78-8125-9902-1-B 11
For JCN to JCN Splices
5.2.2 Useapieceofcablejacket,removedduringcablepreparation,tocoverandprotectexposedcable
semi-conundertheareawheretheneutraland/orgroundconnectionwillbemade.Securewithtape.
Ensurethatthecablejacketpiecedoesnottouchthesplicebody(Figure20).
Note: Ifgroundingsplice,leavesufficientneutralwirelengthtoallowforagroundwireconnectionnextto
cablejacketormakebothneutralandgroundconnectionsusingasingleconnector.
5.2.3 Connectneutralsusingasuitablecompressionconnector("INLINE","C",or"H"type)between
jacketendandreducedsplicediameter.Keepconnectorprofileaslowaspossible.Crimpconnector
followingtheconnectormanufacturer'srecommendation(Figure20).
Splice Body
Neutral Connection
Area for ground connection
Piece of Cable Jacket
Figure20
6.0 Grounding (Optional) for JCN Splices
Note: Usetheseinstructionsifcircuitgroundingisrequiredatthislocation.
6.1 Connectagroundwiretotheneutrals,intheareawherethesplicediameterisreduced.Toprotectthecable
semicon,placeapieceofcablejacket(removedduringthecablepreparation)underthegroundconnector.
Ensurethatthecablejacketpiecedoesnottouchthesplicebody.Keepconnectorprofileaslowaspossible.
ForC-TaporH-Tapconnectors,positionflatagainstthecable(Figure21).
Ground Wire
Connector
Bundled Neutrals
Ground Wire
Connector
Neutral Connector
Piece of cable jacket Piece of cable jacket
Ground Wire Connection
for Bundled Neutrals
Ground Wire Connection
for Non-bundled Neutrals
Figure21