Gas Control Manager Program User Manual (ROC800)
16 Issued Aug-14
Station ESD
Configures the Emergency Shutdown feature. If you
leave this field “Undefined” the ESD is not activated. This
feature can also be used for routine station shut-in. When
tripped, an ESD closes all run switching valves to provide
positive shut-in. A Set condition is logged to the alarm
log. The program restores the run switching function
when the ESD condition clears, and sends a Clear
condition to the alarm log.
ESD TLP
Defines the TLP the program monitors for emergency
shutdown.
Action On
Failure
Verifies tube flowing conditions or DI states relative to the
focus tube depending on the selected Failure Type.
Various actions are possible based on the selection. No
evaluations are made until after the Failure Delay counter
to allow run switching to stabilize before applying any
actions are applied. Valid values are:
Type:
None
Disables any failure evaluation.
Type:
Illegal PV Flow
Evaluates valid tube flow by using the
PV Cutoff Value in the Focus Run
Verification section, which determines
if a tube is actually open or closed.
Type:
Illegal DI State
Uses digital input states to determine
if a tube is actually open or closed.
Action:
Status Only
Generates a status message code to
indicate a Failure condition.
Action:
Alarm Log
Sends a Failure condition to the alarm
log that contains the status message
code number.
Action:
Disable Tube &
Alarm Log
Disables the tube where the Failure
condition is identified and logs that
tube as OFF in the alarm log. If this
tube was not the last tube enabled,
run switching skips the disabled tube
and uses the next tube for control.
Failure Delay
(Sec)
All Action On Failures are performed after the Settling
Delay plus the Failure Delay setting in seconds.
Maximum value is 255 seconds.
2. Click Apply to save your changes.
3. Proceed to Section 3.1.2, Run Switching – Run Switch Tab: Tube
Settings.
Focus Run Verification methods can be used to assure the run switching
program’s focus tube is what is actually happening. An example of this is
a valve with momentary solenoids that do not change state when the
output is pulsed. If this were to occur, the program would switch focus and
lose sight of the actual valve states. This may be most useful for dual