Carrier 38TY Series Installation Instructions Manual

Category
Split-system air conditioners
Type
Installation Instructions Manual

This manual is also suitable for

50TA/TZ/TY/YZ
40TA/TZ/TY/BZ-38TA/FZ/TY/BZ
Electric Heaters
Installation instructions
NOTE: This manual refers to accessories and options with
„D“ as the nal letter in the ordering code.
2
1 - SAFETY CONSIDERATIONS
Installation, servicing and maintenance of air conditioning
equipment can be hazardous due to system pressure and
electrical components. Only trained and qualied service
personnel should install, start-up or service air conditioning
equipment.
Untrained personnel can perform the basic maintenance
functions of cleaning and replacing lters. All other operations
should be performed by trained service personnel. When
working on air conditioning equipment, observe precautions in
the manual and stickers on the unit and other safety precautions
that may apply locally, regionally and nationally, as well as all
applicable laws.
Follow all safety codes. Wear safety glasses and work gloves
suitable for the work carried out.
Disconnect the unit electrically at the main switch before
carrying out any work inside the unit. All procedures that do not
require unit operation, as well as all cleaning and maintenance
operations must be done with the unit de-energised.
WARNING: Before performing service or maintenance
operations on the unit turn off the main power switch to the
unit. Electric shocks could cause serious injuries.
2 - RECEIVING THE ELECTRIC HEATER
2.1 - Inspect the shipment
Inspect the shipment to check for transport damage. If there are
signs of damage the transport managers must inspect the
component before it is installed. Immediately le a claim with
the shipping company or note the damage in the shipping
documents. The manufacturer is not responsible for damage
incurred during transport.
Check that all components listed on the shipping documents
have been supplied. If any item is missing, immediately inform
the nearest Carrier ofce and make a note on the shipping
documents. To prevent damage and/or loss keep all components
in their original packaging until they are installed by qualied
personnel.
3 – UNIT INSTALLATION
The electric heaters (accessory/option) are supplied for installa-
tion in the units and have not been factory-installed; they must be
installed as described in this manual. The manual only applies
to heaters with the ordering code ending in the letter „D“ (e.g.
X40TY04B09D (50TY/YZ 024 with 1.5 kW capacity).
A - The electric heaters are always installed outside the unit
and are xed to the panel of the indoor fan air discharge,
as shown in Figs. 1, 2 and 3.
B - Whether the unit is installed or not, the heater must be
attached by xing it to the panel of the indoor fan outlet,
using the four threaded sheet metal screws supplied with
the heater. The electric heater is installed so that the
control box is above or below depending on the position
of the indoor fan air discharge outlet (see Figs. 2 and 3).
C - If the unit is already installed and connected to the air
discharge duct, this must be cut in accordance with the
depth of the heater so that this can be installed. Next
attach the duct to the heater.
D - The heater thermal protection devices must always be
located in the upper part, whatever the position of the
heater control box.
E - The heater must be xed to the unit as shown in the
following gures:
Fig. 4: View of the electric heater
Fig. 5: View of the indoor fan outlet panel
Fig. 6: View of the installation of the heater in the unit
Fig. 1 - Front view
Fig. 2 - Side view: Unit with indoor fan situated on top
of the panel
Fig. 3 - Side view: Unit with indoor fan situated below
the panel
Indoor fan air discharge panelAir intake lter
UnitElectric heater Indoor fan
Air ow
Indoor fan Electric heater
Control box
Unit
Control box
Air ow
3
Fig. 4 - Electric heater (front view) F - Changing the electric heater control box from its standard
position as supplied to the alternative position is possible
if the indoor fan air discharge is located in the lower part
of the casing.
Proceed to change the control box position so that it is located
in the upper part when mounted in the unit (see Fig. 3).
Figs. 4, 5 and 6 show the heater with the control box in the
lower part and the thermal switches in the upper part. To
change the position it is enough to remove the four screws that
secure the frame of the electric heaters and the thermal
switches as shown below.
Fig. 7
Fig. 5 - Fan panel (front view)
The electric heater must be xed to the discharge air panel.
Align holes 1 of the heater with holes 1 of the panel. Secure
the heater as shown in Fig. 6, using the screws supplied.
Fig. 6 - View of the unit and electric heater
1 Holes and xing points of the electric heater to the unit,
with xing screws.
Fig. 8
Thermal switches
Thermal switches
Control box
Once the electric heater frame and the thermal switches have
been disconnected, turn the heater 180°, removing the strip that
covers them.
Insert the thermal switches in the hole below the control box so
that the manually reset thermal switch is accessible.
Gather the connection cables from the heaters and thermal
switches so that they are protected and hidden by the frame that
has been removed.
Re-insert the screws that were previously removed.
The control box and the thermal switches must be located in
the same zone of the heater, contrary to what is shown in Figs.
4 and 7 so that they can be installed in the unit when the fan is
located with its air discharge section in the lower part of the
unit (Fig. 3).
4
IMPORTANT: Whenever the electric heater power supply is
downstream of the unit main disconnect switch (Figs. 9, 10
and 11) it is not permitted to install a heater of higher capacity
(kW) than indicated in tables 1 and 2, that are the standard
heaters.
C - If the unit has been installed and an electric heater is to be
connected whose control power supply is not connected via
the main unit disconnect switch or if it is desirable to have an
independent power supply connect and protect it as follows:
- Cables of adequate wire section
- Fuses F1 with a current that complies with the heater
capacity (kW) installed.
- A bipole or tripole disconnect switch, depending on
the voltage with the necessary current (A).
- Locate a thermal-magnetic disconnect switch with
current (A) in accordance with tables 3 and 4 in the
electric heater control box, as described in chapter 5.2.
Standard heater connection
Fig. 9
4 - ELECTRIC HEATER CAPACITIES (kW)
The electric heater capacities for cooling models or additional
heater capacities for heat pumps, according to valid Carrier
publications, are:
Table 1 – Cooling only models
Unit Capacity, kW
50TA/TZ 024 4.0 or 4.6
38TA/FZ-40TY/BZ 024
50TA/TZ 036-048 6.0 or 9.0
38TA/FZ-40TY/BZ 036-048
50TA/TZ 060 9.0 or 13.5
38TA/FZ-40TY/BZ 060
50TA/TZ 072 and 084 12.0 or 18.0
38TA/FZ-40TY/BZ 072
38TA/FZ-40TY/TZ 084
Table 2 – Heat pumps
Unit Capacity, kW
50TY/YZ 024 1.5 or 2.0
38TY/BZ-40TY/BZ 024
50TY/YZ 036-048 3.0
38TY/BZ-40TY/BZ 036-048
50TY/YZ 060 4.5
38TY/BZ-40TY/BZ 060
50TY/YZ 072 and 084 6.0
38TY/BZ-40TY/BZ 072 and 084
Supplied with the voltages indicated in the price list, technical
data, wiring diagrams and applicable manuals.
5 – ELECTRICAL CONNECTIONS
Before the denitive installation of the electric heaters in the
unit a number of operations must be carried out.
5.1 – Power supply
The electric heater power supply is suitable for connection to
the unit control and power wiring box and to the general
disconnect switch of the unit.
The disconnect switch in the cooling only and heat pump units
is designed to support the current (A) of the components
connected to it.
Therefore the power supply of the electric heaters must be
connected downstream of the disconnect switch, as shown in
the unit wiring diagrams (see Figs. 9, 10 and 11).
Possible connections:
A - If the electric heater has not been installed and must be
incorporated, fuses F1 and the power cable section (L1,
L2, L3, N) are sufcient for the maximum power
consumption in cooling and heating modes.
B - If the unit has been installed and supplied with the electric
heater incorporated please check if fuses F1 and the power
cable section (L1, L2, L3, N) are sufcient for the new
power consumption. Remember that the unit will operate
in heating mode when the electric heater is installed.
Cooling only models = indoor fan plus electric heater
power consumption
Heat pump models = compressor plus indoor and outdoor
fan plus electric heater power consumption.
Fig. 10
Fig. 11
Legend:
Q1 - Unit main disconnect switch (incorporated)
F1 - Fuses to be eld-supplied by the installer
----- Wiring in the unit
----- Field wiring
NOTE: The unit main disconnect switch has been designed to
support the current (A) of the electric heaters that are
installed. It is not necessary to change it.
Electric heating
To the unit
Electric heating
To the unit
Electric heating
To the unit
5
5.2 – Thermal-magnetic disconnect switch
The following thermal-magnetic disconnect switches must be
incorporated in the electric heater control box (curve C). The
current must comply with the capacity (kW) of the electric
heater installed.
The thermal-magnetic disconnect switches are as follows and
match the models and capacities of the electric heaters in tables
3 and 4.
Table 3 – Cooling models
Power
supply
V-ph-Hz
Letter in wiring
diagram
50TA/TZ – 38TA/FZ – 40TA/TY/TZ/BZ
024 036 042-
048
060 072 084
400-3-50 F18 thermal-
magnetic switch (A)
16 16 16 25 25 32
230-1-50 25 32 - - - -
230-3-50 - 25 40 - 50 50
400-3-50 R3 electric heater
total (kW)
6 6
9
6
9
9
13.5
12 18
230-1-50 4 6 - - - -
230-3-50 - 6 9 - 12 18
Table 4 – Heat pumps
Power
supply
V-ph-Hz
Letter in wiring
diagram
50TY/YZ – 38TY/BZ – 40TY/BZ
024 036 042-
048
060 072-
084
400-3-50 F18 thermal-
magnetic switch (A)
6 10 10 10 16
230-1-50 16 16 - - -
230-3-50 - 16 16 16 20
400-3-50 R3 electric heater
total (kW)
1.5 3 3 4.5 6
230-1-50 2 3 - - -
230-3-50 - 3 3 4.5 6
These thermal-magnetic switches are located in the control box
of the electric heater, as shown in gures 12 and 13.
Fig. 12
Fig. 13
Thermal switch
Once installed in the control box, they must be connected to
contactor K8 in accordance with the wiring diagram. Afterwards
they must be connected to the main unit control box with the
power supply cables.
5.3 - Power supply cables
This manual refers to packaged units. The power supply cables
used for split system vary, units depending on the distance
between the indoor and outdoor units (maximum voltage loss
5%). The standard cables for the power supply in packaged
units are:
Fig. 14 - 230 V single-phase heaters with 2, 3, 4 and
6 kW capacity
F18 installation site
Dimensions, mm
kW A
2 and 4 3000
3 and 6 3200
Wire section, mm2
kW L1 N
2 and 3 2.5 2.5 2.5
4 4 4 4
6 6 6 6
Colour code:
L1 = Black
N = Blue
= Green/yellow striped
2 = Flexible pipe, type PG 13.5
6
5.4 – Power wiring cable
The connection cable between the electric heater control box
and the unit control box must be connected to ensure control
during operation.
Cables corresponding to the unit wiring diagram must be
connected between terminals 14, 19, 5 and 12 of the terminal
strip in the electric heater control box and in the unit control
box. For the packaged 50TA/TY units these have the following
characteristics:
Fig. 17
Dimensions, mm
50TA/TZ
50TY/YZ
kW A
024 1.5-6 3000
036-060 3-4, 5-6,
9-13.5
3900
072-084 6, 12, 18 5000
Wire section, mm2
kW 230 V, 3 ph 400 V, 3 ph
L1, L2, L3 L1, L2, L3,
1.5 1.5 1.5
3 1.5 1.5
4.5 2.5 1.5
6 4 1.5
9 6 2.5
12 10 4
13.5 10 4
18 16 6
Colour code:
L1, L2, L3 = Black
= Green/yellow striped
2 = Flexible pipe, type PG 13.5 for all capacities except 12 and 18 kW
– these are type PG 16
NOTE: The wire section is suitable for ambient temperatures
below 50°C.
NOTE: All data applies to packaged units. For split system
units the data depends on the distance between indoor and
outdoor units.
These cable assemblies must be run from the thermal-magnetic
switch of the electric heaters inside the control box to the power
and control box for the unit, as shown in the unit wiring dia-
grams. Cable , Fig. 16, is taken out of the casing conduit of
the electric heater control box , Fig. 18, and passed through a
conduit using the pre-punched hole in panel .
Fig. 16
Fig. 15 - 230 V three-phase or 400 V three-phase
heaters with 1.5, 3, 4. 5, 6, 9, 12, 13.5 and 18 kW
capacity
Dimensions, mm
50TA/TZ
50TY/YZ
A
024 3300
036-060 3900
072-084 5000
1 Number of the connection terminal and cable
2 Cables:
Section = 1 x 1 mm2
Colours: No. 5 and 12 = Grey
No. 14 = Black
No. 19 = Blue
3 Flexible pipe, type PG 7
4 Terminals:
Flag type (4 off)
Flag terminal protector (4 off)
Rod type, 0.75-1 mm2 (4 off)
Cables are taken out of conduit (Fig. 18) and run to the
unit power and control box through pre-punched hole , as
shown in Figs. 16, 18 and 19.
7
5.5 – Thermal protection
The electric heater includes two thermal protection devices,
one with manual reset and the other with automatic reset.
The rst one must always remain accessible and both must be
located in the upper part of the electric heater. Once connected,
this is in the air discharge of the indoor fan.
NOTE: The heating coil assemblies (accessory/option) can be
supplied with all required connection parts (thermal-magnetic
switches, cables etc.). In this case only the installation in the
panel shown and the electrical connection as shown in the
wiring diagram are required.
If the electric heater is supplied installed in the unit, no
additional operation is required, except in split system units
where the connection cables between the electric heater in the
indoor units must be run to the power and control box in the
outdoor unit.
NOTE: This manual refers to accessories and options with
„D“ as the nal letter in the ordering code.
WARNING: The power supply must always meet applicable
local, national and EU standards.
Fig. 18
Fig. 19
Legend
F18 - Thermal-magnetic switch to be installed in the electric heater
control box (if not in the electric heater).
K8 and K12 - Contactors
R3 - Electric heaters
F20 - Thermal switch with manual reset
F21 - Thermal switch with automatic reset
_____ - Wiring included
-------- - Wiring eld-supplied
Order No: 15050-20, 05.2007 - Supersedes order No: 13452-76, 10.2006 Manufacturer: Carrier, Spain.
Manufacturer reserves the right to change any product specications without notice. Printed in the Netherlands on chlorine-free paper.
Fig. 20 - Wiring diagram for the connection of the electric heaters (models 50TA/TZ/TY/YZ, 38TA/FZ/TY/BZ,
40TA/TZ/TY/BZ)
To the unit control box To the unit control box
400 V/3 ph ~/50 Hz version
(available with 230 V/3 ph ~/50 Hz
on request)
Unit terminals
Power wiring connection, common
for all voltages and models
230 V/1 ph ~/50 Hz
version
NOTE: If the electric heater is installed in the unit the
existing jumper between terminals 5 and 12 in the control box
must be removed once it is installed (see wiring diagram).
(Refer to the unit wiring diagram that is supplied with the unit.)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Carrier 38TY Series Installation Instructions Manual

Category
Split-system air conditioners
Type
Installation Instructions Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI