Manual 7960-719A
Page 2 of 4
6. Attach terminal block to control panel with screw
(supplied) as shown in Figure 3.
7. Remove black fan motor wire from compressor
contactor and place on installed terminal block
(see Figure 3).
8. Install 5" black wire included with kit onto
compressor contactor where the black fan motor
wire was removed, and then connect other end of
wire to the terminal block opposite the black fan
motor wire.
NOTE: A generic wiring diagram is provided on page 4.
FIGURE 3
Terminal Block
Black Fan Motor Wire
5" Black Wire Connections
9. Remove refrigerant service port cap and screw
low ambient cycling control onto service port (see
Figure 4). Finger tighten rst, then use a wrench
to tighten an additional 1/4 turn. Use a second
wrench to back up the service port while tightening
the switch. Apply soap solution to ensure
refrigerant connection is leak-free.
10. Run wires from low ambient fan cycling control up
into control panel with fan motor lead wires. Be
sure to work permagum seal back into place after
wires have been run to control panel.
11. Connect the low ambient control wires to the
installed terminal block: One wire goes with the
black fan motor wire and the other goes with the
installed black wire connected to the compressor
contactor (see Figure 4)
FIGURE 4
Low Ambient Fan
Cycling Control
12. Remove two (2) screws securing the low voltage
terminal strip and gently pull the low voltage
terminal strip out (see Figure 5).