
and MODBUS and the corresponding hardware is
physically setup correctly
ADVANCED WARNING
SYSTEMS
High Level Interface Controller
Installation Guide Item Numbers: 4310-0080
MAN2985-1
N1236
Page 2
WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS
Ampac Technologies Australia Tel: +61 8 9201 6100 Europe Tel: +44 (0) 1302 833 522 New Zealand Tel: +64 9 443 8072 www.ampac.net
Connection and Settings
JTAG
LSB
12/10/2009
BRD43SPB4-
FACP
COMMS
EOL
ETHERNET
EOL
RS485
POWER
SERIAL
PARALLEL
+27V
RS485
ADDRESS
FACP BUS
0V
0V +27V
SHD -
+
SHD
-
+
-
FACP
0V
0V
FACP 0V
SHD
+
POWER
COMMS
MSB
+
-
+
5V
R36
R35
R11
R12
R13
R14
R16
R15
R21
R18
R24 C51
D6
U11
U6
CN3
U10
U12
R10
R9R6
L6
L5
L2
L1
C45
C56C62
C68
C27
C24
C32
C26
C37
C34
C25
C41
C57
ZDN2
R5
C48
C33
R4
C20
C74
R19
R23
U9
U5
U8
TH1
TH2
R3
C63
ZD5
TH6
T1
R34
R33
R27
R22
R2
R32
Q1
M2
M3
L4
L3
U1
D1 D2
D8
C66
C60
C71
C65
C59
C70
C64
TB1
1 2 3 4
SW1
CN1 CN2
TB3
TB2
CN4
CN8
D7
CN7
C72
C47
C40
C61
C49
C50
C36
C31
C58
C53
C23
C18
C21 C17
C29
C30
C42
C14
C15
C46
C43
C35
C22
C28
D5
R8
R31
R20
R1
R30
R29
R26
RN7
RN3 RN4 RN5 RN6
RN2
U13
U3
U2
U7
U4
X1
ZD4
ZD6
ZD3
ZD1
C1
C16
C12
C7
C9
C8
C13
C10
C11
C6
LK2
TH5
TP2
TP1
C38
C67
C55
LK3
ZDN1
R28
C19
D3
R17
N1236
C73
C44
C52
M1
D4
R7
CN5
ZD2
C54
RN1
TP88
TP89
3.3V
R25
LK1
Always Fitted
LK2
Fitted if the
HLI is the last
board on
the Bus
LK3
Fitted if
board
mounted
internally
Figure 1: High Level Interface Controller PCB layout
CN2 RS232 Out
CN4 RS485 Comms In from the previous RS485 Comms output or CN10 (Comms out) of the Main Control Card
CN5 RS485 Comms Out to RS485 Comms In of the next RS485 Add-On board.
CN6 27 Volts from CN8 of the Main Control Card or Power Connector of previous RS485 Add-On board.
CN8 Optional 27 Volts to the next RS485 Add-On board
TB1 RS485 Out
SW1 Address set SW as shown in Figure 2
LK1 EOL Always Fitted
LK2 EOL Link is fitted if the HLI is the last board on the Bus
LK3 EOL Link fitted if the board is mounted internally to a panel
LSB
FACP
COMMS
EOL
RS485
SERIAL
PARALLEL
+27V
ADDRESS
0V
0V +27V
SHD -
+
SHD
-
+
-
FACP
FACP 0V
SHD+
POWER
COMMS
MSB
+-
D6 ZDN2
C74
U8
TB1
1 2 3 4
SW1
CN2
TB3
CN4
CN8
D7
LK2
LK3
CN5
HLI CONTROLLER
(BRD43SPB)
LSB
FACP
COMMS
EOL
EOL
RS485
SERIAL
PARA L LE L
+27V
RS485
ADDRESS
0V
0V +27V
SHD -
+
SHD
-
+
-
FACP
FACP 0V
SHD
+
POWER
COMMS
MSB
+
-
D6 ZDN2
C74
U8
TB1
1 2 3 4
SW1
CN2
TB3
CN4
CN8
D7
LK2
LK3
CN5
LSB
FACP
COMMS
EOL
RS485
SERIAL
PARALLEL
+27V
ADDRESS
0V
0V +27V
SHD -
+
SHD
-
+
-
FACP
FACP 0V
SHD
+
POWER
COMMS
MSB
+-
D6 ZDN2
C74
U8
TB1
1 2 3 4
SW1
CN2
TB3
CN4
CN8
D7
LK2
LK3
CN5
HLI CONTROLLER
(BRD43SPB)
HLI CONTROLLER
(BRD43SPB)
MAIN CONTROL BOARD (BRD85MBA)
CN21
CN20
TH1
CN8
CN1
CN6
D13
D14
CN3
C12
BZ1
CN5
CN2
CN7
CN11
CH16
CH15
CH6 CH8
CH2
CH1
CN16
CN14
CN18
R17
TP3
RN17
RN20
CN4
CN10
CN15
CN13
CN17
c
ba
4 3 2
BRIGADE I/F
FRONT PANELEXPANSION LEDS
EXPANSION PANEL
MODEM
27V IN
PRINTER
PSU MONITOR
LOOP COMMS
1
+
CN1
CN2
1
SLAVE CPU
(302-6692)
CH8
CN1
CN2
1
CH8
CN1
CN2
1
SLAVE CPU
(302-6692)
SLAVE CPU
(302-6692)
U15
CN2
a b c
U11
U10
U14
U13
CPU BOARD
(BRD85CPU)
1 2 3 4
ON
ON
Address Switch Setting (SW1)
Add 1234
1
2
3
4
1000
0100
1100
0010
Address 1 shown
EOL
RS485
EOL
RS485
RJ45
RJ45
RJ45
RS 232
RS 485
RS 485
RS 232
RS 485
RS 232
SmartGraphics
MODBUS
EV3000
HLI
BMS
Nurse Call
LK1
Always
Fitted
LK1
Always
Fitted
LK1
Always
Fitted
LK2
Fitted
Last
Board
Figure 2: High Level Interface Controller Typical wiring layout and Address Setting
  • Page 1 1
  • Page 2 2

Ampac High Level Interface Expander Board Installation guide

Category
Fire protection
Type
Installation guide

Ampac High Level Interface Expander Board provides the ability for FireFinder Series II Fire Alarm Control Panels (FACP’s) to support various high-level interfaces, including Building Management Systems, Paging Systems, Nurse Call Systems, EV3000, SmartGraphics, and MODBUS. It features RS232 or RS485 physical interface, supports up to three HLI Expanders per FACP, and allows for individual interface configuration for each expander. The board requires the latest HLI Firmware and compatible FACP application software for optimal performance.