Satec PM295 Operating instructions

Type
Operating instructions
System 295
Powermeter &
Harmonic Analyzer
Installation and
Operation Manual
BG0130 Rev. A2
SYSTEM 295 POWERMETER
& HARMONIC ANALYZER
Installation & Operation Manual
2
Introduction
LIMITED WARRANTY
The manufacturer offers the customer an 24-month functional warranty on the instrument
for faulty workmanship or parts from date of dispatch from the distributor. In all cases,
this warranty is valid for 36 months from the date of production. This warranty is on a
return to factory basis.
The manufacturer does not accept liability for any damage caused by instrument
malfunction. The manufacturer accepts no responsibility for the suitability of the
instrument to the application for which it was purchased.
Failure to install, setup or operate the instrument according to the instructions herein will
void the warranty.
Your instrument may be opened only by a duly authorized representative of the
manufacturer. The unit should only be opened in a fully anti-static environment. Failure to
do so may damage the electronic components and will void the warranty.
NOTE
The greatest care has been taken to manufacture and calibrate your instrument. However,
these instructions do not cover all possible contingencies that may arise during
installation, operation or maintenance, and all details and variations of this equipment are
not covered by these instructions.
For additional information regarding installation, operation or maintenance of this
instrument, contact the manufacturer or your local representative or distributor.
IMPORTANT
Please read instructions contained in this manual before performing
installation, and take note of the following precautions:
1. Ensure that all incoming AC power and other power sources are turned OFF
before performing any work on the instrument. Failure to do so may result in serious
or even fatal injury and/or equipment damage.
2. Before connecting the instrument to the power source, check the labels on the
side of the instrument to ensure that your instrument is equipped with the appropriate
power supply voltage, input voltages, currents, analog output and communication
protocol for your application.
3. Under no circumstances should the instrument be connected to a power
source if it is damaged.
4. To prevent potential fire or shock hazard, do not expose the instrument to
rain or moisture.
Introduction 3
5. The secondary of an external current transformer must never be allowed to be
open circuit when the primary is energized. An open circuit can cause high voltages,
possibly resulting in equipment damage, fire and even serious or fatal injury. Ensure
that the current transformer wiring is made through shorting switches and is secured
using an external strain relief to reduce mechanical strain on the screw terminals, if
necessary.
6. Setup procedures must be performed only by qualified personnel familiar
with the instrument and its associated electrical equipment.
7. DO NOT attempt to open the instrument under any circumstances.
Modbus is a trademark of Modicon, Inc.
FRead through this manual thoroughly before connecting the meter to
the current carrying circuits. During operation of the meter, hazardous
voltages are present on input terminals. Failure to observe
precautions can result in serious or even fatal injury or damage to
equipment.
BG0130 Rev. A2
4
Introduction
About This Manual
Chapter 1, Introduction, includes a description of the PM295 basic features.
Chapter 2, Installation, provides instructions for mounting, installing and
interfacing the PM295.
Chapter 3, Operating the PM295, contains an overview of the PM295 measurement
and operation techniques.
Chapter 4, Operation Techniques, provides instructions on the manual operation of
the PM295.
Chapter 5 describes Communications Operation.
Chapter 6 provides Technical Specifications of the PM295.
Appendices
Appendix A specifies all of the display formats available for operational mode and
shows the corresponding front panel displays.
Appendix B lists the instrument programmable parameters that can be accessed
either through the front panel or communications.
Appendix C provides a sample of setpoint programming form.
Appendices D, E and F contain cable drawings for computer, printer and modem
communications connections.
Related Manuals
This operating manual contains information required for installation and operation
of the PM295. Information concerning the serial communications protocols is found
in the documents: "System 295 Powermeter and Harmonic Analyzer - ASCII
Communications Protocol - User's Guide" and "System 295 Powermeter and
Harmonic Analyzer - Modbus Communications Protocol - User's Guide" shipped
with your PM295 on diskette in Microsoft Word document format.
Introduction 1
Table of Contents
1. Introduction...............................................................................................1
1.1 About The PM295..................................................................................1
1.2 Instrument Features Summary...............................................................1
1.3 Measurement Capabilities......................................................................5
2. Installation...............................................................................................11
2.1 Initial Inspection...................................................................................11
2.2 Mechanical Installation.........................................................................11
2.3 Input/Output Terminals.........................................................................14
2.4 Power Source Connection....................................................................15
2.5 Voltage Input Connections ...................................................................15
2.5.1 660V Input..............................................................................................15
2.5.2 120V Input..............................................................................................16
2.6 Current Input Connections....................................................................16
2.7 Harmonic Measurement Connections...................................................17
2.8 Wiring Configurations...........................................................................18
2.9 Auxiliary Current Input Connections .....................................................25
2.10 Analog Output Connections..................................................................26
2.11 Relay Output Connections....................................................................27
2.12 Discrete Input Connections...................................................................28
2.13 Communications..................................................................................28
3. Operating The PM295.............................................................................30
3.1 Instrument Turn On..............................................................................30
3.2 Operational Mode.................................................................................30
3.2.1 Front Panel Operation.............................................................................30
3.2.2 Selecting a Display Page.........................................................................31
3.2.3 Display Formats......................................................................................31
3.3 Programming Mode..............................................................................32
3.3.1 Front Panel Operation.............................................................................32
3.3.2 General Operations.................................................................................34
3.3.3 Menu Map..............................................................................................35
3.3.4 Entering/Quitting Programming Mode......................................................35
3.3.5 Entering the Password............................................................................37
3.3.6 Selecting the Setup Group......................................................................37
3.3.7 Basic Setup ............................................................................................38
3.3.8 Serial Port Setup.....................................................................................39
3.3.9 Discrete Input Setup ...............................................................................39
3.3.10 Counter Setup ........................................................................................41
3.3.11 Analog Output Setup...............................................................................41
3.3.12 Analog Expander Setup ..........................................................................43
3.3.13 Pulsing Relay Setup................................................................................44
3.3.14 Event/Alarm Setpoints.............................................................................45
3.3.15 Timer Setup............................................................................................51
2
Introduction
3.3.16 Real Time Clock Setup............................................................................51
3.3.17 Date Format Setup .................................................................................53
3.3.18 Reset Functions......................................................................................53
3.3.19 Password Protection Control...................................................................54
3.4 Self-Test Diagnostics ...........................................................................55
4. Operation Techniques............................................................................56
4.1 Sampling Technique ............................................................................56
4.2 Measurement Modes............................................................................56
4.2.1 Real-time RMS Measurements................................................................56
4.2.2 Averaging...............................................................................................57
4.2.3 Minimum/Maximum Logging....................................................................57
4.3 Demand Measurements.......................................................................58
4.3.1 Demand Readings ..................................................................................58
4.3.2 Block Interval Demand............................................................................58
4.3.3 Sliding Window Demand..........................................................................59
4.3.4 Thermal Demand....................................................................................59
4.3.5 Accumulated and Predicted Demands.....................................................60
4.3.6 Demand Interval Measurement ...............................................................61
4.3.7 Resetting the Demands...........................................................................62
4.3.8 Demand Interval Pulse............................................................................63
4.4 Energy Measurements .........................................................................63
4.4.1 Measurement Modes..............................................................................63
4.4.2 Resetting the Energies............................................................................64
4.4.3 Energy Pulsing........................................................................................64
4.5 Harmonic Measurements .....................................................................64
4.5.1 Measurement Technique.........................................................................64
4.5.2 Harmonic Parameters.............................................................................65
4.5.3 Real-time Waveform Capture..................................................................66
4.6 Auxiliary Measurements.......................................................................66
4.6.1 Voltage and Current Unbalance...............................................................66
4.6.2 Calculated Neutral Current......................................................................67
4.6.3 Auxiliary Current Input Operation.............................................................67
4.6.4 Frequency Measurements.......................................................................67
4.6.5 Phase Rotation.......................................................................................68
4.6.6 Phase Angles..........................................................................................68
4.7 Time-Of-Use System ...........................................................................68
4.7.1 TOU System Operation...........................................................................68
4.7.2 TOU System Registers ...........................................................................69
4.7.3 TOU Calendars.......................................................................................70
4.7.4 Daily Profiles...........................................................................................70
4.7.5 Connecting with Energy-counting Meters.................................................70
4.7.6 Tariff Interval Pulse.................................................................................70
4.8 Discrete Input Operation ......................................................................70
4.9 Relay Output Operation........................................................................71
4.10 Analog Output Operation......................................................................72
4.11 Analog Expander Operation.................................................................74
4.12 Counter Operation................................................................................75
4.13 Timer Operation...................................................................................75
Introduction 3
4.14 User Programmable Events .................................................................76
4.15 On-Board Data Recording....................................................................77
4.15.1 Event Logging.........................................................................................79
4.15.2 Data Logging..........................................................................................80
4.15.3 High-speed Waveform Logging...............................................................81
4.15.4 High-resolution Waveform Logging..........................................................82
4.16 Monitoring And Recording Disturbances...............................................82
4.16.1 Disturbance Analysis...............................................................................82
4.16.2 Monitoring Disturbances..........................................................................83
4.16.3 Recording Disturbances..........................................................................83
4.17 Setpoint Operation...............................................................................84
4.17.1 General ..................................................................................................84
4.17.2 Setpoint Programming.............................................................................84
4.17.3 Triggering Conditions ..............................................................................85
4.17.4 Delaying Setpoint Operations..................................................................88
4.17.5 Setpoint Actions......................................................................................88
4.17.6 Special Considerations............................................................................90
4.17.7 Setpoint Programming Techniques..........................................................91
4.18 Update Rates And Response Time.......................................................99
5. Communications Operation.................................................................101
5.1 General..............................................................................................101
5.2 Eia Interface Standards......................................................................101
5.2.1 EIA RS-232 Standard............................................................................101
5.2.2 EIA RS-422 and EIA RS-485 Standards................................................102
5.3 Configuring The Communications Port...............................................102
5.3.1 Communications Mode..........................................................................102
5.3.2 Interface...............................................................................................103
5.3.3 Communication Address .......................................................................103
5.3.4 Baud Rate ............................................................................................103
5.3.5 Data Format .........................................................................................104
5.3.6 Handshaking.........................................................................................104
5.3.7 DTR/RTS Control Line ..........................................................................105
5.3.8 Configuring the Printer Parameters........................................................105
5.4 Response Time..................................................................................106
5.5 Print Mode .........................................................................................106
6. Technical Specifications......................................................................108
Appendix A Display Formats.......................................................................113
Appendix B Programmable Parameters......................................................124
Appendix C Setpoint Programming Form......................................................152
Appendix D Cable Drawings - Computer Connection...................................153
Appendix E Cable Drawings - Serial Printer Connection..............................159
Appendix F Cable Drawings - Modem Connection.......................................163
INDEX..........................................................................................................164
Introduction 1
1. Introduction
1.1 About The PM295
The PM295 is an advanced microprocessor-based digital instrument that
incorporates the capabilities of the network analyzer, data recorder and
programmable controller allowing for user network monitoring, analysis and control.
The instrument provides three-phase measurements of electrical quantities in power
distribution systems, monitoring external events, operating external equipment via
relay contacts, fast and long-term on-board recording of measured quantities and
events, harmonic network analysis and disturbance recording.
The PM295 can communicate with PLCs and PC based workstations via serial
communications and directly by transducing analog and discrete signals, serving as
excellent partner in power network management. All measurement functions of the
PM295 are remotely programmable via the communications port.
The accompanying PAS295 software package provides easy remote programming
for the instrument, data acquisition, analysis and on-screen presentation.
1.2 Instrument Features Summary
Processing Block
CPU - microcontroller 80C196KC20 with a 20 MHz oscillator
Extended nonvolatile RAM with battery backup for data recording - 512K byte
module
On-board real-time clock
A I0-bit A/D converter
Power supervisory circuit
External watch-dog
Analog Inputs
3 isolated voltage inputs - 660 VAC/120 VAC options
3 isolated current inputs - 1A or 5A secondary options
1 isolated auxiliary current input for ground leakage/neutral current
measurements - 5 mA/1A/5A secondary options (upon order)
2
Introduction
Discrete Inputs
8 programmable optically isolated digital inputs free programmable for sensing
external contactsstatus and pulses.
Applications:
- monitoring external dry contacts
- sensing an external synchronization pulse for demand interval
measurements
- counting external pulses
- connecting with external energy-counting meters
- triggering setpoints from external alarm/event sources
- selecting output values for internal multiplexed analog output
Analog Outputs
one internal multiplexed scalable free-programmable optically isolated current
output - 0-20/4-20 mA (upon order). Provides time-sharing output for up to 16
analog parameters that can be controlled externally by a combination of binary
signals on the instrument's discrete inputs (from 1 to 4 inputs can be operated)
extension for up to 14 analog outputs is available using external analog
expanders (up to 2 units per instrument)
Discrete Outputs
4 digital free-programmable relay outputs (dry contact)
Applications:
- alarm activations
- load control
- energy pulsing
- time reference pulses for synchronization demand and tariff calculations
Timers
4 programmable a 1 sec resolution timers for repeated setpoint operations and
data recording
Counters
8 programmable large-scale counters with scalable input for counting input
pulses and various internal events
User Programmable Events
8 programmable flags for asserting user-definable events, allowing manual
control and expansion of setpoint operations
Introduction 3
Setpoints
16 programmable setpoints for monitoring various events:
- up to 4 triggering conditions for each setpoint combined by OR/AND
logical operations
- up to 4 actions for each setpoint on setpoint operation
- programmable hysteresis (dead-band) for analog triggers
- programmable delay for setpoint operation/release
each setpoint can be combined with other setpoints if extended number of
conditions or actions needed
any measured or sensed quantity/status/pulse/event can be used as a trigger
condition for setpoint operation
voltage disturbance and phase rotation monitoring are available for triggering
setpoint operations
setpoint actions available:
- operating relay output
- increment/decrement/clear counter
- assert/clear user programmable event
- reset total accumulating energy registers
- reset extreme demand registers
- reset TOU system accumulating energy registers
- reset TOU system demand registers
- clear all counters
- clear Min/Max log registers
- event logging on setpoint operation
- data logging in selected data log partition
- high-speed waveform logging for disturbance analysis
- high-resolution waveform logging for harmonic analysis
each setpoint can be programmed to be operated manually via
communications by overriding present conditions or by gating setpoint
operations in addition to other setpoint conditions (for example when
event/data recording is needed for a user-defined time interval)
each setpoint can be programmed to allow the setpoint operations to be
recorded in the event log on any setpoint transition - operate, release or either
transition
On-board Data Recording
19 free-programmable extended memory partitions for recording events,
measured data, and captured waveforms:
- one event logging partition for recording various events and setpoint
operations, providing storage for up to 36864 events with a 512K
memory module (assuming the entire memory allocated for the
partition)
4
Introduction
- 16 programmable data logging partitions, each for recording from 1 to
16 user programmable parameters per record, providing total storage
for up to 114,688 parameters with a 512K memory module (assuming
the entire memory allocated for data logging)
- one partition for high-speed waveform recording (32 samples x 16
cycles x 6 inputs per record) for disturbance analysis, and one partition
for high-resolution waveform recording (128 samples x 4 cycles x 6
inputs per record) for harmonic analysis, each providing storage for up
to 19, 40, or 82 records with a 512K memory module (assuming the
entire memory allocated for the partition)
each memory partition can be sized to store desired number of records, from
1 record and up to the entire memory size, using an arbitrary combination of
partitions
each memory partition can be programmed to store the oldest records without
overwriting previously recorded data when a partition is filled up, or to wrap
around by writing new records over the oldest records so that stored records
will always contain the most recent data
Time-of-Use System
8 programmable accumulating energy registers for 16 tariffs, each
configurable for counting kWh/kvarh/kVAh or pulses from up to 8 external
energy-counting meters
3 programmable demand registers for 16 tariffs, configurable for recording
extreme (minimum and maximum) demands using varying calculation
techniques: block interval/sliding window/thermal demand
16 daily profiles (types of days) with up to 8 tariff changes per day
2-year calendar
Communications
one programmable optically isolated serial port - RS-232/RS-422/RS-485
embedded options with a user-selectable baud rate of 110 to 38400 BPS
Display
multi-page display composed of 11 windows with high-brightness seven-
segment digital LEDs. A total of 55 display pages are available
Keypad
four membrane long-life push-buttons for page scrolling and programming
Power Supply
90-264 V AC, 10-290 V DC options
Introduction 5
1.3 Measurement Capabilities
Table 1-1 lists quantities and signals measured, calculated and sensed by the PM295. Measurement readings can be
accessed via the front panel and communications. These readings can also be transferred through internal analog and
relay outputs, and used as triggers for alarm/event setpoint operations. Ranges and full scale values for measurement
parameters are summarized in technical specifications (see Chapter 6). Chapter 3 describes measurement functions and
modes of measuring input values.
Table 1-1 Measured Quantities and Sensed Signals
Measurement Mode Usage/output
Parameter Real-
time Sliding
average Demand Min/
Max Display Commu-
nications Analog
output Pulse Data
logging Trigger
setpoint
Per phase Measurements
Voltage (L-N/L-L) À • •
Current • •
kW Á • •
kvar Á • •
kVA Á • •
Power factor (signed) Á • •
Voltage THD Â • •
Current THD • •
K-Factor • •
Three-phase total measurements
Total kW • •
Total kvar • •
Total kVA • •
Total power factor signed • •
Total power factor lag • •
6
Introduction
Table 1-1 Measured Quantities and Sensed Signals
Measurement Mode Usage/output
Parameter Real-
time Sliding
average Demand Min/
Max Display Commu-
nications Analog
output Pulse Data
logging Trigger
setpoint
Total power factor lead • •
Auxiliary measurements
Auxiliary current (ground
leakage/neutral current) • •
Neutral current (calculated) • •
Frequency • •
Voltage unbalance • •
Current unbalance • •
Low values on any phase
Low voltage (L-N/L-L) À• •
Low current • •
Low kW Á• •
Low kvar Á• •
Low kVA Á• •
Low power factor lag Á• •
Low power factor lead Á• •
Low voltage THD • •
Low current THD • •
Low K-Factor • •
High values on any phase
High voltage (L-N/L-L) À• •
High current • •
High kW Á• •
High kvar Á• •
Introduction 7
Table 1-1 Measured Quantities and Sensed Signals
Measurement Mode Usage/output
Parameter Real-
time Sliding
average Demand Min/
Max Display Commu-
nications Analog
output Pulse Data
logging Trigger
setpoint
High kVA Á• •
High power factor lag Á• •
High power factor lead Á• •
High voltage THD • •
High current THD • •
High K-Factor • •
Demands
Volt demand per phase À • • Ã • •
Ampere demand per phase • • Ã • •
Total kW demand (block interval,
sliding window, thermal) • • Ã • •
Total kvar demand (block interval,
sliding window, thermal) • • Ã • •
Total kVA demand (block interval,
sliding window, thermal) • • Ã • •
Predicted demands
Total kW demand (accumulated,
sliding window) • •
Total kvar demand (accumulated,
sliding window) • •
Total kVA demand (accumulated,
sliding window) • •
Total energies
kWh (import, export, net, total) • •
8
Introduction
Table 1-1 Measured Quantities and Sensed Signals
Measurement Mode Usage/output
Parameter Real-
time Sliding
average Demand Min/
Max Display Commu-
nications Analog
output Pulse Data
logging Trigger
setpoint
kvarh (import, export, net, total) • •
kVAh (total) • •
Per phase harmonic measurements
Voltage harmonics (1-40), % • • Ä • •
Current harmonics (1-40), % • • Ä • •
Harmonic voltages (for odd
harmonics 1-39) • • Ä • •
Harmonic currents (for odd
harmonics 1-39) • • Ä • •
Three-phase total harmonic measurements
Harmonic total kW (for odd
harmonics 1-39) • • Ä • •
Harmonic total kvar (for odd
harmonics 1-39) • • Ä • •
Harmonic total power factors (for odd
harmonics 1-39) • • Ä • •
TOU energy registers
8 registers for 16 tariffs, free
programmable for counting
kWh/kvarh/kVAh or pulses from
external energy-counting meters
• •
TOU demand registers
3 registers ( kW/kvar/kVA demands)
for 16 tariffs, free • •
programmable for registration
block interval/sliding window/
thermal Min/Max demands
v
Introduction 9
Table 1-1 Measured Quantities and Sensed Signals
Measurement Mode Usage/output
Parameter Real-
time Sliding
average Demand Min/
Max Display Commu-
nications Analog
output Pulse Data
logging Trigger
setpoint
TOU system parameters
Active tariff • •
Active profile • •
Pulse counters
8 large scale counters for counting
external pulses or internal events • •
Discrete inputs
8 discrete inputs, free configurable for
sensing external contacts or pulses • •
Timers
4 timers with 1 sec resolution
Internal events
kWh pulse (import/export/total) • •
kvarh pulse (import/export/total) • •
kVAh pulse • •
Start demand interval • •
Start tariff interval • •
Time/date parameters
Year, month, day of month, day of
week, hour, minute, second
Special measurements
Voltage disturbance
Phase rotation • •
Phase angles per phase
10
Introduction
NOTES
¬For all applications/outputs, the voltage parameters can represent line-to-neutral or line-to-line voltages depending on the
wiring configuration selected in the Powermeter. (4Ln3/3Ln3 = line-to-neutral voltages; all other configurations = line-to-line
voltages).
-In 3-wire connection schemes, the individual phase values for power factor, active power, apparent power and reactive power
will be zero, because they have no meaning. Only total three-phase power values can be used.
®In all grounded connections using either 4Ln3 or 4LL3 wiring configurations, harmonic voltages will represent line-to-neutral
voltages. In a 3-wire direct connection, harmonic voltages will represent line-to-neutral voltages that arise on the Powermeter's
input transformers. In a 3-wire open delta connection, harmonic voltages will comprise L12 and L23 line-to-line voltages.
¯Display readings are the maximum demands over entire time of survey.
°Measurements can be made via 16 programmable Min/Max registers.
Installation 11
2. Installation
2.1 Initial Inspection
Upon receipt, the instrument should be free of damage and in perfect order. To
confirm this, first inspect the instrument for physical damage incurred in transit. If
the instrument is damaged, inform your local distributor immediately. Only after you
have determined that the instrument is damage-free, test the electrical performance.
2.2 Mechanical Installation
Location
The instrument should be mounted away from heat sources in a dirt-free
environment. The instrument should not be operated in direct sunlight nor should it
come into contact with oil or moisture.
Although designed to operate in an electrically noisy environment, the instrument
should not be placed near very high electric fields. It must be placed at least one-half
meter (1.64 feet) from current lines carrying up to 600 amperes. For currents greater
than 600A and up to 2,000A, this distance must be at least 1 meter (3.28 feet).
In the event that the instrument is mounted in a harsh, noisy environment with high
potential for electromagnetic impulses from heavy switch gears, motors or lightning,
it is recommended to install appropriate protective devices such as lightening and
over-voltage arresters to all incoming voltage inputs.
Mounting
The PM295 is designed to be panel mounted. The dimensions of the cutout
necessary both for front (standard) and rear panel mounting are shown in Figures 2-
1 and 2-2.
For either front or rear mounting, the instrument is positioned through the cutout,
and the bracket(s) are then screwed to the back of the instrument as shown in the
figures. For front mounting, the four thrust screws are tightened against the panel to
affix the instrument in place.
12
Installation
Figure 2-1 Front Mounting (standard)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173

Satec PM295 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI