Danfoss VLT AutomationDrive FC 360, VLT® AutomationDrive FC 360 Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Danfoss VLT AutomationDrive FC 360 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
MAKING MODERN LIVING POSSIBLE
Quick Guide
VLT
®
AutomationDrive FC 360
www.danfoss.com/drives
Contents
1 Safety
3
2 Quick Start
4
2.1 Identification and Variants
4
2.2 Hand On/Auto On Mode
5
2.3 Application Selections
5
2.4 Jumper Terminal 12 and 27
8
2.5 Automatic Motor Adaptation (AMA)
8
3 Introduction
9
3.1 Exploded Views
9
3.2 Product Overview
11
3.3 Additional Resources
11
3.4 Frame Sizes and Power Ratings
11
4 Installation
12
4.1 Mechanical Installation
12
4.2 Electrical Installation
13
4.2.1 General Requirements 15
4.2.2 Grounding Requirements 15
4.2.2.1 Leakage Current (>3.5 mA) 15
4.2.3 Mains, Motor and Earth Connections 16
4.2.4 Control Wiring 17
4.2.4.1 Access 17
4.2.4.2 Control Terminal Types 17
4.2.4.3 Control Terminal Functions 18
4.2.4.4 Using Screened Control Cables 18
4.3 Serial Communication
19
5 User Interface and Programming
20
5.1 Programming
20
5.1.1 Local Control Panels (LCP) 20
5.1.2 Numerical Local Control Panel (LCP 21) 20
5.1.3 Control Panel LCP 102 21
5.1.4 The Right-Key Function 22
5.2 Main Menu
22
5.3 Quick Menu
24
5.4 PM Motor Setup
26
5.5 Profibus
27
5.6 Parameter List
28
Contents
VLT
®
AutomationDrive FC 360 Quick Guide
MG06A402 - Rev. 2013-10-30 1
5.6.1 Main Menu Structure 29
6 Wiring Examples
33
7 Warnings and Alarms
36
7.1 System Monitoring
36
7.2 Warning and Alarm Types
36
7.2.1 Warnings 36
7.2.2 Alarm Trip vs. Alarm Trip Lock 36
7.3 Warning and Alarm Displays
36
7.4 Warning and Alarm Definitions
37
7.5 Error Definitions
39
8 Basic Troubleshooting and FAQs
40
8.1 Start Up and Operation
40
9 Specifications
42
9.1 Power-dependent Specifications
42
9.1.1 Mains Supply 3 x 380-480 V AC 42
9.2 General Technical Data
45
9.3 Fuse Specifications
49
9.3.1 Fuses 49
9.3.2 Recommendations 49
9.3.3 CE Compliance 49
9.4 Connection Tightening Torques
50
Index
51
Contents
VLT
®
AutomationDrive FC 360 Quick Guide
2 MG06A402 - Rev. 2013-10-30
1 Safety
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input power. Failure to perform
installation, start-up, and maintenance by qualified
personnel could result in death or serious injury.
Installation, start-up, and maintenance must be
performed by qualified personnel only.
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains,
the motor may start at any time, causing risk of death,
serious injury, equipment, or property damage. The
motor can start by means of an external switch, a serial
bus command, an input reference signal from the LCP or
LOP, or after a cleared fault condition.
Disconnect the frequency converter from mains
whenever personal safety considerations make
it necessary to avoid unintended motor start.
Press [Off/Reset] on the LCP, before
programming parameters.
The frequency converter, motor, and any driven
equipment must be in operational readiness
when the frequency converter is connected to
AC mains.
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input power. Failure to perform
installation, start-up, and maintenance by qualified
personnel could result in death or serious injury.
Installation, start-up, and maintenance must be
performed by qualified personnel only.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors,
which can remain charged even when the frequency
converter is not powered. Failure to wait the specified
time after power has been removed before performing
service or repair work, could result in death or serious
injury.
1. Stop the motor.
2. Disconnect AC mains, permanent magnet type
motors, and remote DC-link power supplies,
including battery back-ups, UPS, and DC-link
connections to other frequency converters.
3. Wait for the capacitors to discharge fully, before
performing any service or repair work. The
duration of waiting time is specified in
Table 1.1.
Voltage [V]
Minimum waiting time (minutes)
4 15
380-480 0.37-7.5 kW 11-75 kW
High voltage may be present even when the warning LEDs are
off!
Table 1.1 Discharge Time
The following symbols are used in this document:
WARNING
Indicates a potentially hazardous situation which could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which could
result in minor or moderate injury. It may also be used
to alert against unsafe practices.
NOTICE
Indicates important information, including situations that
may result in damage to equipment or property.
Illustration 1.1 Approval
Safety
VLT
®
AutomationDrive FC 360 Quick Guide
MG06A402 - Rev. 2013-10-30 3
1
1
2 Quick Start
WARNING
Improper use could result in death, serious injury,
equipment, or property damage. Before installing or
using the equipment, carefully read 1 Safety and 4 Instal-
lation!
2.1 Identification and Variants
Confirm that the equipment matches the requirements
and ordering information by checking power size, voltage
and overload data on the name plate of the frequency
converter.
130BC435.11
CHASSIS/IP20
VLT
MADE BY DANFOSS
IN CHINA
AutomationDrive
www.danfoss.com
R
T/C: FC-360HK37T4E20H2BXCDXXSXXXXAXBX
P/N: 134F2970 S/N: 691950A240
0.37 kW 0.5HP High Overload
IN: 3x380-480V 50/60Hz 1.24/0.99A
OUT: 3x0-Vin 0-500Hz 1.2/1.1A(Tamb. 45 C)
o
1
2
3
CAUTION:
SEE MANUAL
WARNING:
AND LAODSHARING BEFORE SERVICE
STORED CHARGE DO NOT TOUCH UNTIL 4 MIN. AFTER
DISCONNECTION
RISK OF ELECTRIC SHOCK-DUAL SUPPLY DISCONNECT MAINS
Illustration 2.1 Name Plate 1 and 2
1 Typecode
2 Ordering number
3 Specifications
Table 2.1 Legend to Illustration 2.1
1-6: Product Name
7: Overload
H: Heavy Duty
Q: Normal Duty
1)
8-10: Power Size
0.37-75 kW e.g.
K37: 0.37 kW
2)
1K1: 1.1 kW
11K: 11 kW etc.
11-12: Voltage Class T4: 380-480 V three phases
13-15: IP Class E20: IP20
16-17: RFI H2: C3 Class
18: Brake chopper
X: No
B: Built-in
4)
19: LCP X: No
20: PCB Coating C: 3C3
21: Mains terminals D: Load sharing
29-30: Embedded Fieldbus
AX: No
A0: Profibus
AL: ProfiNet
3)
Table 2.2 Type Code: Selection of Different Features and Options
See for options and accessories.
1) Only 11-75 kW for normal duty variants. Profibus and ProfiNet
unavailable for normal duty.
2) For all power sizes see 3.4 Frame Sizes and Power Ratings
3) Not available yet.
4) 0.37-22 kW with built-in brake chopper. 30-75 kW external brake
chopper only.
130BC437.10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
F C - 3 6 0 H T 4 E 2 0 H 2 X X C D X X S X X X X A X B X
Q B 0
L
A
A
Illustration 2.2 Typecode String
Quick Start
VLT
®
AutomationDrive FC 360 Quick Guide
4 MG06A402 - Rev. 2013-10-30
22
2.2 Hand On/Auto On Mode
After installation (see 4 Installation), there are 2 simple
ways to start up the frequency converter, Hand On and
Auto On mode. At the first power-up it is in auto on mode.
130BD062.10
D
Hand
On
Reset
Auto
On
OK
On
Warn
Alarm
Illustration 2.3 Location of Hand On, Off/Reset and Auto On
Keys on the NLCP
Press [Hand On] to provide a local start command
to the frequency converter. Press [
] and [
] to
increase and decrease speed.
Press [Off/Reset] to stop the frequency converter.
Press [Auto On] to control the frequency
converter either via control terminals or serial
communication.
CAUTION
Since the frequency converter is in auto on mode at first
power up, the frequency converter may start the motor
directly.
NOTICE
5-12 Terminal 27 Digital Input has coast inverse as default
setting. Connect terminals 12 and 27 to test Hand On/
Auto On running.
For LCP operation, see 5 User Interface and Programming.
2.3
Application Selections
Use the selections for quick application set-up of the most
common applications by setting 0-16 Application Selections.
When necessary, the selections can be modified for
individual needs. All selections are for Auto On mode.
NOTICE
When an application is selected, relevant parameters are
automatically set. Customer specific configuration of all
parameters based on specific requirements is still
possible.
CAUTION
If any of the applications below are selected, relay 1 is
set to [Running] and relay 2 is set to [Alarm]
Application
Pumps, fans, compressors
130BC430.10
+24V 12
DI1 18
DI2 19
DI3 27
DI4 29
DI5 32
DI6 33
DI7 31
COM 20
+10V 50
AI1 53
-
+
AI2 54
COM 55
AO1 45
AO2 42
1
2
3
4
5
6
R1
R2
FC 360
Start
Coast inverse
Jog
4-20
mA
Description
For applications where a
value (e.g. pressure,
temperature) must be
kept at a desired level by
sensor feedback
Parameter settings
1-00 (Configuration Mode): [3] Process Close Loop
1-03 (Torque Characteristics): [1] Variable Torque
3-00 (Ref Range): [0] Min- Max
3-15 (Ref Source 1): [0] No Function
4-12 (Motor Low Limit): 30.0 Hz
4-14 (Motor High Limit): 50.0 Hz
5-10 (DI 18 Selection): [8] Start
5-12 (DI 27 Selection): [2] Coast Inverse
5-14 (DI 32 Selection): [14] Jog
5-40 (Relay 1 Selection): Running
5-40 (Relay 2 Selection): Alarm
6-22 (AI 54 Low): 4.0 mA
6-23 (AI 54 High): 20.0 mA
6-29 (AI 54 Mode): [0] Current Mode
6-70 (Term 45 Mode): [0] 0-20 mA
6-71 (AO45): [100] Output freq
6-90 (Term 42 Mode): [0] 0-20 mA
6-91 (AO42): [103] Motor current
7-20 (Process CL feedback source): [2] Analog input 54
Table 2.3 Process Closed Loop
Quick Start
VLT
®
AutomationDrive FC 360 Quick Guide
MG06A402 - Rev. 2013-10-30 5
2 2
Application
Local/Remote
130BC431.10
+24V 12
DI1 18
DI2 19
DI3 27
DI4 29
DI5 32
DI6 33
DI7 31
COM 20
+10V 50
AI1
53
-
+
AI2
54
COM 55
AO1
45
AO2 42
1
2
3
4
5
6
R1
R2
FC 360
Start
Coast inverse
Setup select
4-20
mA
Description
For applications
where the speed
reference can be
switched between
local potentiometer
and remote current
signal
Parameter settings Set-up 1 Set-up 2
0-10 (Active Set-
up)
[9] Multi Set-up [9] Multi Set-up
0-12 (Link Set-up) [20] Linked [20] Linked
1-00 (Configuration
Mode)
[0] Speed Open Loop [0] Speed Open Loop
3-00 (Ref Range) [0] Min- Max [0] Min- Max
3-15 (Ref Source 1) [1] AI 53 [2] AI 54
3-16 (Ref Source 2)
4-12 (Motor Low
Limit)
25.0 Hz 25.0 Hz
4-14 (Motor High
Limit)
50.0 Hz 50.0 Hz
5-10 (DI 18
Selection)
[8] Start [8] Start
5-12 (DI 27
Selection)
[2] Coast Inverse [2] Coast Inverse
5-14 (DI 32
Selection)
[23] Set-up select [23] Set-up select
5-40 (Relay 1
Selection)
Running Running
5-40 (Relay 2
Selection)
Alarm Alarm
6-10 (AI 53 Low) 0.07 V
6-11 (AI 53 High) 10 V
6-19 (AI 53 Mode) [1] Voltage Mode
6-22 (AI 54 Low) 4.0 mA
6-23 (AI 54 High) 20.0 mA
6-29 (AI 54 Mode) [0] Current Mode
6-70 (Term 45
Mode)
[0] 0-20 mA [0] 0-20 mA
6-71 (AO45) [100] Output freq [100] Output freq
6-90 (Term 42
Mode)
[0] 0-20 mA [0] 0-20 mA
6-91 (AO42) [103] Motor current [103] Motor current
Table 2.4 Local/Remote
Application
Conveyors, extruders
130BC432.10
+24V 12
DI1 18
DI2 19
DI3 27
DI4 29
DI5 32
DI6 33
DI7 31
COM 20
+10V 50
AI1
53
AI2
54
COM 55
AO1
45
AO2 42
1
2
3
4
5
6
R1
R2
FC 360
Start
Coast inverse
Description
For running at a stable
speed by a voltage
reference signal.
Parameter settings
1-00 (Configuration Mode): [0] Speed Open Loop
3-00 (Ref Range): [0] Min- Max
3-15 (Ref Source 1): [1] AI 53
4-12 (Motor Low Limit): 25.0 Hz
4-14 (Motor High Limit): 50.0 Hz
5-10 (DI 18 Selection): [8] Start
5-12 (DI 27 Selection): [2] Coast Inverse
5-40 (Relay 1 Selection): Running
5-40 (Relay 2 Selection): Alarm
6-10 (AI 53 Low): 0.07 V
6-11 (AI 53 High): 10 V
6-19 (AI 53 Mode): [1] Voltage Mode
6-70 (Term 45 Mode): [0] 0-20 mA
6-71 (AO45): [100] Output freq
6-90 (Term 42 Mode): [0] 0-20 mA
6-91 (AO42): [103] Motor current
Table 2.5 Speed Open Loop
Quick Start
VLT
®
AutomationDrive FC 360 Quick Guide
6 MG06A402 - Rev. 2013-10-30
22
Application
Machine tools, texturizers
130BC433.12
+24 V 12
DI1 18
DI2 19
DI3 27
DI4 29
DI5 32
DI6 33
DI7 31
COM 20
50
AI1
53
AI2
54
COM 55
AO1
45
AO2 42
1
2
3
4
5
6
R1
R2
FC 360
Start
Coast inverse
+10 V
B
A
Description
For precise speed
applications with 24 V
encoder feedback
Parameter settings
1-00 (Configuration Mode): [1] Speed Close Loop
3-00 (Ref Range): [0] Min- Max
3-15 (Ref Source 1): [1] AI 53
3-16 (Ref Source 2): [11] Local Bus Ref
4-12 (Motor Low Limit): 20.0 Hz
4-14 (Motor High Limit): 50.0 Hz
5-10 (DI 18 Selection): [8] Start
5-12 (DI 27Selection): [2] Coast Inverse
5-14 (DI 32 Selection): [82] Encoder input B
5-15 (DI 33 Selection): [81] Encoder input A
5-40 (Relay 1 Selection): Running
5-40 (Relay 2 Selection): Alarm
6-10 (AI 53 Low): 0.07 V
6-11 (AI 53 High): 10 V
6-19 (AI 53 Mode): [1] Voltage Mode
6-70 (Term 45 Mode): [0] 0-20 mA
6-71 (AO45): [100] Output freq
6-90 (Term 42 Mode): [0] 0-20 mA
6-91 (AO42): [103] Motor current
7-00 (Speed PID Feedback Source): [1] 24 V encoder
Table 2.6 Speed Close Loop
Application
Industrial washing
machines, conveyors
130BC434.10
+24V 12
DI1 18
DI2 19
DI3 27
DI4 29
DI5 32
DI6 33
DI7 31
COM 20
+10V 50
AI1
53
AI2
54
COM 55
AO1
45
AO2 42
1
2
3
4
5
6
R1
R2
FC 360
Start
Coast inverse
Pre set ref bit 0
Pre set ref bit 1
Pre set ref bit 2
Description
For applications with
8 different speeds by
digital input. By using
another digital input,
16 speeds are
possible.
Parameter settings
1-00 (Configuration Mode): [0] Speed Open Loop
3-00 (Ref Range): [0] Min- Max
3-15 (Ref Source 1): [0] No Function
4-14 (Motor High Limit): 50.0 Hz
5-10 (DI 18 Selection): [8] Start
5-12 (DI 27 Selection): [2] Coast Inverse
5-13 (DI 29 Selection): [16] Preset ref bit 0
5-14 (DI 32 Selection): [17] Preset ref bit 1
5-15 (DI 33 Selection): [18] Preset ref bit 2
6-70 (Term 45 Mode): [0] 0-20 mA
6-71 (AO45): [100] Output freq
6-90 (Term 42 Mode): [0] 0-20 mA
6-91 (AO42): [103] Motor current
Table 2.7 Multi-speed
NOTICE
For further examples, refer to 6 Wiring Examples.
Quick Start
VLT
®
AutomationDrive FC 360 Quick Guide
MG06A402 - Rev. 2013-10-30 7
2 2
2.4 Jumper Terminal 12 and 27
When using factory default programming values, jumper
wire may be required between terminal 12 and terminal 27
for the frequency converter to operate.
Digital input terminal 27 is designed to receive a
24 V DC external interlock command. In many
applications, the user wires an external interlock
device to terminal 27
When no interlock device is used, wire a jumper
between control terminal 12 to terminal 27. This
provides internal 24 V signal on terminal 27
No signal present prevents the unit from
operating
2.5 Automatic Motor Adaptation (AMA)
Automatic motor adaptation (AMA)
It is highly recommended to run AMA because it measures
the electrical characteristics of the motor to optimise
compatibility between the frequency converter and the
motor under VVC
plus
mode.
The frequency converter builds a mathematical
model of the motor for regulating output motor
current thus enhancing motor performance.
Some motors may be unable to run the complete
version of the test. In that case, select Enable
reduced AMA
If warnings or alarms occur, see 7 Warnings and
Alarms
Run this procedure on a cold motor for best
results
To run AMA using the numeric LCP (NLCP)
1. By default parameter setting, connect terminals
12 and 27 before running AMA.
2. Enter the main menu.
3.
Go to parameter group 1-** Load and Motor.
4. Press [OK].
5. Set motor parameters using name plate data for
parameter group 1-2* Motor Data.
6.
Set motor cable length in 1-42 Motor Cable Length
7.
Go to 1-29 Automatic Motor Adaptation (AMA).
8. Press [OK].
9.
Select [1] Enable complete AMA.
10. Press [OK].
11. The test runs automatically and indicates when it
is complete.
NOTICE
AMA function in FC 360 does not cause the motor to run
and it does not harm the motor.
Quick Start
VLT
®
AutomationDrive FC 360 Quick Guide
8 MG06A402 - Rev. 2013-10-30
22
3 Introduction
3.1 Exploded Views
130BC439.10
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
03
02
01
05
04
Illustration 3.1 Exploded View J1-J5 (0.37-22 kW), IP20
1
NLCP (accessory) 10 2-Pole Relay 2 (0.37-7.5 kW), pluggable
3-Pole Relay 2 (11-22 kW), pluggable
2 Control cassette 11 Mains terminals
3 RFI switch (screw M3x12 only) 12 Cable strain relief (0.37-2.2 kW: accessory)
4 Removable fan assembly 13 Pluggable RS-485 terminal
5 Grounding clamp (accessory) 14 Fixed I/O terminals
6 Shielded cable grounding clamp and strain relief (accessory) 15 Fixed I/O terminals
7 Motor terminal (U V W) and brake and load sharing terminals 16 Terminal cover
8 PE ground 17 Option-B (MCB102/103 accessories)
9 3-Pole relay 1
Table 3.1 Legend to Illustration 3.1
Introduction
VLT
®
AutomationDrive FC 360 Quick Guide
MG06A402 - Rev. 2013-10-30 9
3 3
3
2
1
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
130BD647.10
Illustration 3.2 Exploded View J7 (55 kW, 75 kW), IP20
1
J7 drive 10 I/O cable clamps
2 Removable fan assembly 11 Terminal cover
3 M5 screw X4 (for fan assembly) 12 Motor terminals
4 NLCP (accessory) 13 Load sharing terminals
5 Option B (accessory) 14 Removable plugger (for load sharing terminal)
6 I/O terminals 15 Shielded cable grounding clamps
7 I/O terminals 16 Mains terminals
8 Pluggable RS-485 terminals 17 Decoupling plate (accessory)
9 Relay terminal 1 & 2, fixed 18 M4 screw X3 (for decoupling plate)
Table 3.2 Legend to Illustration 3.2
Introduction
VLT
®
AutomationDrive FC 360 Quick Guide
10 MG06A402 - Rev. 2013-10-30
33
3.2 Product Overview
A frequency converter is an electronic motor controller
that converts AC mains input into a variable AC waveform
output. The frequency and voltage of the output are
regulated to control the motor speed or torque. The
frequency converter can vary the speed of the motor in
response to system feedback, such as changing
temperature or pressure for controlling fan, compressor, or
pump motors. The frequency converter can also regulate
the motor by responding to remote commands from
external controllers.
In addition, the frequency converter monitors the system
and motor status, issues warnings or alarms for fault
conditions, starts and stops the motor, optimizes energy
efficiency, and offers many more control, monitoring, and
efficiency functions. Operation and monitoring functions
are available as status indications to an outside control
system or serial communication network.
3.3 Additional Resources
Other resources are available to understand advanced
frequency converter functions and programming.
The Programming Guide provides greater detail
on working with parameters.
The Design Guide is intended to provide detailed
capabilities and functionality to design motor
control systems.
Optional equipment is available that may change
some of the procedures described. Be sure to see
the instructions supplied with those options for
specific requirements.
Contact the local Danfoss supplier or go to
www.danfoss.com/fc360 for downloads.
3.4 Frame Sizes and Power Ratings
Frame size
380-480 V
J1 J2 J3 J4 J5 J6 J7
Power size
[kW]
0.37-2.2 3.0-5.5 7.5 11-15 18.5-22 30-45 55-75
Dimensions
[mm]
A
a
D
C
B
b
130BC449.10
Height A 210 272.5 272.5 317.5 410 515 550
Width B 75 90 115 133 150 233 308
Depth C
(with option B)
168 (181) 168 (181) 168 (181) 245 (258) 245 (258) 241 323
Mounting holes
a 198 260 260 297.5 390 495 521
b 60 70 90 105 120 200 270
Mounting screw M4 M5 M5 M6 M6 M8 M8
Table 3.3 Frames Sizes, Power Ratings and Dimensions
Introduction
VLT
®
AutomationDrive FC 360 Quick Guide
MG06A402 - Rev. 2013-10-30 11
3 3
4 Installation
4.1 Mechanical Installation
Select the best possible operation site by considering:
Ambient operating temperature
Installation method
How to cool the unit
Position of the frequency converter
Cable routing
Power source supplying correct voltage and
necessary current
Motor current rating within the maximum current
from the frequency converter
Correct rating of external fuses and circuit
breakers
Cooling and Mounting:
Top and bottom clearance for air cooling must be
provided, see Table 4.1 for clearance requirements
Derating for temperatures starting from 45 °C
and elevation 1000 m above sea level must be
considered. See the equipment Design Guide for
detailed information.
Enclosure J1-J5 J6/J7
Clearance above and below the
unit [mm]
100 200
Table 4.1 Minimum Airflow Clearance Requirements
Mount the unit vertically
IP20 units allow side-by-side installation
Improper mounting can result in over heating
and reduced performance
Use the slotted mounting holes on the unit for
wall mounting, when provided
See 9.4 Connection Tightening Torques for proper
tightening specifications.
Installation
VLT
®
AutomationDrive FC 360 Quick Guide
12 MG06A402 - Rev. 2013-10-30
44
4.2 Electrical Installation
This section contains detailed instructions for wiring the frequency converter.
130BC438.14
3 Phase
power
input
Switch Mode
Power Supply
Motor
Analog Output
Interface
(PNP) = Source
(NPN) = Sink
ON=Terminated
OFF=Open
Brake
resistor
91 (L1)
92 (L2)
93 (L3)
PE
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
0/4-20 mA
12 (+24 V OUT)
31 (D IN)
18 (D IN)
20 (COM D IN)
10 V DC
15 mA 100 mA
+ - + -
(U) 96
(V) 97
(W) 98
(PE) 99
(A OUT) 45
(A OUT) 42
(P RS-485) 68
(N RS-485) 69
(COM RS-485) 61
0V
5V
S801
0/4-20 mA
RS-485
RS-485
03
+10 V DC
0/4-20 mA
0-10 V DC
24 V DC
02
01
05
04
240 V AC, 2 A
24 V (NPN)
0 V (PNP)
0 V (PNP)
24 V (NPN)
19 (D IN)
24 V (NPN)
0 V (PNP)
27
24 V
0 V
(D IN/OUT)
0 V (PNP)
24 V (NPN)
(D IN/OUT)
0 V
24 V
29
24 V (NPN)
0 V (PNP)
0 V (PNP)
24 V (NPN)
33 (D IN)
32 (D IN)
95
P 5-00
21
ON
(+UDC) 89
(BR) 81
24 V (NPN)
0 V (PNP)
0-10 V DC
(-UDC) 88
RFI
3)
0 V
240 V AC, 2 A
Relay 1
1)
Relay 2 2)
4)
06
5)
Illustration 4.1 Basic Wiring Schematic Drawing
A=Analog, D=Digital
1) Built-in brake chopper available from 0.37-22 kW
2) Relay 2 is 2-pole for J1-J3 and 3-pole for J4-J7. Relay 2 of J4-J7 with terminals 4, 5 and 6 same NO/NC logic as Relay 1. Relay
are pluggable in J1-J5, and fixed in J6-J7.
3) Dual DC choke in 30-75 kW
4) Switch S801 (bus terminal) can be used to enable termination on the RS-485 port (terminals 68 and 69).
5) No BR for J6 and J7 drives
Installation
VLT
®
AutomationDrive FC 360 Quick Guide
MG06A402 - Rev. 2013-10-30 13
4 4
130BD391.11
1
2
3
4
5
6
78
9
10
Reset
Auto
On
Hand
On
OK
Back
Menu
Status Quick
Menu
Main
Menu
PE
U
V
W
L1
L2
L3
PE
Illustration 4.2 Typical Electrical Connection
1
PLC 6 Min. 200 mm (7.9 in) between control cables, motor and mains
2 Frequency converter 7 Motor, 3-phase and PE
3 Output contactor (Generally not recommended) 8 Mains, 3-phase and reinforced PE
4 Earth (grounding) rail (PE) 9 Control wiring
5 Cable insulation (stripped) 10
Equalising min. 16 mm
2
(0.025 in)
Table 4.2 Legend to Illustration 4.2
Installation
VLT
®
AutomationDrive FC 360 Quick Guide
14 MG06A402 - Rev. 2013-10-30
44
4.2.1 General Requirements
WARNING
EQUIPMENT HAZARD!
Rotating shafts and electrical equipment can be
hazardous. Extreme care should be taken to protect
against electrical hazards when applying power to the
unit. All electrical work must conform to national and
local electrical codes and installation, start up, and
maintenance should only be performed by trained and
qualified personnel. Failure to follow these guidelines
could result in death or serious injury.
CAUTION
WIRING ISOLATION!
Run input power, motor wiring and control wiring in 3
separate metallic conduits or use separated shielded
cable for high frequency noise isolation. Failure to isolate
power, motor and control wiring could result in less than
optimum frequency converter and associated equipment
performance.
Run motor cables from multiple frequency converters
separately. Induced voltage from output motor cables
run together can charge equipment capacitors even with
the equipment turned off and locked out.
An electronically activated function within the
frequency converter provides overload protection
for the motor. The overload provides Class 20
motor protection. See 7 Warnings and Alarms for
details on the trip function.
Wire Type and Ratings
All wiring must comply with local and national
regulations regarding cross-section and ambient
temperature requirements.
Danfoss recommends that all power connections
be made with a minimum 75 °C rated copper
wire.
See 9 Specifications for recommended wire sizes.
4.2.2
Grounding Requirements
WARNING
GROUNDING HAZARD!
For operator safety, it is important to ground the
frequency converter properly by a certified electrical
installer in accordance with national and local electrical
codes as well as instructions contained within this
document. Ground currents are higher than 3.5 mA.
Failure to ground the frequency converter properly could
result in death or serious injury.
Proper protective grounding for equipment with
ground currents higher than 3.5 mA must be
established, see 4.2.2.1 Leakage Current (>3.5 mA).
A dedicated ground wire is required for input
power, motor power and control wiring.
Use the clamps provided with the equipment for
proper ground connections.
Do not ground one frequency converter to
another in a “daisy chain” fashion (see
Illustration 4.3).
Keep the ground wire connections as short as
possible.
Using high-strand wire to reduce electrical noise
is recommended.
Follow motor manufacturer wiring requirements.
130BC500.10
FC 1
FC 1
FC 2
FC 2
FC 3
FC 3
PE
PE
Illustration 4.3 Grounding Principle
4.2.2.1
Leakage Current (>3.5 mA)
Follow national and local codes regarding protective
earthing of equipment with a leakage current > 3.5 mA.
The earth leakage current depends on various system
configurations including RFI filtering, screened motor
cables, and frequency converter power.
EN/IEC61800-5-1 (Power Drive System Product Standard)
requires special care if the leakage current exceeds 3.5 mA.
Grounding must be reinforced in one of the following
ways:
Installation
VLT
®
AutomationDrive FC 360 Quick Guide
MG06A402 - Rev. 2013-10-30 15
4 4
Ground wire of at least 10 mm
2
(copper wire)
Two separate ground wires both complying with
the dimensioning rules
See EN 60364-5-54 § 543.7 for further information.
Using RCDs
Where residual current devices (RCDs), also known as earth
leakage circuit breakers (ELCBs), are used, comply with the
following:
Use RCDs of type B only which are capable of
detecting AC and DC currents
Use RCDs with an inrush delay to prevent faults
due to transient earth currents
Dimension RCDs according to the system configu-
ration and environmental considerations
4.2.3
Mains, Motor and Earth Connections
WARNING
INDUCED VOLTAGE!
Run output motor cables from multiple frequency
converters separately. Induced voltage from output
motor cables run together can charge equipment
capacitors even with the equipment turned off and
locked out. Failure to run output motor cables separately
could result in death or serious injury.
Earthing (grounding) clamps are provided for motor wiring
(see Illustration 4.4).
Do not install power factor correction capacitors
between the frequency converter and the motor
Do not wire a starting or pole-changing device
between the frequency converter and the motor
Follow motor manufacturer wiring requirements
All frequency converters may be used with an
isolated input source as well as with ground
reference power lines. When supplied from an
isolated mains source (IT mains or floating delta)
or TT/TN-S mains with a grounded leg (grounded
delta), set 14-50 RFI Filter to OFF (size J6-J7) or
remove the RFI screw (J1-J5). When off, the
internal RFI filter capacitors between the chassis
and the intermediate circuit are isolated to avoid
damage to the intermediate circuit and to reduce
earth capacity currents in accordance with IEC
61800-3.
Do not install switch between the frequency
converter and the motor in IT mains.
130BC501.10
01
02 03
04
05
Illustration 4.4 Mains, Motor and Ground Connections for
Basic Frequency Converters
Illustration 4.5 Mains, Motor and Ground Connections for J7-
frame Frequency Converters
Installation
VLT
®
AutomationDrive FC 360 Quick Guide
16 MG06A402 - Rev. 2013-10-30
44
Illustration 4.4 displays mains input, motor, and grounding
for basic frequency converters. Illustration 4.5 displays
mains input, motor, and grounding for FC 360 J7-frame
frequency converters. Actual configurations vary with unit
types and optional equipment.
4.2.4 Control Wiring
4.2.4.1 Access
Remove cover plate with a screw driver. See
Illustration 4.6.
130BC504.10
Illustration 4.6 Control Wiring Access for J1-J7 Enclosures
4.2.4.2
Control Terminal Types
Illustration 4.7 shows the frequency converter control
terminals. Terminal functions and default settings are
summarized in Table 4.3.
42 45
12
18
19
27
29
31
32
33
20
50
53
54
55
130BC505.12
Illustration 4.7 Control Terminal Locations
See 9.2 General Technical Data for terminal ratings details.
Termin
al
Para-
meter
Default
setting
Description
Digital I/O, Pulse I/O, Encoder
12 - +24 V DC
24 V DC supply voltage.
Maximum output current
is 100 mA for all 24 V
loads.
18 5-10 [8] Start
Digital inputs.
19 5-11 [10] Reversing
31 5-16 [0] No operation Digital input, pulse input.
32 5-14 [0] No operation
Digital input, 24 V
encoder.
33 5-15 [0] No operation
27
5-12
5-30
DI [2] Coast
inverse
DO [0] No
operation
Selectable for either
digital input, digital
output or pulse output.
Default setting is digital
input.
29
5-13
5-31
DI [14] Jog
DO [0] No
operation
20 -
Common for digital inputs
and 0 V potential for 24 V
supply.
Analog inputs/outputs
42 6-91 [0] No operation Programmable analog
output. The analog signal
is 0-20 mA or 4-20 mA at
a maximum of 500 Ω. Can
also be configured as
digital outputs
45 6-71 [0] No operation
50 - +10 V DC
10 V DC analog supply
voltage. 15 mA maximum
commonly used for
potentiometer or
thermistor.
53 6-1* Reference
Analog input. Selectable
for voltage or current.54 6-2* Feedback
55 - Common for analog input
Serial communication
61 -
Integrated RC-Filter for
cable screen. ONLY for
connecting the screen
when experiencing EMC
problems.
68 (+) 8-3* RS-485 Interface. A control
card switch is provided
for termination resistance.
69 (-) 8-3*
Relays
Installation
VLT
®
AutomationDrive FC 360 Quick Guide
MG06A402 - Rev. 2013-10-30 17
4 4
Termin
al
Para-
meter
Default
setting
Description
01, 02,
03
5-40 [0] [0] No operation
Form C relay output.
These relays are in various
locations depending upon
the frequency converter
configuration and size.
Usable for AC or DC
voltage and resistive or
inductive loads.
RO2 in J1-J3 enclosure is
2-pole, only terminals 04
and 05 are available
04, 05,
06
5-40 [1] [0] No operation
Table 4.3 Terminal Descriptions
4.2.4.3
Control Terminal Functions
Frequency converter functions are commanded by
receiving control input signals.
Programme each terminal for the function it
supports in the parameters associated with that
terminal. See Table 4.3 for terminals and
associated parameters.
Confirm that the control terminal is programmed
for the correct function. See 5 User Interface and
Programming for details on accessing parameters
and for details on programming.
The default terminal programming initiates
frequency converter functioning in a typical
operational mode.
4.2.4.4
Using Screened Control Cables
Correct screening
The preferred method in most cases is to secure control
and serial communication cables with screening clamps
provided at both ends to ensure best possible high
frequency cable contact.
If the ground potential between the frequency converter
and the PLC is different, electric noise may occur that
disturbs the entire system. Solve this problem by fitting an
equalizing cable as close as possible to the control cable.
Minimum cable cross section: 16 mm
2
.
1
2
PE
FC
PE
PLC
130BB922.12
PE PE
<10 mm
Illustration 4.8 Screening Clamps at Both Ends
1
Min. 16 mm
2
2 Equalizing cable
Table 4.4 Legend to Illustration 4.8
50/60 Hz ground loops
With very long control cables, ground loops may occur. To
eliminate ground loops, connect one end of the screen-to-
ground with a 100 nF capacitor (keeping leads short).
100nF
FC
PE
PE
PLC
<10 mm
130BB609.12
Illustration 4.9 Connection with a 100 nF Capacitor
Avoid EMC noise on serial communication
This terminal is connected to ground via an internal RC
link. Use twisted-pair cables to reduce interference
between conductors. The recommended method is in
Illustration 4.10:
PE
FC
PE
FC
130BB923.12
PE PE
69
68
61
69
68
61
1
2
<10 mm
Illustration 4.10 Twisted-pair Cables
1
Min. 16 mm
2
2 Equalizing cable
Table 4.5 Legend to Illustration 4.10
Alternatively, the connection to terminal 61 can be
omitted:
PE
FC
PE
FC
130BB924.12
PE PE
69
69
68
68
1
2
<10 mm
Illustration 4.11 Twisted-pair Cables without Terminal 61
1
Min. 16 mm
2
2 Equalizing cable
Table 4.6 Legend to Illustration 4.11
Installation
VLT
®
AutomationDrive FC 360 Quick Guide
18 MG06A402 - Rev. 2013-10-30
44
/