CP-AG30/31/32/35&AG33 Amplier Kits, P/N268300, Page 2
www.ReznorHVAC.com; (800) 695-1901
©2014 Reznor LLC, All rights reserved.
Trademark Notes: Reznor
®
is registered in at least the United States.
All other trademarks are the property of their respective owners.
04/14 (Serial No. Date Code BNE) Form CP-AG30/31/32/35&AG33 Amplier Kits (Ver A)
DIAGRAM 2 - applies to
replacement amplier in
electronic modulation
Option AG33
43
42
TEMP SELECTOR
BL
8 4
BK
5 1 32
T244
Y
BR
M/R VALVE
R
6
R
7 9
1
W
32
O
R
A1044U AMPLIFIER
TS144E TEMP. SENSOR
(SET JUMPER
J5
@ 20 SEC)
2
REPLACEMENT
Amplifier,
Model A1044U,
P/N 268274
43
42
TEMP SELECTOR
BL
8 4
BK
5 1 32
T244
Y
BR
M/R VALVE
R
6
R
7 9
1
W
32
O
R
A1044CL AMPLIFIER (USED ON ADFH ONLY) or A1044EL AMPLIFIER
TS144C TEMP. SENSOR - USED ON ADFH ONLY
TS144E TEMP. SENSOR
2
A1044EL or A1044CL Amplifier
17
BL
18
BK
MR VALVE
R R
R
R
T
H
H
T
H
L
1
A
L
R
M
1
M
V
FP
V S
APS
IGNITION SYSTEM
GND
IGN
FLAME
SENSOR
HOT SURFACE
IGNITOR
W
W
7
BRBR
7
BR
7
SELECTRASTAT
TS144E TEMP SENSOR (PN 119617)
2
1
4
1
W
5 1 3
Y
3
AMPLIFIER A1044E (PN 119616) or A1044 (P/N 86989)
2
O
2 6 7 98
MV2
BK
BK
A1044 or A1044E Amplifier
“J5”
Instructions - Step 3 (cont’d)
4. When installation is complete, close the cabinet. Turn on the electric; turn on the
gas; and check for proper operation.
5. Keep this form for future reference.
adaptable to work with sensor
Models TS144, TS144C, and
TS144E. Check the model number
displayed on the sensor and follow
the instructions that apply.
Sensor TS144 - No change
required.
Sensor TS144C - Change the “Min”
label to 20° - 60°.
Sensor TS144E - Change the “Min”
label to 20° - 60° and the “Max”
label to 60° - 120°.
Find the labels included with the
amplier and select the one or two
that will be needed. Do not remove
the existing dial label but be sure
that it is clean and dry. Remove
the adhesive backing and carefully
slide the replacement label under
the temperature pointer. Line up
with the center leg and adhere the
label.
Temperature Dials on Model
A1044U Amplier
b) Position the mounting rail for
the new amplier over the same
area where the old amplier was
mounted. Mark the two mounting
holes. Drill 7/64” pilot holes. Attach
the rail using the screws provided.
Carefully attach the amplier to the
mounting rail.
c) Locate all of the disconnected
amplier wires (Step 2) and cut
off their terminals. Replace with
the insulated terminals in the kit.
Refer to replacement amplier in
DIAGRAM 2 and connect the wires.
d) In the center on the lower
portion of the amplier, locate
“J5”. Move the jumper to the 20
second position as shown on the
replacement amplier in
DIAGRAM 2.
Set the dials to the temperature
settings of the removed amplier.
Install the amplier cover.
Section applies only to Kit P/N 268302 (cont’d)
Steps 4 & 5 apply to
ALL Replacements
- both Kit P/N 268301
and Kit P/N 268302