Frick Quantum LX Condenser/Vessel Operating instructions

Type
Operating instructions
OPERATION – SERVICE
(SESSION LEVEL 2)
FRICK QUANTUMâ„¢ LX
CONDENSER/VESSEL
CONTROL PANEL
VERSION 3.0x
Form 090.562-0 (AUGUST 2011)
File: SERVICE MANUAL - SECTION 90
Replaces: S90-5612 O/MARCH 2008
Dist: 3, 3a, 3b, 3c
OPERATION - SERVICE
090.562-O (AUG 11) FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
Page 2 OPERATION - SERVICE
Table of Contents
SETUP DESCRIPTION ............................................................................................................................................ 5
Wiring ............................................................................................................................................................... 5
Configuration .................................................................................................................................................... 5
Operation .......................................................................................................................................................... 5
IDENTIFYING A CONDENSER/VESSEL SYSTEM ...................................................................................................... 5
The Operator Interface Panel ............................................................................................................................ 5
The Condenser I/O Panel ................................................................................................................................... 5
The Vessel I/O Panel ......................................................................................................................................... 5
CONDENSER/VESSEL SYSTEM CONFIGURATIONS ................................................................................................. 6
System Installation ............................................................................................................................................ 7
WIRING FOR AC POWER ....................................................................................................................................... 7
Interface Panel .................................................................................................................................................. 7
Condenser/Vessel Panel .................................................................................................................................... 7
CHECKING THE AC POWER ................................................................................................................................... 8
Interface Panel .................................................................................................................................................. 8
Condenser/Vessel Panel .................................................................................................................................... 8
WIRING FOR COMMUNICATIONS .......................................................................................................................... 9
Interface Panel .................................................................................................................................................. 9
Wiring the Quantumâ„¢ LX Panel ................................................................................................................. 9
Condenser/Vessel System Communications Wiring Diagram ........................................................................... 10
INITIAL STARTUP AND LOGIN .............................................................................................................................. 11
VERIFYING COMMUNICATIONS ....................................................................................................................... 12
PANEL CONFIGURATION ........................................................................................................................... 13
CONDENSER CONFIGURATION .................................................................................................................. 14
Introduction ........................................................................................................................................ 14
Calibrating Sensors ...................................................................................................................... 14
Establishing Setpoints .................................................................................................................. 14
Step Control ................................................................................................................................. 14
Step Configuration ....................................................................................................................... 15
Summer/Winter Sequence ........................................................................................................... 15
Variable Speed Fan ...................................................................................................................... 15
Control Overrides ........................................................................................................................ 15
Clearing Alarms ............................................................................................................................ 16
Condenser Status ......................................................................................................................... 16
VESSEL CONFIGURATION ......................................................................................................................... 17
Introduction ........................................................................................................................................ 17
Calibrating Sensors ...................................................................................................................... 17
Establishing Setpoints .................................................................................................................. 17
Level Control ................................................................................................................................ 17
Pump Control ............................................................................................................................... 17
Safeties ........................................................................................................................................ 18
Alarms ......................................................................................................................................... 18
Vessel Status ............................................................................................................................... 18
090.562-O (AUG 11)
Page 3
FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
OPERATION – SERVICE
AMMONIA SYSTEM CONFIGURATION ....................................................................................................... 19
Introduction ........................................................................................................................................ 19
Configuration - Ammonia Sensors ............................................................................................... 19
Calibrating Ammonia Sensors ...................................................................................................... 19
Setpoints - Ammonia Safeties ...................................................................................................... 20
TROUBLESHOOTING ..................................................................................................................................... 21
Operator Interface Panel ........................................................................................................................... 21
Condenser/Vessel Panel(s) ........................................................................................................................ 21
TYPICAL SYSTEM CONFIGURATION .............................................................................................................. 22
CONNECTING A COMPUTER DIRECTLY TO A QUANTUMâ„¢ LX CONTROL PANEL ............................................ 22
Using A Web Browser (Ethernet) .............................................................................................................. 23
Operator Access ....................................................................................................................................... 24
To Change Setpoints ................................................................................................................................. 24
Keys And Key Functions ............................................................................................................................ 25
MENU STRUCTURE .............................................................................................................................................. 26
GRAPHIC SCREENS ............................................................................................................................................. 27
OPERATING STATUS ....................................................................................................................................... 27
USER DEFINED OPERATING STAUS SCREEN – Condenser or Vessel ............................................................... 28
STATUS
Condenser Status ............................................................................................................................... 29
Vessel Status ...................................................................................................................................... 30
Trending - Trending Setup ................................................................................................................. 31
Trending - Real Time Trending ........................................................................................................... 14
Trending – History Trending ............................................................................................................... 33
Trending – Real Time Data Log .......................................................................................................... 34
Trending – History Data Log ............................................................................................................... 35
Event Log ........................................................................................................................................... 36
SAFETIES
Current Safeties .................................................................................................................................. 37
Safety History ..................................................................................................................................... 38
SETPOINTS
Condenser Step Control ...................................................................................................................... 39
Condenser Summer Sequence ............................................................................................................ 42
Condenser Winter Sequence .............................................................................................................. 43
Condenser Variable Speed Fan ........................................................................................................... 44
Condenser Control Overrides ............................................................................................................. 45
Vessel 1 (2 or 3) Level Control ............................................................................................................ 46
Vessel 1 (2 or 3) Pump Control ........................................................................................................... 48
Vessel 1 (2 or 3) Safeties .................................................................................................................... 50
Ammonia Safeties............................................................................................................................... 51
PID Setup - Condenser ....................................................................................................................... 52
PID Setup - Vessel.............................................................................................................................. 53
Overview to Tuning a PID Controller ............................................................................................ 54
Auxiliaries – Analog Inputs – Condenser (or Vessel) Safeties ............................................................. 56
Auxiliaries – Digital Input Configuration (Condenser or Vessel) .......................................................... 57
Auxiliaries – Digital Output Configuration - Condenser ...................................................................... 58
Auxiliaries – Digital Output Configuration - Vessel ............................................................................. 59
090.562-O (AUG 11) FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
Page 4 OPERATION - SERVICE
Panel .................................................................................................................................................. 60
CALIBRATION
Vessel 1 (2 or 3) ................................................................................................................................. 62
Ammonia ............................................................................................................................................ 63
ANALOG OUTPUTS – Condenser Outputs .......................................................................................... 64
Condenser (or Vessel) Auxiliaries – Page 1 ........................................................................................ 66
Condenser (or Vessel) Auxiliaries – Page 2 ........................................................................................ 67
CONFIGURATION
Panel Configuration ............................................................................................................................ 68
Condenser Step Configuration ............................................................................................................ 69
Communications ................................................................................................................................. 70
Ethernet ............................................................................................................................................. 72
SESSION ................................................................................................................................................... 74
SERVICE
Digital ................................................................................................................................................. 75
Analog ................................................................................................................................................ 75
Communications Log .......................................................................................................................... 76
Communications Loop Back Test ........................................................................................................ 77
Diagnostics ......................................................................................................................................... 77
Software Maintenance ....................................................................................................................... 78
HELP ......................................................................................................................................................... 80
ABOUT ...................................................................................................................................................... 81
MISCELLANEOUS SCREENS ....................................................................................................................... 82
Alpha .................................................................................................................................................. 82
ALARMS/SHUTDOWNS MESSAGES ................................................................................................................. 83
Warning
The Quantumâ„¢ LX Control has the capability of being modified by the user/owner in order to obtain different performance
characteristics. Any modification to the standard default settings may have a severe negative impact on the operation and
performance of the equipment. Any modification to these control settings is the sole responsibility of the user/owner and Frick
disclaims any liability for the consequences of these modifications. It is possible that the modification of these settings may
cause improper operation and performance that may result in property damage, personal injury or death. It is the
responsibility of the user/owner to evaluate and assess the consequences of their actions prior to modifying the controls for
this unit.
090.562-O (AUG 11)
Page 5
FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
OPERATION – SERVICE
SETUP DESCRIPTION
The following Setup Guide is meant to assist the
installation technician in making all necessary
electrical power, control and communications
connections to a Quantumâ„¢ LX Condenser/Vessel
system. They will be provided also with the basic
information necessary to login and configure the
system. It will then aid in troubleshooting the system
should problems arise. This Guide will help to ensure:
WIRING
ï‚· Location of incoming AC source power
to all panels (Interface and Remote)
ï‚· Basic installation guidelines are
followed.
ï‚· Location, polarity and grounding of
communications wiring.
ï‚· Location of all control (I/O) wiring.
ï‚· Proper powering up of all panels.
CONFIGURATION
ï‚· Verifying communications.
ï‚· Calibrating sensors.
ï‚· Setting up operating Setpoints.
OPERATION
ï‚· Verifying the data being returned to the
Interface panel from all remote panels.
ï‚· Checking and clearing of alarms.
ï‚· Ammonia Configuration
IDENTIFYING A CONDENSER/VESSEL
SYSTEM
A system will include one Operator Interface
Panel and one Condenser I/O Panel and/or
possibly a Vessel I/O Panel.
THE OPERATOR INTERFACE PANEL
Each system will have an Operator Interface
Panel, as shown below:
The Operator Interface Panel (we will call it
the Interface Panel throughout the rest of
this guide) is the central point of the system,
whereby any I/O panels are attached. It can
easily be identified by the presence of a
display screen and a keypad. The Interface
Panel monitors and controls all of the I/O
panels that are attached to it, through RS-
485 serial communications (to be explained
later).
The Interface Panel runs the actual program
that provides the control for the system.
Through communications, it monitors the
status of each attached I/O panel, and
provides the necessary control instructions
for each panel to perform. Additionally, all
setpoints are stored in the Interface Panel.
Status of the system may be monitored form
here, and appropriate changes made to
system operation.
THE CONDENSER I/O PANEL
Each system may have one Condenser panel:
The panel does not have a display or keypad.
THE VESSEL I/O PANEL
Each system may have one Vessel panel:
The panel does not have a display or keypad.
A Vessel panel can control between one and
three separate vessels.
090.562-O (AUG 11) FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
Page 6 OPERATION - SERVICE
CONDENSER/VESSEL SYSTEM
CONFIGURATIONS
As stated before, each complete Condenser/Vessel
system will consist of one Interface Panel, and may
have a Condenser panel and/or a Vessel panel (a
Vessel Panel can control up to three vessels).
See the example below of a system:
Multiple Condenser/Vessel systems may be
interconnected via a common Ethernet connection.
Each system operates independently of one another
yet they may all be monitored and controlled through
a common computer. Such a system would include
the Quantumâ„¢ LX Condenser/Vessel Interface Panel,
an Ethernet Hub or Switch, Condenser/Vessel panels
and a computer running a Web Browser. A simplified
example of such a system (with three
Condenser/Vessel systems) is shown here:
Condenser
I/O
Panel
Interface
Panel
Interface
Panel
Vessel
I/O
Panel
Interface
Panel
Computer or
HMI
Ethernet Hub or
Switch
Condenser
I/O
Panel
Vessel
I/O
Panel
Communications from
Comm. 4 (PL14)
on Quantum board
Interface
Panel
Condenser
I/O
Panel
Vessel
I/O
Panel
090.562-O (AUG 11)
Page 7
FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
OPERATION – SERVICE
SYSTEM INSTALLATION
An in depth installation setup is beyond the scope of
this guide, however some basic rules can be
observed:
ï‚· Maintain a total distance of 2000 feet or less
between the Operator Interface Panel, and
the very last Remote I/O Panel on any one
communications cable run. As will be
explained later, it is possible to have two
separate communications cable runs,
depending upon the total number of Remote
I/O Panels. Keep in mind that neither of
these cable runs can exceed 2000 feet in
length.
ï‚· The system is capable of Ethernet
communications, this may be something to
consider when placing Interface Panels, as
you would want a nearby Ethernet
connection to be available.
ï‚· Keep all communications wiring in a separate
conduit from control wiring.
ï‚· When wiring for communications, it is
important to ground only one end of the
communications cable. This ground will be
located in the very last Remote Panel of
each communications cable run. If the
communications were to be grounded at
both ends, then it would be possible for
ground loops to develop, which could impair
communications between panels.
ï‚· Interface Panels should be located in easy
access areas, and should be mounted at eye
level for screen viewing.
ï‚· I/O Panels are rated for both indoor and
outdoor use. Although access to the Remote
Panels will be rare after installation and
setup, it is still advantageous to keep them
accessible for potential maintenance
situations (reasonable lighting, sufficient
door swing, etc.).
ï‚· Install all panels within a convenient distance
of a power source.
WIRING FOR AC POWER
Interface Panel
The incoming AC power will consist of three 14
AWG wires (hot, neutral and ground).
 Unlatch the two ¼ turn cover latches to
the Interface panel, and open the door.
ï‚· Inside the enclosure, you will find a
power supply and a terminal strip, as
shown here:
ï‚· Connect the three incoming AC wires to
the terminal screws as shown
previously.
ï‚· Proceed to the section entitled
Checking
the AC Power
.
Condenser/Vessel Panel
As with the Interface panel, the incoming AC
power will consist of three 14 AWG wires (hot,
neutral and ground).
 Unlatch the two ¼ turn cover latches to
the Interface panel, and open the door.
ï‚· Inside the enclosure, you will find a long
DIN rail at the left side of the panel. At
the top of the DIN rail is a terminal strip
(if the unit is equipped with an optional
panel heater, there will also be a circuit
breaker), as shown here:
ï‚· Connect the three incoming AC wires to
the terminal screws shown above.
ï‚· Notice that there are multiple number 2
terminals, connection may be made to
any of them.
ï‚· Proceed to the section entitled
Checking
the AC Power
.
Hot Neutral Ground
Ground
Ho
t
Neutral
090.562-O (AUG 11) FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
Page 8 OPERATION - SERVICE
CHECKING THE AC POWER
Interface Panel
ï‚· Ensure that the Control Power switch is in
the OFF position.
ï‚· Energize the 120 Volt circuit at its source.
ï‚· Using a DVM, measure the voltage at the AC
power terminal strip. Ensure that you read
approximately 120 VAC between Hot and
Neutral, and Hot and Ground. There must not
be voltage between Neutral and Ground.
ï‚· Once the incoming voltage has been
verified, turn the Control Power switch to
ON.
ï‚· On the enclosure door, and watch the
Quantumâ„¢ LX controller (on the backside of
the door). You should notice various LED’s
blinking or flashing.
ï‚· Watch the display on the front of the door.
After a short period of time, you should
notice the display showing a boot sequence.
Various text messages will be shown as it
proceeds with the boot-up process. When
finished, a screen similar to the following
image should be visible:
ï‚· If the panel has reached the point of showing
the above screen, the boot process was
successful. Turn OFF the Control Power
switch, and De-energize the 120 Volt circuit
at its source.
ï‚· If the panel does not reach to the point of
showing the above screen, then
troubleshooting will be required. Refer to
end of this guide entitled
Troubleshooting
.
Condenser/Vessel Panel
ï‚· Unlike the Interface Panel, the
Condenser/Vessel panel(s) do not have an
external power switch. Instead, the
enclosure will contain two HOA (Hand-Off
Automatic Modules). These modules allow
the technician to override control signals, by
manually energizing components. An
example of one of these modules is shown
here:
ï‚· Notice in the above pictorial, there is a Red
power OFF tab, and a black power ON
plunger. These items are located on a circuit
breaker for each of the two HOA modules.
Together, they act as the Control Power
switch.
ï‚· Push each of the Red power OFF tabs down.
The Black power ON plunger should pop up.
If the plunger does not pop up, then the
power was already off. Do this to both HOA
modules.
ï‚· Energize the 120 Volt circuit at its source.
ï‚· Using a DVM, measure the voltage at the AC
power terminals (1, 2 and PE). Ensure that
you read approximately 120 VAC between
Hot and Neutral, and Hot and Ground. There
must not be voltage between Neutral and
Ground.
ï‚· Once the incoming voltage has been
verified, push in the Black power ON
plungers of both HOA modules.
ï‚· To the right of the HOA modules are several
I/O boards. There will be at least one Digital
board (recognizable by the plug-in I/O
modules), and one Analog board. Inspect all
boards for the presence of flashing, blinking
or steadily lit LED’s. If LED’s are lit on all
boards, then power has been properly
applied.
 If LED’s are not lit on all boards, then refer
to the section entitled
Troubleshooting
.
Red, power
OFF tab
Black, power
ON plunger
090.562-O (AUG 11)
Page 9
FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
OPERATION – SERVICE
WIRING FOR COMMUNICATIONS
NOTE: Refer to the section entitled
CONDENSER/VESSEL SYSTEM COMMUNICATIONS
WIRING DIAGRAM, for additional information about
how the system is configured.
Interface Panel
Depending upon the configuration of the system,
there may be a Condenser panel, and/or a Vessel
panel. A common communications cable needs to
be run from the Quantumâ„¢ LX panel to each of
these. Refer to the section entitled
Condenser/Vessel System Communications
Wiring Diagram
. The incoming RS-485
communications cable to the interface panel will
be a two-conductor, shielded type. Frick Controls
recommends the use of Belden #9841 or equal.
Wiring the Quantumâ„¢ LX Panel
Use the following wiring procedure:
ï‚· Open the Quantumâ„¢ LX panel
door.
ï‚· On the inside of the enclosure door,
you will find the Quantumâ„¢ LX
controller, and a three position
terminal block, as shown here:
Notice that there are two wires that connect
from the left side of the terminal block, to
the Quantumâ„¢ LX at PL14 (Comm. 4). These
are the internal TX / RX communications
wires. You will be connecting the external
field communications wires to the other
(right) side of these terminals.
ï‚· Take the end of the incoming
communications cable, and strip
about 2 inches of insulation from
the end.
ï‚· Clip the shield wire back even with
the insulation, and either use heat
shrink tubing to cover the area, or
electrical tape. This will help to
ensure that any strands of the
shield that may be exposed don’t
come into contact with any live
voltage areas of the panel.
ï‚· Strip the end of each of the two
remaining conductors back about ¼
of an inch. Generally there are only
three color combinations available
depending on the type of cable
used. There will be either a black
and white/clear insulated wire, a
red and white/clear insulated wire,
or a red and black. Either way, one
of the wires should be black. Take
the black wire and insert it into the
top position of the terminal block
(labeled as –TX/RX).
ï‚· Take the remaining wire
(white/clear or red) and insert it
into the second position down from
the top of the terminal block
(labeled as +TX/RX).
ï‚· It is very important that the colors
of these wires follow this same
polarity scheme throughout the
daisy-chaining process to all panels.
ï‚· Refer to the
CONDENSER/VESSEL
SYSTEM COMMUNICATIONS
WIRING DIAGRAM
in this guide to
verify dipswitch settings.
Comm. 4 Location
+TX/RX
-TX/RX
N/C
CONDENSER/VESSEL SYSTEM COMMUNICATIONS WIRING DIAGRAM
Shield Wire
Not Connected
Operator
Interface
Panel
Note: For the
DIPSWITCH settings
shown below, a
shaded box
indicates a closed
or ON position, an
unshaded box
indicates an open
or OFF position.
= OFF
COMM. 4 Cable Run
Twist
Shield
Wires
To
g
ether
CONDENSER
12345678
DIPSWITCH
Settings
Analog Board 1
Digital Board 1
Digital Board 2 (opt)
123456
123456
VESSEL
12345678
DIPSWITCH
Settings
Analog Board 1
Digital Board 1
Digital Board 1 (opt)
123456
123456
090.562-O (AUG 11)
Page 11
FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
OPERATION – SERVICE
INITIAL STARTUP AND LOGIN
To initiate the startup and login process, the Interface
Panel and each of the Condenser and Vessel Panels
will need to be powered up. It is assumed that the
power has already been verified in the
Checking The
AC Power
section.
Once the Interface Panel has fully booted, the
following screen will appear:
This is the default screen, and will appear each time
power has been cycled.
From the above screen, press the [Menu] key.
The following drop down menu will appear:
Using the keypad up/down arrow keys scroll down to
highlight
Session
and press [Enter].
The following screen will replace the
Operating
Screen
:
Change the User Level to [3], and enter a password of
[4824]. This sets the Level to 3, which allows access
to all features. Press [Submit].
Select the [Menu] key again. This time, a more
expanded menu will appear:
From the above menu, select [Home] to return to the
Operating Status
screen.
At this point, the Interface Panel has been set to
allow access for the remainder of all procedures.
090.562-O (AUG 11) FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
Page 12 OPERATION - SERVICE
VERIFYING COMMUNICATIONS
The first step in verifying communications is to view
what I/O boards have been detected by the
Quantumâ„¢ LX Interface Panel. This information will
appear on the
About
screen, shown here:
Review the information that is shown in the Analog
and Digital Board areas of the screen. Compare what
is shown against what is actually installed.
NOTE: This screen does not update (refresh)
automatically. To see any new or different
information that may occur, you must access a
different screen, then come back to this one to
see any new data.
The analog board area of the screen can list up to
two possible analog boards that are allowed (one for
Condenser and one for Vessel). In the digital board
area, Up to four total boards may be listed:
ï‚· A Condenser panel will have one standard
digital board, and can have one optional
digital board.
ï‚· A Vessel panel will have one standard
digital board, and can have one optional
digital board.
Compare what is displayed here with what is actually
installed in your system. If a board is physically
installed in a panel, yet does not show up on this
screen, then find the panel that the board is located
in, and visually check the RX and TX LED’s on the
board. These LEDs should be flashing. The RX LED will
be flashing much faster than the TX LED, but neither
should be off completely, as this indicates a potential
wiring problem.
Start by verifying that the boards within the first panel
in the communications line are correctly being
detected. Then move on to the next panel. If the first
panel in the communications daisy chain shows
correctly, but there is a problem with the second
panel, then do nothing with the wiring up to and
including the first panel. Inspect instead the last panel
for proper communications polarity and connections.
A good indication that you have wires backwards
(reversed) would be that the RX LED is on solid within
the suspect panel. If wiring WAS found to be
incorrect, make the correction, and then access the
Communications
screen by selecting
Configuration
from the Main Menu, then Configuration, and finally
Communications
.
On the Communications screen shown above, use the
[Tab] key to select
Redetect IO Comms
and press
[Enter]. This will cause the Quantumâ„¢ LX controller
to reinitiate all communications with the system. After
redetecting IO Comms, wait about 30 seconds, then
access the
About
screen once again. If the wiring
issue has been corrected, the questionable I/O board
should now be listed, and the RX/TX LED’s for that
board should be flashing normally.
When all installed boards have been detected, then
the basic setup is complete. You can now move on to
configuring the system operating parameters.
090.562-O (AUG 11)
Page 13
FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
OPERATION – SERVICE
PANEL CONFIGURATION
Panel Configuration
Access this screen from the Main Menu. Select
Configuration > Panel Configuration
. The following
screen will appear:
If a Condenser is installed, it should be
enabled
. The
same is true for each installed Vessel. The Panel
configuration screen also provides the ability to
supply a unique name for each installed Vessel. After
moving the cursor to one of the Name fields, press
the Up Arrow key to access an alpha/numeric data
entry screen, as shown here:
The
Alpha
screen shows a graphic representation of
the numerical keypad. The symbols that appear above
each key on this screen are the possible combinations
of symbols that are associated with the digital portion
of the key.
As an example, suppose that you wanted to modify
the text line in the screen example shown. You want
to change the line from reading
Vessel 1
, to
Recirculator.
The first thing you would do, is to use
the [Backspace] key on the keypad to position the
cursor (blinking vertical line), to the far left side of the
text. Notice as the cursor backspaces, it erases the
current line of text.
Press the number [6] key (notice that the capital
R
is
one of the symbols in the line right above the [6] key).
A capital
P
will appear in the
Current Character
box.
Continue to press the [6] until the capital
R
appears
there. Now press the [Up Arrow] key, and notice that
the
R
has been placed on the text line in the first
position.
Next press the [8] key on the keypad, and continue
pressing it until the small
e
appears in the
Current
Character
box. Press the [Up Arrow] key to place the
e
on the text line. Continue entering text until you are
satisfied with the changes that you have made, press
the [Enter] key to accept them, and you will be
returned to the previous screen. Once all vessel
names have been entered (if desired), press the
[Submit] key.
NOTE: If many fields need to be renamed, the
user can plug a standard computer keyboard (PS2
style plug) into the socket labeled PL7 of the
Quantumâ„¢ LX processor board. Refer to the
following pictorial:
090.562-O (AUG 11) FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
Page 14 OPERATION - SERVICE
CONDENSER CONFIGURATION
Introduction
If a Condenser is not part of the installed system, skip
to the Vessel Configuration. Before the Condenser
system can be effectively put into operation, certain
setup parameters must be performed and verified. The
following listing shows these basic steps:
ï‚· Calibrating Sensors - The first of these steps
is to calibrate all installed sensors. A sensor
that is out of calibration will cause improper
and inefficient operation of the system.
ï‚· Establishing Setpoints - Setpoints need to be
set to define the various ranges that the
system will control within.
 Step Configuration – This assigns a
sequence of operation that all fans,
pumps and motors can be energized or
de-energized, in any combination, to
achieve the desired control.
 Variable Speed Fan –This allows any
installed variable speed fan to be
customized with regard to its speed and
on/off control.
 Control Overrides – Here you are able to
fine tune the system by allowing certain
conditions to be delayed from occurring
until the system settles.
 Alarms – Alarms and Warnings are inevitable
during system setup, you may view any
alarms and clear them from here.
 Condenser Status – Once everything has been
setup, the operation of the system can be
monitored from this screen.
Calibrating Sensors
Each temperature, pressure or humidity sensor on the
Condenser must be calibrated before the system is put
into operation.
Access this screen from the Main Menu. Select
Calibration
>
Condenser
:
The process used for establishing calibration values is
relatively simple. For temperature for example, it will
require a container of ice water or an infrared digital
temperature probe.
First, establish the temperature for a specific
temperature sensor. If a digital infrared measurement
device is used, simply enter the calibrated
temperature into the
Current Value
box and press
[Submit]. The system will automatically calculate the
correct
offset
value to use. If an ice bath is used,
simply allow the temperature of the sensor to
stabilize, and then enter 32 into the
Current Value
box
and press [Submit]. This process should be repeated
for each sensor in the system.
Establishing Setpoints
Step Control
Condenser Step Control setpoints must be setup.
Access this screen from the Main Menu. Select
Setpoints
>
Condenser
>
Step Control
.
These setpoints are used to configure the
operating characteristics for both summer and
winter modes.
ï‚· Control/Defrost Setpoints
ï‚· Deadband/Delay selection
ï‚· Outside Air Temp. Control
090.562-O (AUG 11)
Page 15
FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
OPERATION – SERVICE
Step Configuration
Fans and pumps need to be assigned to specific steps.
Access this screen from the Main Menu. Select
Configuration
>
Condenser Step Configuration
:
Summer/Winter Sequence
Summer and Winter Sequence setpoints
must be setup. Access this screen from the
Main Menu. Select
Setpoints
>
Condenser
>
Summer Sequence (or Winter Sequence)
.
An identical screen will appear for Winter
Sequence. These screens allow the steps
that were assigned from the
Step
Configuration
screen to turn on starting with
the lowest numbered step. Steps are turned
off with the highest numbered step which is
currently on, and descend to the lowest
numbered step. Steps with the same
sequence number will turn on as a group.
Steps assigned as zero will be disabled.
Variable Speed Fan
Variable Speed Fan setpoints must be setup.
Access this screen from the Main Menu. Select
Setpoints
>
Condenser
>
Variable Speed Fan
.
This screen allows the user to optimize the
settings for a Variable Speed Fan.
Control Overrides
Access this screen from the Main Menu. Select
Setpoints > Condenser
>
Control Overrides
:
The high pressure and low pressure controls
specify the pressures at which all steps should be
turned on or turned off, respectively. The Low
Temperature Override permits any steps that are
configured as water pumps with override control
to be shutdown under low temperature
conditions.
090.562-O (AUG 11) FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
Page 16 OPERATION - SERVICE
Clearing Alarms
Access this screen from the Main Menu. Select
Safeties >
Condenser >
Safeties
>
Current
:
This screen shows any alarms or shutdowns that
are currently active for the Condenser.
The alarms/shutdowns may be cleared for the
Condenser by tabbing to the [Clear Safeties]
button in the upper right corner, and press
[Enter].
Condenser Status
Access this screen from the Main Menu. Select
Status
> Condenser
:
Many of the operating characteristics for the
Condenser can be viewed from here.
090.562-O (AUG 11)
Page 17
FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
OPERATION – SERVICE
VESSEL CONFIGURATION
Introduction
If a Vessel is not part of the installed system, then go
to the Condenser Configuration. Before the Vessel
system can be effectively put into operation, certain
setup parameters must be performed and verified. The
following listing shows these basic steps:
ï‚· Calibrating Sensors - The first of these steps
is to calibrate all installed sensors. A sensor
that is out of calibration will cause improper
and inefficient operation of the system.
ï‚· Establishing Setpoints - Setpoints need to be
set to define the various ranges that the
system will control within.
 Level Control – The level control system
can be customized here.
 Pump Control – This allows for fine
tuning of the installed pumps.
 Safeties – Here you may assign certain
operational ranges that will cause an alarm or
warning to be generated if exceeded.
 Alarms – Alarms and Warnings are
inevitable during system setup, you may
view any alarms and clear them from
here.
 Vessel Status – Once everything has been
setup, the operation of the system can be
monitored from this screen.
Calibrating Sensors
Each temperature, pressure or humidity sensor on the
Vessel should be calibrated before the system is put
into operation.
Access this screen from the Main Menu. Select
Calibration
>
Vessel 1 (2 or 3):
Establishing Setpoints
Level Control
Vessel Level Control setpoints must be setup for
each Vessel that is enabled. Access these
screens from the Main Menu. Select
Setpoints
>
V
essel 1 (2 or 3)
>
Level Control
.
This screen permits the installer to utilize either
analog level control with a PI Loop, or digital
level control based on a single level transmitter,
or two float sensors.
Pump Control
Access this screen from the Main Menu. Select
Setpoint > Vessel 1 (2 or 3)
>
Pump Control
:
First, the pumps and auxiliaries should be
enabled in the bottom right hand corner. If the
Pump Differential control is utilized, the pressure
across the pump is monitored in order to ensure
pressure stays above the
Minimum Differential
Pressure
.
090.562-O (AUG 11) FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
Page 18 OPERATION - SERVICE
Safeties
Access this screen from the Main Menu. Select
Setpoints > Vessel 1 (2 or 3)
>
Safeties
:
This screen allows the installer to enable the
appropriate analog and digital alarm inputs as well as
setpoints associated with the alarms.
Alarms
Access this screen from the Main Menu. Select
Safeties >
Vessel 1 (2 or 3) >
Safeties
>
Current
:
This screen shows any alarms or shutdowns that
are currently active for the selected Vessel.
The alarms/shutdowns may be cleared for the
Vessel by tabbing to the [Clear Safeties] button in
the upper right corner, and press [Enter].
Vessel Status
Access this screen from the Main Menu. Select
Status
> Vessel 1 (2 or 3).
Many of the operating characteristics for the Vessel
can be viewed from here.
090.562-O (AUG 11)
Page 19
FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
OPERATION – SERVICE
AMMONIA SYSTEM CONFIGURATION
Introduction
Before the Condenser/Vessel system can be effectively
put into operation, certain setup parameters must be
performed and verified. The following listing shows
these basic steps:
ï‚· Configuring Ammonia Sensors - The first of
these steps is to configure the installed
ammonia sensors. This allows the controller
to be able to properly display warning
messages about the ammonia system.
 Calibrating Sensors – Next you will need to
calibrate all installed ammonia sensors. A
sensor that is out of calibration can cause a
potentially dangerous ammonia leak to be
undetected.
 Safeties – Here you may assign operational
ranges that will cause an alarm or warning to
be generated if an ammonia reading is
exceeded.
Configuration - Ammonia Sensors
There are three system wide warning/shutdown
outputs that can be configured. To access this
configuration screen, select
Menu
>
Configuration
>
Digital I/O > Digital Outputs > Page 2:
At the bottom of this screen you can configure the
board and channel for the three Ammonia Output
warning and shutdown alarms. These will alert the
user if ANY of the ammonia sensors has an active
warning or shutdown. These warnings and shutdowns
can be used for plant warnings that pertain to
ammonia and not standard shutdowns or warnings.
Calibrating Ammonia Sensors
Each Ammonia sensor that is to be used must be
calibrated before the system is put into operation.
Sensors may be installed on both the Condenser and/or
Vessels (up to three total sensors).
The first step in configuring and calibration the
ammonia sensors, is to insure that all sensors are first
plugged in.
NOTE: Set the User Level to 3 (from the
Session
screen).
Access the
Ammonia Calibration
screen from the
Main Menu. Select
Calibration
>
Ammonia:
Notice that there are three lines on this screen,
labeled as Ammonia 1, 2 and 3. If you custom name
each of these sensors (as described later in this
manual), your custom names will replace those shown
here.
Use the above screen to calibrate each ammonia
input channel using an ammonia detector.
The first box on each line is for
Current Value
. Read
the value shown on the ammonia detector for the
first sensor, and enter that reading into the
Current
Value
box. Use the Offset box to adjust the Current
Value.
Set the Low and High Range values according to the
ranges of the sensor itself.
The Sensor Signal type must be set next. A drop-
down menu is provided to select between the
following choices:
ï‚· None
ï‚· 0-5V
ï‚· 1-5V
ï‚· 4-20mA
ï‚· Pot.
ï‚· ICTD
ï‚· RTD
ï‚· CT
ï‚· RPM
090.562-O (AUG 11) FRICK® QUANTUM™ LX CONDENSER/VESSEL CONTROL PANEL
Page 20 OPERATION - SERVICE
ï‚· Vibration
ï‚· 0-10V
ï‚· +/- 5V
Most sensors will be 4-20mA.
Next, the Device Source must be selected. This
setting tells the Quantumâ„¢ LX what Analog board the
device is connected to. A drop-down menu is
provided to select between:
ï‚· None
ï‚· Analog Board 1
ï‚· Analog Board 2
ï‚· Analog Board 3
Lastly, the I/O channel must be defined. Enter the
value that corresponds to the channel number of the
Analog board that the sensor is connected to.
Once configured, ensure that the value shown in the
Current Value
box of each attached sensor matches
the value as shown on the ammonia detector.
Setpoints - Ammonia Safeties
After calibrating all ammonia sensors, the alarm
thresholds (safeties) need to be set. Access the
following screen from the Main Menu. Select
Setpoints
>
Ammonia Safeties:
The purpose of this screen is to allow the user to
assign safety ranges for up to three different
ammonia sensors. If any of these sensors should
exceed the values set for it, an appropriate message
will be shown on the Status screen for the unit
(Condenser or Vessel) selected, and an associated
output can be energized in the event that a shutdown
occurs. This output can be used to control external
functions, such as controlling an exhaust fan, signal
an alarm, or provide a signal to a compressor or PLC
for additional control.
These warnings and shutdowns do not affect the
operation of a Condenser or Vessel, it simply provides
for a warning or shutdown message to be displayed,
and provide a method for handling a shutdown
situation through external means.
A drop-down selection box appears that allows the
user to set the Ammonia unit configuration. The
selection made here determines on which
Status
Screen
a warning or shutdown will be displayed. The
choices are:
ï‚· Condenser
ï‚· Vessel 1
ï‚· Vessel 2
ï‚· Vessel 3
ï‚· Disabled
The following setpoint boxes appear on this screen:
 Name – A user specified custom name may
be entered here.
 Warning – If the Ammonia sensor input
value exceeds this setpoint for the Delay
period of time, an Ammonia Warning will
message will be displayed on the Status
screen for the unit that is selected on the
Ammonia Safety Configuration
drop-down
box.
ï‚· Delay - The amount of time after the
ammonia sensor input value exceeds
the Ammonia Warning setpoint before a
warning will be displayed.
 Shutdown – If the Ammonia sensor input
value exceeds this setpoint for the Delay
period of time, an Ammonia Shutdown event
will occur. This event does not actually
shutdown a unit, but issues a shutdown
message to the selected
Status Screen
, as
well as energizing the selected
Ammonia
Output (1, 2 or 3)
.
ï‚· Delay - The amount of time after the
ammonia sensor input value exceeds
the Ammonia Shutdown setpoint before
a Shutdown event will occur.
A drop-down selection box appears that allows the
user to associate an Ammonia Output channel to each
shutdown. NOTE: The selected output will not be
energized by a warning, only a shutdown. The choices
are:
ï‚· Ammonia Output 1
ï‚· Ammonia Output 2
ï‚· Ammonia Output 3
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84

Frick Quantum LX Condenser/Vessel Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI