Schneider Electric 4000 User manual

Type
User manual

This manual is also suitable for

Instruction Bulletin
63230-300-212
April 2001
POWERLOGIC
®
Circuit Monitor
Series 4000
Reference Manual
Retain for future use
© 2000 Schneider Electric All Rights Reserved
Read these instructions carefully and look at the equipment to become
familiar with the device before trying to install, operate, service, or maintain
it. The following special messages may appear throughout this bulletin or on
the equipment to warn of potential hazards or to call attention to information
that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label
indicates that an electrical hazard exists which will result in personal injury if
the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal
injury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.
NOTE: Provides additional information to clarify or simplify a procedure.
Electrical equipment should be installed, operated, serviced, and maintained
only by qualified personnel. This document is not intended as an instruction
manual for untrained persons. No responsibility is assumed by Square D for
any consequences arising out of the use of this manual.
This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to part 15 of the FCC Rules. These limits are
designated to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
NOTICE
DANGER
DANGER indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not
avoided, can result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not
avoided, can result in minor or moderate injury.
CAUTION
CAUTION, used without the safety alert symbol, indicates a potentially
hazardous situation which, if not avoided, can result in property damage.
PLEASE NOTE
Class A FCC Statement
63230-300-212 POWERLOGIC® Circuit Monitor Series 4000 Reference Manual
April 2001 Contents
i
© 2001 Schneider Electric All Rights Reserved
CONTENTS
CONTENTS ................................................ I
LISTOFFIGURES ..........................................VII
LISTOFTABLES ........................................... IX
CHAPTER 1—INTRODUCTION ................................1
CHAPTERCONTENTS .......................................1
WHATISTHECIRCUITMONITOR? .............................2
AccessoriesandOptionsfortheCircuitMonitor .................3
Features................................................4
TOPICSNOTCOVEREDINTHISBULLETIN ......................4
FIRMWARE ................................................5
CHAPTER 2—SAFETY PRECAUTIONS ..........................7
CHAPTER 3—OPERATION ....................................9
CHAPTERCONTENTS .......................................9
OPERATINGTHEDISPLAY ..................................10
HowtheButtonsWork ....................................10
DisplayMenuConventions ................................11
SelectingaMenuOption ..............................11
Changing a Value ....................................11
MAINMENUOVERVIEW .....................................12
CONFIGURING THE CIRCUIT MONITOR USING THE
SETUPMENU .............................................13
SettingUptheDisplay ....................................13
SettingUptheCommunications ............................14
SettingtheDeviceAddress ............................14
RS-485, RS-232, and Infrared Port Communications Setup . . . 15
EthernetCommunicationsCard(ECC)Setup ..............16
SettingUptheMeteringFunctionsoftheCircuitMonitor .........16
SettingUpAlarms .......................................18
CreatingaNewCustomAlarm ..........................19
SettingUpandEditingAlarms ..........................21
SettingUpI/Os .........................................23
Selecting I/O Modules . ...............................23
ConfiguringI/OModules...............................25
SettingUpPasswords ....................................27
AdvancedSetupFeatures .................................28
CreatingCustomQuantitiestobeDisplayed ...............28
CreatingCustomScreens .............................31
Viewing Custom Screens ..............................34
AdvancedMeterSetup ................................34
RESETTINGMIN/MAX,DEMAND,ANDENERGYVALUES .........37
VIEWINGMETEREDDATA ...................................38
ViewingMeteredDatafromtheMetersMenu ..................38
Viewing Minimum and Maximum Values from the
Min/MaxMenu ..........................................39
POWERLOGIC® Circuit Monitor Series 4000 Reference Manual 63230-300-212
Contents April 2001
ii
© 2001 Schneider Electric All Rights Reserved
VIEWINGALARMS ..........................................41
ViewingActiveAlarms ....................................42
View and Acknowledging High Priority Alarms .................42
VIEWINGI/OSTATUS .......................................43
READINGANDWRITINGREGISTERS ..........................44
PERFORMINGAWIRINGERRORTEST ........................45
Running the Diagnostics Wiring Error Test . . ..................46
CHAPTER 4—METERING CAPABILITIES .......................51
CHAPTERCONTENTS ......................................51
REAL-TIMEREADINGS ......................................52
MIN/MAXVALUESFORREAL-TIMEREADINGS ..................53
PowerFactorMin/MaxConventions .........................54
VARSignConventions ................................55
DEMANDREADINGS........................................56
Demand Power Calculation Methods . ........................57
BlockIntervalDemand ................................57
SynchronizedDemand ................................59
DemandCurrent ........................................59
DemandVoltage ........................................59
ThermalDemand ........................................60
PredictedDemand .......................................60
PeakDemand ..........................................61
GenericDemand ........................................61
InputPulseDemandMetering ..............................62
ENERGYREADINGS ........................................64
POWERANALYSISVALUES..................................66
CHAPTER 5—INPUT/OUTPUT CAPABILITIES . ..................69
CHAPTERCONTENTS ......................................69
I/OOPTIONS ..............................................70
DIGITALINPUTS ...........................................71
DEMANDSYNCHPULSEINPUT ..............................72
ANALOGINPUTS ...........................................73
AnalogInputExample ....................................74
RELAYOUTPUTOPERATINGMODES .........................75
MECHANICALRELAYOUTPUTS ..............................77
Setpoint-controlledRelayFunctions .........................78
SOLID-STATEKYZPULSEOUTPUT ...........................78
2-WirePulseInitiator .....................................79
3-WirePulseInitiator .....................................79
CALCULATINGTHEKILOWATTHOUR-PER-PULSEVALUE.........80
ANALOGOUTPUTS .........................................81
AnalogOutputExample ...................................82
63230-300-212 POWERLOGIC® Circuit Monitor Series 4000 Reference Manual
April 2001 Contents
iii
© 2001 Schneider Electric All Rights Reserved
CHAPTER 6—ALARMS . . ....................................83
CHAPTERCONTENTS ......................................83
ABOUTALARMS ...........................................84
AlarmsGroups ..........................................84
Setpoint-DrivenAlarms ...................................85
Priorities ...............................................87
AlarmLevels ...........................................87
CUSTOMALARMS..........................................88
SETPOINT-CONTROLLEDRELAYFUNCTIONS ..................88
TypesofSetpoint-ControlledRelayFunctions .................89
SCALEFACTORS ..........................................91
SCALINGALARMSETPOINTS ................................92
ALARMCONDITIONSANDALARMNUMBERS ...................93
CHAPTER 7—LOGGING . ....................................99
CHAPTERCONTENTS ......................................99
ALARMLOG ..............................................100
AlarmLogStorage......................................100
DATALOGS ..............................................100
Alarm-DrivenDataLogEntries ............................101
OrganizingDataLogFiles ................................101
DataLogStorage.......................................101
MIN/MAXLOGS ...........................................102
Min/MaxLog ..........................................102
IntervalMin/Max/AverageLog .............................102
IntervalMin/Max/AverageLogStorage ..................103
MAINTENANCELOG .......................................103
MEMORYALLOCATION ....................................104
CHAPTER 8—WAVEFORM AND EVENT CAPTURE .............107
CHAPTERCONTENTS .....................................107
TYPES OF WAVEFORM CAPTURES . . ........................108
Steady-stateWaveformCapture ...........................108
InitiatingaSteady-stateWaveform......................108
DisturbanceWaveformCapture ...........................108
Adaptive Waveform Capture ..............................109
100ms rms Event Recording ..............................110
SETTING UP THE CIRCUIT MONITOR FOR AUTOMATIC EVENT
CAPTURE................................................111
Setting Up Alarm-Triggered Event Capture . ..................111
SettingUpInput-TriggeredEventCapture ...................111
WAVEFORM STORAGE . ...................................111
HOW THE CIRCUIT MONITOR CAPTURES AN EVENT ...........112
POWERLOGIC® Circuit Monitor Series 4000 Reference Manual 63230-300-212
Contents April 2001
iv
© 2001 Schneider Electric All Rights Reserved
CHAPTER 9—DISTURBANCE MONITORING . . .................113
CHAPTERCONTENTS .....................................113
ABOUTDISTURBANCEMONITORING.........................114
CAPABILITIES OF THE CIRCUIT MONITOR DURING AN EVENT . . .117
USING THE CIRCUIT MONITOR WITH SMS TO PERFORM
DISTURBANCEMONITORING ...............................118
UNDERSTANDING THE ALARM LOG . . . .......................119
CHAPTER 10—MAINTENANCE AND TROUBLESHOOTING . ......121
CHAPTERCONTENTS .....................................121
CIRCUIT MONITOR MEMORY . . .............................123
UpgradingMemoryintheCircuitMonitor ....................123
IDENTIFYINGTHEFIRMWAREVERSION ......................124
VIEWINGTHEDISPLAYINDIFFERENTLANGUAGES ............124
CALIBRATION OF THE CURRENT/VOLTAGE MODULE (CVM) . . . . 124
GETTING TECHNICAL SUPPORT ............................124
TROUBLESHOOTING ......................................125
APPENDIX A—ABBREVIATED REGISTER LISTING . ............127
CONTENTS ..............................................127
ABOUTREGISTERS .......................................127
HOWPOWERFACTORISSTOREDINTHEREGISTER...........128
HOWDATEANDTIMEARESTOREDINTHEREGISTER .........129
REGISTERLISTING ........................................130
APPENDIXBUSINGTHECOMMANDINTERFACE .............181
CONTENTS ..............................................181
OVERVIEWOFTHECOMMANDINTERFACE ...................182
IssuingCommands .....................................183
I/OPOINTNUMBERS ......................................186
OPERATINGOUTPUTSFROMTHECOMMANDINTERFACE ......187
USING THE COMMAND INTERFACE TO CHANGE CONFIGURATION
REGISTERS ..............................................187
CONDITIONALENERGY ....................................188
CommandInterfaceControl ...............................188
Digital Input Control . . . ..................................188
INCREMENTAL ENERGY . ..................................189
UsingIncrementalEnergy ................................189
SETTINGUPINDIVIDUALHARMONICCALCULATIONS ..........190
CHANGINGSCALEFACTORS ...............................191
63230-300-212 POWERLOGIC® Circuit Monitor Series 4000 Reference Manual
April 2001 Contents
v
© 2001 Schneider Electric All Rights Reserved
GLOSSARY ..............................................193
INDEX...................................................197
POWERLOGIC® Circuit Monitor Series 4000 Reference Manual 63230-300-212
Contents April 2001
vi
© 2001 Schneider Electric All Rights Reserved
63230-300-212 List of Figures
April 2001
vii
© 2001 Schneider Electric All Rights Reserved
Figure 31: Arrowonthedisplayscreen........................ 10
Figure 32: Displaybuttons.................................. 10
Figure 33: Partsofamenu ................................. 11
Figure 34: MenuoptionsontheMainMenu .................... 12
Figure 35: Menusthatcanbepasswordprotected............... 27
Figure 36: PerformingresetsfromtheResetmenu .............. 37
Figure 37: Viewing metered data on the Meters and Min/Max
menus......................................... 38
Figure 38: ViewAlarmsmenu............................... 41
Figure 39: DiagnosticsMenuaccessedfromtheMainMenu....... 44
Figure 310: Wiring Error Test option on the Diagnostics menu. ...... 45
Figure 41: Powerfactormin/maxexample ..................... 54
Figure 42: Reactive PowerVARsignconvention............... 55
Figure 43: BlockIntervalDemandExamples ................... 58
Figure 44: ThermalDemandExample......................... 60
Figure 45: PredictedDemandExample........................ 60
Figure 46: Channel pulse metering example. . .................. 63
Figure 47: Reactiveenergyaccumulatesinfourquadrants ........ 65
Figure 51: Demandsynchpulsetiming........................ 72
Figure 52: Analoginputexample............................. 74
Figure 53: Two-wirepulsetrain.............................. 79
Figure 54: Three-wirepulsetrain............................. 79
Figure 55: Analogoutputexample............................ 82
Figure 61: Samplealarmlogentry ........................... 86
Figure 62: How the circuit monitor handles setpoint-driven alarms. . . 86
Figure 63: Two alarms set up for the same quantity with different
pickup and dropout set points 87
Figure 71: Memoryallocationexample....................... 104
Figure 72: MemoryallocationinSMS........................ 105
Figure 81: Event capture initiated from a high-speed input . . ...... 112
Figure 91: A fault can cause voltage sag on the whole system. . . . . 115
Figure 92: Waveform showing voltage sag, which was caused by a
remote fault and lasted five cycles. 115
Figure 93: OnboardFilestab............................... 118
Figure 94: OnboardAlarms/Eventstab....................... 118
Figure 95: Eventlogentriesexample ........................ 119
Figure 96: Samplealarmlogentry .......................... 119
Figure 101:Memorychiplocationinthecircuitmonitor ........... 123
Figure A1: Bitsinaregister................................ 128
Figure A2: Powerfactorregisterformat....................... 128
Figure B1: CommandInterfacePointerRegisters............... 182
Figure B2: Identifying I/Os for the command interface............ 186
Figure B3: IncrementEnergyExample ....................... 189
LIST OF FIGURES
List of Figures 63230-300-212
April 2001
© 2001 Schneider Electric All Rights Reserved
viii
63230-300-212 List of Tables
April 2001
ix
© 2001 Schneider Electric All Rights Reserved
Table 11: SummaryofCircuitMonitorInstrumentation ............ 2
Table 12: Circuit Monitor Parts, Accessories, and Custom Cables . . . 3
Table 31: FactoryDefaultsfortheDisplaySettings.............. 14
Table 32: OptionsforCommunicationsSetup.................. 15
Table 33: OptionsforMeterSetup........................... 17
Table 34: OptionsforCreatinganAlarm...................... 20
Table 35: OptionsforEditinganAlarm ....................... 22
Table 36: I/ODescriptions................................. 24
Table 37: OptionsforPasswordSetup........................ 27
Table 38: OptionsforCustomQuantities...................... 30
Table 39: Available Default Quantities ........................ 33
Table 310: OptionsforAdvancedMeterSetup .................. 36
Table 311: Read/WriteRegisterOptions....................... 44
Table 312: Wiring Error Messages............................ 48
Table 41: One-Second, Real-Time Readings Samples ........... 52
Table 42: 100msReal-TimeReadings....................... 53
Table 43: DemandReadings............................... 56
Table 44: EnergyReadings ................................ 64
Table 45: PowerAnalysisValues............................ 68
Table 51: I/O Extender Options ............................. 70
Table 52: Sample register readings for analog inputs ............ 74
Table 53: Sample register readings for analog output ............ 82
Table 61: Scale Groups ................................... 91
Table 62: ScaleGroupRegisterNumbers..................... 92
Table 63: ListofDefaultAlarmsbyAlarmNumber .............. 94
Table 64: AlarmTypes.................................... 96
Table 71: Values Stored in Maintenance Log ................. 103
Table 81: Available Resolutions for Disturbance Waveform
Captures...................................... 108
Table 82: Available Resolutions for Adaptive Waveform
Captures...................................... 109
Table 83: 100ms rms Quantities ........................... 110
Table 91: Capability of the circuit monitor to measure electromagnetic
phenomena . .................................. 117
Table 101: Troubleshooting . . . ............................. 125
Table A1: DateandTimeFormat........................... 129
Table A2: DateandTimeByteExample...................... 129
Table A3: AbbreviatedRegisterList......................... 130
Table A4: AbbreviatedRegisterListforI/OStatus.............. 166
Table A5: Registers for Alarm Position Counters . . . ............ 173
Table A6: Spectral Components............................ 178
Table B 1: Locationofthecommandinterface ................. 182
Table B 2: CommandCodes............................... 183
Table B 3: RegistersforHarmonicCalculations ................ 190
LIST OF TABLES
List of Tables 63230-300-212
April 2001
© 2001 Schneider Electric All Rights Reserved
x
63230-300-212 Chapter 1—Introduction
April 2001 Chapter Contents
1
© 2001 Schneider Electric All Rights Reserved
This chapter offers a general description of the Series 4000 Circuit Monitor,
tells how to best use this bulletin, and lists related documents.
CHAPTERCONTENTS .......................................1
WHATISTHECIRCUITMONITOR? .............................2
AccessoriesandOptionsfortheCircuitMonitor .................3
Features................................................4
TOPICSNOTCOVEREDINTHISBULLETIN ......................4
FIRMWARE ................................................5
CHAPTER 1—INTRODUCTION
C
HAPTER CONTENTS
Chapter 1—Introduction 63230-300-212
What is the Circuit Monitor? April 2001
© 2001 Schneider Electric All Rights Reserved
2
The circuit monitor is a multifunction, digital instrumentation, data acquisition
and control device. It can replace a variety of meters, relays, transducers and
other components. The circuit monitor can be located at the service entrance
to monitor the cost and quality of power, and can be used to evaluate the
utility service. When located at equipment mains, the circuit monitor can
detect voltage-based disturbances that cause costly equipment downtime.
The circuit monitor is equipped with
RS-485 and RS-232 communications for
integration into any power monitoring and control system. However, System
Manager software (
SMS)fromPOWERLOGIC, which is written specifically
for power monitoring and control, best supports the circuit monitors
advanced features.
The circuit monitor is a true rms meter capable of exceptionally accurate
measurement of highly nonlinear loads. A sophisticated sampling technique
enables accurate, true rms measurement through the 255th harmonic. You
can view over 50 metered values plus extensive minimum and maximum data
from the display or remotely using software. Table 11 summarizes the
readings available from the circuit monitor.
W
HAT IS THE CIRCUIT MONITOR?
Table 1–1: Summary of Circuit Monitor Instrumentation
Real-Time Readings Energy Readings
Current (per phase, N, G, 3-Phase)
Voltage (LL, LN, NG, 3-Phase)
Real Power (per phase, 3-Phase
)
Reactive Power (per phase, 3-Phase)
Apparent Power (per phase, 3-Phase)
Power Factor (per phase, 3-Phase)
Frequency
Temperature (internal ambient)
THD (current and voltage)
K-Factor (per phase)
Accumulated Energy, Real
Accumulated Energy, Reactive
Accumulated Energy, Apparent
Bidirectional Readings
Reactive Energy by Quadrant
Incremental Energy
Conditional Energy
Demand Readings Power Analysis Values
Demand Current (per phase present, 3-Phase avg.)
Demand Voltage (per phase present, 3-Phase avg.)
Average Power Factor (3-Phase total)
Demand Real Power (per phase present, peak)
Demand Reactive Power (per phase present, peak)
Demand Apparent Power (per phase present, peak)
Coincident Readings
Predicted Power Demands
Crest Factor (per phase)
Displacement Power Factor (per phase, 3-Phase
)
Fundamental Voltages (per phase)
Fundamental Currents (per phase)
Fundamental Real Power (per phase)
Fundamental Reactive Power (per phase)
Harmonic Power
Unbalance (current and voltage)
Phase Rotation
Harmonic Magnitudes & Angles (per phase)
Sequence Components
63230-300-212 Chapter 1—Introduction
April 2001 What is the Circuit Monitor?
3
© 2001 Schneider Electric All Rights Reserved
The circuit monitor has a modular design to maximize its usability. In addition
to the main meter, the circuit monitor has plug-on modules and accessories,
including:
Current/voltage module (CVM). A standard part of the circuit monitor is
the current/voltage module where all metering data acquisition occurs.
Remote display. The optional remote 4-line display is available with a
back-lit liquid crystal display (LCD) or a vacuum fluorescent display (VFD).
The VFD model includes an infrared port that can be used to
communicate directly with the circuit monitor from a laptop and can be
used to download firmware, which keeps the circuit monitor up to date with
the latest system enhancements.
I/OExtender. The I/O extender, located on the side of the circuit monitor,
enables you to plug inup to 8 industry-standard inputs and outputs.
Several preconfigured combinations are available, or you can create a
custom configuration.
Digital I/O Card. You can further expand the I/O capabilities of the circuit
monitor by adding a digital I/O card (4 inputs and 4 outputs). This card fits
into one of the option slots on the top of the circuit monitor.
Ethernet Communications Card. The Ethernet communications card
provides an Ethernet port that accepts a 100 Mbps fiber optic cable or a
10/100 Mbps UTP and provides an RS-485 master port to extend the
circuit monitor communications options. This card is easily installed into
option slot A on the top of the circuit monitor.
Table 12 lists the circuit monitor parts and accessories and their associated
instruction bulletins.
Table 1–2: Circuit Monitor Parts, Accessories, and Custom Cables
Description Part Number Document Number
Circuit Monitor CM4000 63230-300-200
Current/ Voltage Module CVM 63230-301-200
VFD Display with infrared (IR) port and proximity sensor CMDVF
63230-305-200
LCD Display CMDLC
Optical Communications Interface (for use with the VFD display only) OCIVF 63230-306-200
I/O Extender Module
63230-302-200
with no preinstalled I/ Os, accepts up to 8 individual I/O modules with a
maximum of 4 analog I/Os
IOX
with 4 digital inputs (32 Vdc), 2 digital outputs (60 Vdc),
1 analog output (420 mA), and 1 analog input (05Vdc)
IOX2411
with 4 analog inputs (420 mA) and 4 digital inputs (120 Vac) IOX0404
with 8 digital inputs (120 Vac) IOX08
Digital I/O Card
Field installable with 4 digital inputs (120 Vac), 3 (10 A) relay outputs (120Vac),
1 pulse output (KYZ)
IOC44 63230-303-200
Ethernet Communications Card with
100 Mbps fiber or 10/100 Mbps UTP Ethernet port and 1 RS-485 master port
ECC21 63230-304-200
Optical Communications Interface OCIVG 63230-306-200
Memory Expansion Kit (16 MB and 32 MB kits)
CM4MEM16M
CM4MEM32M
63230-300-205
For parts list of individual inputs and outputs, see Table 51onpage70.
Accessories and Options for the
Circuit Monitor
Chapter 1—Introduction 63230-300-212
Topics Not Covered in This Bulletin April 2001
© 2001 Schneider Electric All Rights Reserved
4
Some of the circuit monitors many features include:
True rms metering to the 255th harmonic
Accepts standard CT and PT inputs
600 volt direct connection on metering inputs
Certified ANSI C12.20 revenue accuracy and IEC 687.2 class revenue
accuracy
High accuracy0.04% current and voltage
Min/max readings of metered data
Power quality readingsTHD, K-factor, crest factor
Real-time harmonic magnitudes and angles to the 63rd harmonic
Current and voltage sag/swell detection and recording
Downloadable firmware
Easy setup through the optional remote display (password protected)
where you can view metered values
Setpoint-controlled alarm and relay functions
Onboard alarm and data logging
Wide operating temperature range 25° to 70°C
Modular, field-installable digital and analog I/O modules
Flexible communicationsRS-485 and RS-232 communications are
standard, optional Ethernet communications card available with fiber optic
connection
Two option card slots for field-installable I/O and Ethernet capabilities
Standard 8MB onboard logging memory (field upgradable to 16 MB, 32
MB, and higher
CT and PT wiring diagnostics
Revenue security with utility sealing capability
Some of the circuit monitors advanced features, such as onboard data logs
and alarm log files, can only be set up over the communications link using
SMS. SMS versions 3.12 and higher support the CM4000 device type.This
circuit monitor instruction bulletin describes these advanced features, but
does not tell how to set them up. For instructions on using
SMS,refertothe
SMS online help and the
SMS-3000 Setup Guide,
which is available in
English (63220-060-200), French (63220-060-201), and Spanish (63220-
060-202). For information about related instruction bulletins, see Table 12
on page 3.
CM4 Mounting Adapters CM4MA
63230-204-316
63230-300-206
63230-305-201
4-ft display cable (1.2 m) CAB-4
N/A
12-ft display cable (3.6 m) CAB-12
30-ft display cable (9.1 m) CAB-30
10-ftRS-232cable(3m) CAB-106
Table 1–2: Circuit Monitor Parts, Accessories, and Custom Cables
For parts list of individual inputs and outputs, see Table 51onpage70.
Features
TOPICS NOT COVERED IN
THIS BULLETIN
63230-300-212 Chapter 1—Introduction
April 2001 FirmwAre
5
© 2001 Schneider Electric All Rights Reserved
This instruction bulletin is written to be used with firmware version 11.000 or
higher. See Identifying the Firmware Versionon page 124 for instructions
on how to determine the firmware version.
FIRMWARE
Chapter 1—Introduction 63230-300-212
FirmwAre April 2001
© 2001 Schneider Electric All Rights Reserved
6
63230-300-212 Chapter 2—Safety Precautions
April 2001
7
© 2001 Schneider Electric All Rights Reserved
This chapter contains important safety precautions that must be followed
before attempting to install, service, or maintain electrical equipment.
Carefully read and follow the safety precautions outlined below.
CHAPTER 2—SAFETY PRECAUTIONS
HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION
Only qualified workers should install this equipment. Such work
should be performed only after reading this entire set of instructions.
NEVER work alone.
Before performing visual inspections, tests, or maintenance on this
equipment, disconnect all sources of electric power. Assume that all
circuits are live until they have been completely de-energized, tested,
and tagged. Pay particular attention to the design of the power
system. Consider all sources of power, including the possibility of
backfeeding.
Turn off all power supplying this equipment before working on or
inside.
Always use a properly rated voltage sensing device to confirm that all
power is off.
Beware of potential hazards, wear personal protective equipment,
carefully inspect the work area for tools and objects that may have
been left inside the equipment.
Use caution while removing or installing panels so that they do not
extend into the energized bus; avoid handling the panels, which could
cause personal injury.
The successful operation of this equipment depends upon proper
handling, installation, and operation. Neglecting fundamental
installation requirements may lead to personal injury as well as
damage to electrical equipment or other property.
Before performing Dielectric (Hi-Pot) or Megger testing on any
equipment in which the circuit monitor is installed, disconnect all input
and output wires to the circuit monitor. High voltage testing may
damage electronic components contained in the circuit monitor.
Failure to follow these instructions will result in death or
serious injury.
DANGER
Chapter 2—Safety Precautions 63230-300-212
April 2001
© 2001 Schneider Electric All Rights Reserved
8
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216

Schneider Electric 4000 User manual

Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI