BEA LO21 User guide

Type
User guide
75.5079.09 LO-21P 20130325 Page 1 of 13
PRODUCT
DESCRIPTION
TECHNICAL
SPECIFICATIONS
USERS GUIDE LO-21P
LOCK OUT RELAY
COMPONENT ID
SAFETY
PRECAUTIONS
The microprocessed LO-21P (PN: 10LO21P) Lock Out Relay is designed to provide a lockout function for the BEA
Bodyguard presence sensor, when used with the complete Parallax System. The LO-21P uses the motor and Bodyguard to
determine if the swing path of the automatic door is clear and allows the door to open or close. If the swing path of the
automatic door is not clear and the door is in the open position, the LO-21P will allow the Bodyguard to hold the door open
as long as it detects something. If the door is closed and there is something in the Bodyguard pattern, the LO-21P will
prohibit the activation device from opening the door.
Shut off all power going to the header before attempting any wiring procedures.
Maintain a clean & safe environment when working in public areas.
Constantly be aware of pedestrian traffic around the door area.
Always stop pedestrian traffic through the doorway when performing tests that may result in unexpected
reactions by the door.
Always check placement of all wiring before powering up to insure that moving door parts will not catch any
wires and cause damage to equipment.
Ensure compliance with all applicable safety standards (i.e. ANSI A156.10) upon completion of installation.
DESCRIPTION
SPECIFICATIONS
Power Supply
12-24 Volts AC/ DC
Operating Frequency
4 MHz (Microprocessor)
Power Consumption
10 mA at rest, 50 mA Max.
Output
SPST Relay
Max. Voltage - Relay Contact
60V DC, 120V AC
Max. Current - Relay Contacts
2A DC, 0.5A AC
75.5079.09 LO-21P 20130325 Page 2 of 13
ELECTRICAL
INSTALLATION
OPTION 1
STANDARD
WIRING
STANDARD WIRING
WIRE CONNECTIONS
Black
Motor Input -
Red
Motor Input +
Purple
Bodyguard COM. Pin 3
White
Bodyguard Data (-) Pin 6
Black / White
Activation Sensor COM.
Orange
Power input / 12-24 VAC/VDC ( - )
Gray
Bodyguard N.O. Pin 4
Red / White
Bodyguard Data (+) Pin 7 & Activation Sensor N.O.
Brown
Power input / 12-24 VAC/VDC (+)
Green
Door Control Common
Blue
Door Control Activation
Yellow
Door Control safety
All LO-21 wiring must be accomplished with the module unplugged. If the red / white striped and
white wires (data wires) touch each other when power is applied, damage to the unit will result.
LO-21P WIRING DIAGRAMS:
The wiring shown below may be used on most models of operators. See wiring diagrams at back of this manual for
specific diagrams.
brown
red/white
white
gray
purple
orange
24 V
TRANSFORMER
DATA + 7
DATA - 6
N.C. 5
N.O. 4
COM 3
POWER 2
POWER 1
red
black
blue
green
115 VAC
BODYGUARD
1 2 3 4 5
EAGLE
8 7 6 5 4 3 2 1
Contacts to open
at desired point of
inhibiting
Approach SuperScan
Stall SuperScan
(Swing Side)
1 2 3 4 5 6 7 8
yellow
SAFETY
AUTO
OFF
HOLD
MOTOR
+
-
OPERATOR
LO-21P
NOTE:
LO-21P DIPSWITCH SETTINGS:
#1 THROUGH #5 - SET FOR
REQUIRED LOCKOUT TIME
#6 ON, #7 OFF, #8 ON
Door Control
COMMON
ACTIVATION
STALL
Blk/white
IMPORTANT:
Before connecting the red and black wires from the LO-21P to the Motor, be sure to check the polarity of the voltage
with a multi-meter, to determine which wire is the positive side. The red wire of the lockout module must always be
connected to the positive side of the motor. When a positive reading is observed on the meter, (while the door is in hold
open) the red probe indicates the positive side. Thus, the red wire of the lockout will always be attached to whatever
wire the red probe was on when a positive reading was obtained.
NOTES:
For pairs of doors, wire the additional SuperScans the same as shown above.
For the inhibit function, operator mounted auxiliary switches may be used dry contacts only.
Bodyguard must be programmed to a relay value of 2.
NOTE: Bodyguard MUST be programmed
to a Relay Output value of 2. Default is 1.
75.5079.09 LO-21P 20130325 Page 3 of 13
ELECTRICAL
INSTALLATION
OPTION 2
Operator Mounted
Switch
Wiring diagram below shows how to wire when using an operator-mounted switch to control the flow of voltage from the
motor to the lockout module. Switch should be set to close a set of dry contacts when door is within 2 to 3 degrees of the
full open position.
brown
red/white
white
gray
purple
orange
LO-21P
24 V
TRANSFORMER
DATA + 7
DATA - 6
N.C. 5
N.O. 4
COM 3
POWER 2
POWER 1
MOTOR
+
red
black
blue
green
115 VAC
BODYGUARD
1 2 3 4 5
EAGLE
OPERATOR
-
MOTOR VOLTAGE
COMMON
ACTIVATION
STALL
8 7 6 5 4 3 2 1
Contacts to open
at desired point of
inhibiting
Approach SuperScan
Stall SuperScan
(Swing Side)
AUTO
OFF
HOLD
1 2 3 4 5 6 7 8
blk/white
OPERATOR AUX. SWITCH
SWITCH CLOSED AT FULL
OPEN POSITION
COM
NO
SINGLE POLE-DOUBLE
THROW SWITCH
Door Control
SAFETY
yellow
IMPORTANT:
Before connecting the red and black wires from the LO-21P to the Motor, be sure to check the polarity of the voltage
with a multi-meter, to determine which wire is the positive side. The red wire of the lockout module must always be
connected to the positive side of the motor. When a positive reading is observed on the meter, (while the door is in hold
open) the red probe indicates the positive side. Thus, the red wire of the lockout will always be attached to whatever
wire the red probe was on when a positive reading was obtained.
NOTES:
For pairs of doors, wire the additional SuperScans the same as shown above.
For the inhibit function, operator mounted auxiliary switches may be used dry contacts only.
Bodyguard must be programmed to a relay value of 2.
NOTE: Bodyguard MUST be programmed
to a Relay Output value of 2. Default is 1.
75.5079.09 LO-21P 20130325 Page 4 of 13
ELECTRICAL
INSTALLATION
Option 3 Double
Pole Double Throw
Switch
The wiring diagram below shows how to wire a DPDT switch to control the On-Off-Hold function, as well as data
between the motor and the LO21P.
brow n
red/w hite
w hite
gray
pu rple
orang e
LO-21P
24 V
TRANSFORMER
DATA + 7
DATA - 6
N.C. 5
N.O. 4
COM 3
POWER 2
POWER 1
MOTOR
+
red
blac k
blue
green
115 V A C
BODYGUARD
1 2 3 4 5
EAG LE
OPERATOR
-
MOTOR VOLTAGE
COM MO N
ACT IVATIO N
STAL L
8 7 6 5 4 3 2 1
Contacts to open
at desired point of
inhibiting
Approach SuperScan
Stall SuperScan
(Swing Side)
AUTO
OFF
HOLD
Door Co ntro l
1 2 3 4 5 6 7 8
blk/w hite
DOUBLE-PO LE
DOUBLE THROW SWIT CH
S AFETY
yellow
IMPORTANT:
Before connecting the red and black wires from the LO-21P to the Motor, be sure to check the polarity of the voltage
with a multi-meter, to determine which wire is the positive side. The red wire of the lockout module must always be
connected to the positive side of the motor. When a positive reading is observed on the meter, (while the door is in hold
open) the red probe indicates the positive side. Thus, the red wire of the lockout will always be attached to whatever
wire the red probe was on when a positive reading was obtained.
NOTES:
For pairs of doors, wire the additional SuperScans the same as shown above.
For the inhibit function, operator mounted auxiliary switches may be used dry contacts only.
Bodyguard must be programmed to a relay value of 2.
NOTE: Bodyguard MUST be programmed
to a Relay Output value of 2. Default is 1.
75.5079.09 LO-21P 20130325 Page 5 of 13
SET-UP
INSTRUCTIONS
SETUP
INSTRUCTION
Cont.
Upon completion of all wiring, proceed with the set-up as follows:
1. Insure that the On-Off-Hold Open switch is in the ON position, and insure that the door control is powered and
operating normally.
2. Power the Bodyguard sensor and, using a BEA Remote Control, unlock the sensor and change the
Output Configuration to a value of 2. If necessary, refer to the Bodyguard User’s Guide for programming
instruction.
3. Power the LO-21P on with 12-24 VAC/VDC, and insure all sensors or other devices in the application are
properly powered
4. Observe the green LED on the Bodyguard upon powering. With the door in the closed position, the green LED
should begin blinking, then expire approximately 5 seconds thereafter to indicate a successful set-up for the
closed-door position.
5. Activate the door to the open position, the Bodyguard should once again begin flashing green, then expire
approximately 5 seconds thereafter to indicate a successful set-up for the open-door position. If the door goes
into safety swing as soon as it starts to close and you have a time delay set for the length of the closing cycle,
reverse the black and red wires to the motor input for DC units. Correct any faults before proceeding.
To perform a quick test by remote control to check motor wire polarity, perform the
following:
Place On-Off-Hold switch in the ON or AUTO position.
Activate the door and immediately walk into the Bodyguard detection pattern while
door is open. Door should be holding open at this point. Make sure there is no Eagle
activation during this time.
Unlock the Bodyguard and press Magic Wand + 2. Green LED will begin flashing If
door closes while flashing green, check for correct polarity at the red and black wire
from lockout.
6. Once the Bodyguard has learned the open and closed door positions, observe the green and red LED’s on the
LO-21P. Walk in and out of the field of detection for the Bodyguard while the door is open, and then again when
it is closed. The LED’s indicate the following:
GREEN LED: The green LED, when illuminated, indicates that there is detection at the
Bodyguard while the door is in the open position.
If someone steps into the Bodyguard detection zone when the door is open, the LO-21P’s
Green LED will illuminate to indicate that the Bodyguard will be connected to the activation
circuitry of the door, thus holding the door open as long as there is detection.
Green LED will also illuminate when the activating device (Eagle) is triggered, or when On-Off-
Hold Open switch is placed to the Hold Open position.
RED LED: The red LED, when illuminated, indicates that there is detection at the Bodyguard
while the door is in the closed position. It may also indicate that there is an activation signal
from the Eagle or the Hold Open switch.
When the door is closed, and someone steps into the detection zone of the Bodyguard, the red
LED on the LO-21P will illuminate, indicating that it will ignore any activation signal it receives.
Therefore, the door will remain closed until the Bodyguard detection zone is clear. Once the
Bodyguard zone is clear and the door has been activated it will open and remain open for the
hold time set by the motion sensor and/or door control, and will also hold open during detection
at Bodyguard.
CLOSED DOOR
OPEN DOOR
CLOSING DOOR
0 Volts DC
9 to 12 Volts DC
8 Volts DC
If the Bodyguard learns a “door closed” position, but does not execute a set-up for the
“open door position”, place the door to a hold open position. With a BEA remote control,
unlock the Bodyguard, and with the door in the open position, press the Magic Wand key
and then the number 2 the Bodyguard should begin flashing green to signify a set-up. If
it does not, this will be a quick indication that the improper data is being sent for the
“open door” position. Check to insure that data exists on the data lines leading into the
Bodyguard. In the full open position, voltage should be approximately 9 to 12 volts DC. If
it is not, check the data lines (White wire on terminal 6 and Red/White wire on terminal 7)
for correct voltage (see chart).
STOP
2
+
75.5079.09 LO-21P 20130325 Page 6 of 13
DIPSWITCH
6, 7 and 8
OPERATION
7. Adjustment is necessary to configure the dipswitches to obtain the correct lock out time delay. To set the
dipswitches( 1 through 5) for lock out time, perform the following:
Activate the door to the open position.
Time the overall door closing cycle
Configure the dip switches according to the chart on Page 4 for the lockout time that is required
Activate the door again to the open position
Stand outside of the Bodyguard detection pattern, and while the door is closing, observe the red LED on the
Bodyguard
The red LED on the Bodyguard should NOT illuminate during the closing cycle. If it does, it is probably
seeing the door at the very last degree or two of door closing, which would indicate that the lock out time
needs to be slightly increased.
Reconfigure the dipswitches to add 1 second of lock out time.
When the lock out time is correct. The red LED will not illuminate during the entire closing cycle of the door.
8. The last test is to insure that the Bodyguard detects an object as soon as the door has stopped closing.
Simply allow the doors to begin closing, and step in behind the doors, into the Bodyguards field of
detection. The red LED shall illuminate and remain on at the Bodyguard, and at the LO-21P, as soon as
the door reaches the fully closed position, provided that an object remains in the Bodyguard’s detection
field.
9. Set the dipswitches according to the chart below to achieve the desired lockout time. The total lockout time
is the sum total of the dipswitches that are in the ON position. For easy reference, use the timetables
below. Default time is 7 seconds (times are approximate).
Dipswitch 6 Position
Description of Performance
ON (Default)
The LO21P expects to see voltage coming in at the red and black wire while the
door is in the Open position. Typical for DC motors.
OFF
The LO21P expects to see voltage coming in at the red and black wire while the
door is in the Closed position.
Dipswitch 7 and 8
Position
Description of Performance
7 OFF / 8 ON (Default)
The LO21P CLOSES the Safety circuit (yellow wire) upon a Bodyguard
Detection during the door closed position
7 ON / 8 OFF
The LO21P OPENS the Safety circuit (yellow wire) upon a Bodyguard
Detection during the door closed position
Dipswitch #
Time Delay (seconds)
1
1
2
2
3
4
4
8
5
16
Time
Delay
(sec)
dip 1
1 sec
dip 2
2 sec
dip 3
4 sec
dip 4
8 sec
dip 5
16 sec
Time
Delay
(sec)
dip 1
1 sec
dip 2
2 sec
dip 3
4 sec
dip 4
8 sec
dip 5
16 sec
1
on
off
off
off
off
17
on
off
off
off
on
2
off
on
off
off
off
18
off
on
off
off
on
3
on
on
off
off
off
19
on
on
off
off
on
4
off
off
on
off
off
20
off
off
on
off
on
5
on
off
on
off
off
21
on
off
on
off
on
6
off
on
on
off
off
22
off
on
on
off
on
7
on
on
on
off
off
23
on
on
on
off
on
8
off
off
off
on
off
24
off
off
off
on
on
9
on
off
off
on
off
25
on
off
off
on
on
10
off
on
off
on
off
26
off
on
off
on
on
11
on
on
off
on
off
27
on
on
off
on
on
12
off
off
on
on
off
28
off
off
on
on
on
13
on
off
on
on
off
29
on
off
on
on
on
14
off
on
on
on
off
30
off
on
on
on
on
15
on
on
on
on
off
31
on
on
on
on
on
16
off
off
off
off
on
75.5079.09 LO-21P 20130325 Page 7 of 13
COMPANY
CONTACT
TROUBLE-
SHOOTING
PROBLEM
PROBABLE CAUSE
CORRECTIVE ACTION
Door will not open
all LED’s are
OFF at the LO21P
1. Faulty door control
2. Faulty LO21P
3. Faulty On-Off-Hold
Open switch
4. Faulty Eagle
5. Faulty wiring
1. Insure input power is good at LO21P orange and
brown wires. Should be 12 to 24 volts AC or DC.
2. Go directly to door control and jumper common and
activation input. If door opens, proceed to next step. If
not, replace/repair faulty door control.
3. Go to LO21P and jumper the red/white striped wire to
the black/white striped wire. Green LED on LO21P
should come on, and door should open. If not, replace
LO21P. If LED comes on, but door does not open, check
to insure that the blue and green wires are connected to
the door control properly.
4. Check to insure that On-Off-Hold Open switch is
functioning properly.
5. Check Eagle sensor for proper operation. Jumper
common and N.O. terminals while wires are attached. If
door does not open, check wiring between Eagle and
LO21P.
Door will not open
red LED is ON at
LO21P
1. Bodyguard is in detection
2. Bodyguard not
programmed properly
3. Faulty wiring between
Bodyguard and LO21P
1. Launch a setup on Bodyguard
2. Insure Bodyguard relay output is programmed to a
value of 2. Default is 1.
3. When Bodyguard is in detection, an open circuit
occurs at the purple and gray wires on the LO21P.
Thus if there is any break in wiring between purple
and gray and the LO21P, the lockout will react the
same as if the Bodyguard were in detection. Insure
there are no breaks in the wiring.
Door will not close
1. On-Off-Hold Open switch
is in Hold Open position
2. Bodyguard is in detection
3. Faulty door control
1. Place switch in On or Auto position
2. Launch a setup at Bodyguard
3. Remove wire from common and activate terminal at
door control, if door does not close, replace/repair
faulty control.
Bodyguard keeps re-
learning with each door
position
1. Incorrect data polarity at
Bodyguard
2. Insufficient voltage
switching at red and
black wire of LO21P
1. Insure that the white wire goes to terminal 6 of the
Bodyguard, and the red/white striped wire goes to
terminal 7 of the Bodyguard
2. When door is closed, there should be 0 volts
observed on the red and black wires of the LO21P.
When the door is open, voltage should be greater
than approximately 9 volts. If voltage is not great
enough at red and black wires when door is open,
the LO21P will not be able to send the correct data
to the Bodyguard. Remember, polarity must also be
correct. The red wire must ALWAYS connect to the
positive wire of the motor, as observed during door
open position. See important note on page 2.
As the door is closing,
the Bodyguard, upon
seeing the closing door,
seems to reactivate the
door to the open
position
1. Dipswitch 6 at LO21P is
in wrong position
1. Place dipswitch 6 in opposite position and re-test the
door
IMPORTANT NOTE: When experiencing sensor system problems, it is recommended to disable the main power
supply as to fully disable the system, until necessary repairs can be made.
Do not leave problems unresolved. If a satisfactory solution cannot be achieved after troubleshooting a problem, please call B.E.A.,
Inc. If you must wait for the following workday to call B.E.A., leave the door inoperable until satisfactory repairs can be made. Never
sacrifice the safe operation of the automatic door or gate for an incomplete solution.
The following numbers can be called 24 hours a day, 7 days a week. For more information, visit www.beasensors.com.
West:
1-888-419-2564
Mid-West:
1-888-308-8843
South-East:
1-800-407-4545
North-East:
1-866-836-1863
US and Canada:
1-866-249-7937
Canada:
1-866-836-1863
75.5079.09 LO-21P 20130325 Page 8 of 13
BODYGUARD
DK-12
DATA + 7
DATA - 6
N.C. 5
N.O. 4
COM 3
POWER 2
POWER 1
5 N/C
4 N/O
3 COM
2 PWR
1 PWR
24 V
TRANSFORMER
115 VAC
SIZE:
SHEET:SCALE:
A
PH: (412) 249-4100 FAX: (412) 249-4101
B.E.A., Inc.
100 Enterprise Drive Pittsburgh, PA 15275
DATE:
www.beasensors.com
CAGE CODE: DWG NO: FILE OF: DRAWN BY: REV:
1 OF 1
NTS
Tech Support
TITLE: BESAM 300/400 (ETIK2) WITH LO-21P
PARALLAX II SYSTEM Q-DISCONNECT
ON APPROACH SIDE
6 JUNE 2003
GDM
B
80.0185
WHITE
BLACK
RED
8 POWER
7 POWER
6 COM
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 POWER
7 POWER
6 COM
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 POWER
7 POWER
6 COM
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 POWER
7 POWER
6 COM
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
BLACK
RED
LO-21P
RED/WHITE
WHITE
GRAY
BLUE
BESAM ETIK
CONTROL
HS LS HD
BLACK
WHITE
17 STALL INPUT
18 STALL INPUT
15 STALL INPUT
16 STALL INPUT
13 ACTIVATION
12 COMMON
11 SAFETY
10 COMMON
Common
N/O
N/C
Motor Voltage (See Note #6)
LEFT APPROACH SIDE LEFT SAFETY SIDE
RIGHT SAFETY SIDE RIGHT APPROACH SIDE
BROWN
WHITE
BROWN
RED
GREEN
BLACK
RED +
BLACK --
BLUE
RED
BLACK
GREEN
BLUE
EAGLE
NOT USED
NOT USEDNOT USED
NOT USED
NOTE:
1.) REMOVE FROM PIN 6 AND PLACE A WIRE NUT ON THE
APPROACH SIDE SUPERSCAN'S 2 WHITE WIRES.
INSTALL THE BLUE WIRE INTO PIN 6.
2.) ON SAFETY SIDE SUPERSCANS MOVE BROWN WIRE
FROM PIN 5 TO PIN 4.
3.) B-SWITCH SHOULD CLOSE AT APPROX.
65-70 DEGREES.
4.) INSTALL A JUMPER BETWEEN PINS 17&18
5.) THE BODYGUARD RELAY OUTPUT FUNCTION
MUST BE CHANGED TO #2.
6.) RH MOTOR SHOWN, REVERSE LO-21P RED
AND BLACK WIRES FOR LH MOTOR.
OFF
AUTO
HOLD
OPEN
SUPERSCAN QUICK
DISCONNECT CABLE
SUPERSCAN QUICK
DISCONNECT CABLE
BROWN
ORANGE
Wire nut
(See Note #1)
(See Note #1)
(See Note #5)
(See Note #2)
(See Note #2)
(See Note #4)
B-SWITCH
(See Note #3)
VIOLET
BLACK / WHITE
GREEN
YELLOW
75.5079.09 LO-21P 20130325 Page 9 of 13
BODYGUARD
DK-12
DATA + 7
DATA - 6
N.C. 5
N.O. 4
COM 3
POWER 2
POWER 1
5 N/C
4 N/O
3 COM
2 PWR
1 PWR
24 V
TRANSFORMER
115 VAC
HOLD
OPEN
OFF
SIZE:
SHEET:SCALE:
A
PH: (412) 249-4100 FAX: (412) 249-4101
B.E.A., Inc.
100 Enterprise Drive Pittsburgh, PA 15275
DATE:
www.beasensors.com
CAGE CODE: DWG NO: FILE OF: DRAWN BY: REV:
1 OF 1
NTS
Tech Support
TITLE: BESAM 300/400 (ETIK2) WITH LO-21P
PARALLAX II SYSTEM Q-DISCONNECT
ON SAFETY SIDE
6 JUNE 2003
GDM
B
AUTO
80.0186
BLACK
BROWN
WHITE
BLACK
RED
GREEN
BLACK
RED
BROWN
8 POWER
7 POWER
6 COM
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 POWER
7 POWER
6 COM
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 POWER
7 POWER
6 COM
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 POWER
7 POWER
6 COM
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
BLACK
WHITE
GREEN
RED
LO-21P
RED/WHITE
WHITE
BLUE
BESAM ETIK
CONTROL
HS LS HD
BLACK
WHITE
17 STALL INPUT
18 STALL INPUT
15 STALL INPUT
16 STALL INPUT
13 ACTIVATION
12 COMMON
11 SAFETY
10 COMMON
Common
N/O
N/C
Motor Voltage (See Note #6)
LEFT APPROACH SIDE LEFT SAFETY SIDE
RIGHT SAFETY SIDE RIGHT APPROACH SIDE
EAGLE
RED +
BLACK --
YELLOW
YELLOW
RED
NOT USED
NOT USED
NOT USED
NOT USED
SUPERSCAN QUICK
DISCONNECT CABLE
SUPERSCAN QUICK
DISCONNECT CABLE
Wire nut
BROWN
ORANGE
NOTE:
1.) REMOVE FROM PIN 6 AND PLACE A WIRE NUT ON THE
APPROACH SIDE SUPERSCAN'S WHITE WIRE.
INSTALL THE YELLOW WIRE INTO PIN 6.
2.) ON SAFETY SIDE SUPERSCAN MOVE GREEN WIRE
FROM PIN 5 TO PIN 4.
3.) B-SWITCH SHOULD CLOSE AT APPROX.
65-75 DEGREES.
4.) INSTALL A JUMPER BETWEEN PINS 17&18
5.) THE BODYGUARD RELAY OUTPUT FUNCTION
MUST BE CHANGED TO #2.
6.) RH MOTOR SHOWN, REVERSE LO-21P RED
AND BLACK WIRES FOR LH MOTOR.
(See Note #5)
(See Note #1)
(See Note #2)
(See Note #2)
(See Note #1)
(See Note #4)
B-SWITCH
(See Note #3)
YELLOW
VIOLET
GRAY
BLACK / WHITE
YELLOW
GREEN
75.5079.09 LO-21P 20130325 Page 10 of 13
BODYGUARD
DK-12
DATA + 7
DATA - 6
N.C. 5
N.O . 4
COM 3
PO WER 2
PO WER 1
5 N/C
4 N/O
3 COM
2 PW R
1 PW R
24 V
TRANS FO RMER
115 VAC
SIZ E:
SHE E T:SCA LE :
A
PH: (412) 249-4100 FAX: (412) 249-4101
B.E.A., Inc.
100 Enterprise Drive Pittsburgh, PA 15275
DAT E:
www.beasensors.com
CAG E CO DE: DWG NO : F ILE OF : DRA WN BY : REV :
1 O F 1NTS
TITLE: STANLEY MP CONTROL W ITH LO-21P
PARALLAX II SYSTEM Q-DISCONNECT
ON APPROACH SIDE
6 JUNE 2003
GDM
B
80.0187
RED
BLACK
WHITE
BLACK
RED
8 PO WER
7 PO WER
6 CO M
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 PO WER
7 PO WER
6 CO M
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 PO WER
7 PO WER
6 CO M
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 PO WER
7 PO WER
6 CO M
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
BLACK
RED
LO-21P
VIOLE T
BLUE
LEFT APPROAC H SIDE LEFT SAFETY SIDE
RIGHT SAFETY SID E RIGHT APPROAC H SIDE
WHITE
RED
GREEN
BLACK
1 COMMON
2 OPERATE
3 SENSOR OP
4 12 VAC
5 12 VAC
6 AUX INPUT
7 SAFETY/STALL
8 COMMON
STANLEY MP
CONTROL
STALL
TORQUE
Comm on
N/O
N/C
SWITCH (See Note #2)
WHITE
BLACK
Motor Voltage (See Note #4)
SUP E RS CAN Q UICK
DIS CO NNECT CA B LE
SUP E RS CAN Q UICK
DIS CO NNECT CA B LE
BROWN
BROWN
BLUE
BLUE
GREEN
EAGLE
ORANGE
VIOLET
Tech Support
NOT USED NOT USED NOT USED NOT USED
BLACK --
RED +
NOTE:
1.) REMOVE FRO M PIN 6 AND PLACE A WIRE NUT O N THE
APPROACH SIDE SUPERSCAN'S 2 WHITE WIRES.
INSTALL THE BLUE WIRE INTO PIN 6.
2.) MAGIC FORCE AUX. SWITCH #4 SHOULD OPEN AT
APPROX. 65-70 DEG REES. FO R MAGIC SWING REFER TO
INHIBIT SWITCH BEA PT# 10 SSINHL O R 10SSINHR.
3.) THE BODYGUARD RELAY O UTPUT FUNCTION
MUST BE CHANGED TO #2.
4.) SHO WN LH,RH MAG IC SWING AND RH MAGIC FO RCE
FO R LH MAGIC FO RCE REVERSE RED AND BLACK WIRES.
5.) DO OR CONTROL SW2 SWITCH BANK SET DIPSWITCH #1
TO THE OFF (TIMER) PO SITION.
HOLD
OPEN
OFF
AUTO
(See Note #3)
(See Note #5)
(See Note #1)
(See Note #1)
RED/WHIT E
BRO W N
O RANG E
WHITE
GRA Y
BLACK / WHITE
GRE EN
YELLOW
YELLOW
75.5079.09 LO-21P 20130325 Page 11 of 13
BODYGUARD
DK-12
DATA + 7
DATA - 6
N.C. 5
N.O . 4
CO M 3
PO WER 2
PO WER 1
5 N/C
4 N/O
3 COM
2 PWR
1 PWR
24 V
TRANSFO RMER
115 VAC
SIZ E:
SHE E T:SCA LE :
A
PH: (412) 249-4100 FAX: (412) 249-4101
B.E.A., Inc.
100 Enterprise Drive Pittsburgh, PA 15275
DATE:
www.beasensors.com
CAG E CO DE: DW G NO : F ILE OF : DRA WN BY : REV:
1 O F 1
NTS
6 JUNE 2003
GDM
B
80.0188
RED
BLACK
BROWN
WHITE
BLACK
RED
BLACK
RED
BROWN
8 PO WER
7 PO WER
6 CO M
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 PO WER
7 PO WER
6 CO M
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 PO WER
7 PO WER
6 CO M
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 PO WER
7 PO WER
6 CO M
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
BLACK
WHITE
RED
LO-21P
BRO W N
O RANG E
RED/W HIT E
WHITE
BLUE
1 COMMON
2 OPERATE
3 SENSOR OP
4 12 VAC
5 12 VAC
6 AUX INPUT
7 SAFETY/STALL
8 COMMON
STANLEY MP
CONTROL
STALL
TORQUE
Comm on
N/O
N/C
SWITCH (See Note #2)
WHITE
BLACK
Motor Voltage (See Note #4)
TITLE: STANLEY MP CONTROL W ITH LO-21P
PARALLAX II SYSTEM Q-DISCONNECT
ON SAFETY SIDE
GREEN
GREEN
SUP E RSCAN Q UICK
DIS CO NNE CT CA B LE
YELLOW
VIOLET
OFF
AUTO
YELLOW
YELLOW
SUP E RSCAN Q UICK
DIS CO NNE CT CA B LE
Tech Support
EAGLE
NOT USED
NOT USED
NOT USED
NOT USED
NOTE:
1.) REMOVE FROM PIN 6 AND PLACE A WIRE NUT O N THE
APPROACH SIDE SUPERSCAN'S WHITE WIRE.
INSTALL THE YELLOW WIRE INTO PIN 6.
2.) MAGIC FO RCE AUX. SWITCH #4 SHO ULD OPEN AT
APPROX. 65-70 DEG REES. FO R MAGIC SWING REFER TO
INHIBIT SWITCH BEA PT# 10 SSINHL O R 10SSINHR.
3.) THE BODYG UARD RELAY OUTPUT FUNCTION
MUST BE CHANGED TO #2.
4.) SHOWN LH,RH MAGIC SWING AND RH MAG IC FORCE
FOR LH MAG IC FORCE REVERSE RED AND BLACK WIRES.
5.) DOOR CONTROL SW2 SWITCH BANK SET DIPSWITCH #1
TO THE OFF (TIMER) POSITION.
RED +
BLACK --
HOLD
OPEN
(See Note #5)
LEFT APPR OAC H SIDE
LEFT SAFETY SID E
RIGHT SAFETY SID E RIGHT APPR OAC H SIDE
(See Note #1)
(See Note #1)
(See Note #3)
ORANGE
GRA Y
VIOLE T
BLACK / WHITE
GRE E N
YELLOW
75.5079.09 LO-21P 20130325 Page 12 of 13
BODYGUARD
DK-12
DATA + 7
DATA - 6
N.C. 5
N.O . 4
COM 3
PO WER 2
PO WER 1
5 N/C
4 N/O
3 COM
2 PW R
1 PW R
SIZ E:
SHE E T:
SCA LE :
A
PH: (412) 249-4100 FAX: (412) 249-4101
B.E.A., Inc.
100 Enterprise Drive Pittsburgh, PA 15275
DAT E:
www.beasensors.com
CAG E CO DE:
DW G NO :
F ILE OF :
DRA WN BY : REV :
1 O F 1
NTS
6 JUNE 2003
GDM
A
80.0193
RED
BLACK
WHITE
BLACK
RED
8 PO WER
7 PO WER
6 CO M
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 PO WER
7 PO WER
6 CO M
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 PO WER
7 PO WER
6 CO M
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 PO WER
7 PO WER
6 CO M
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
BLACK
RED
LO-21P
GRA Y
LEFT APPROACH SIDE
LEFT SAFETY SID E
RIGHT SAFETY SID E
WHITE
RED
GREEN
BLACK
BROWN
BROWN
BLUE
BLUE
GREEN
EAGLE
HOLD OPEN
OFF
AUTO
Tech Support
NOT USED
NOT USED
NOT USED
NOT USED
BLACK --
RED +
18 -24 VDC
17 +24 VDC
19 +18 VDC
14 SW ITCH 2
13 SW ITCH 1
12 SYNC
11 0 VDC
10 SYNC
8 OFF
9 MAT
5 P DET
4 COM
3 I IMP
CUP
SLAVE
CUP
MASTER
14 SW ITCH 2
18 -24 VDC
17 +24 VDC
19 +18 VDC
13 SW ITCH 1
SYNC 12
0 VDC 11
SYNC 10
OFF 8
MAT 9
5 P DET
4 COM
3 I IMP
NOTE:
1.) REMOVE FROM PIN 6 AND PLACE A WIRE NUT ON THE
APPROACH SIDE SUPERSCAN'S 2 WHITE WIRES.
INSTALL THE BLUE WIRE INTO PIN 6.
2.) THE BODYG UARD RELAY OUTPUT FUNCTION
MUST BE CHANGED TO #2.
3.) DO NOT PO WER ALL THE SENSO RS FROM O NE
CONTROL BOX .
4.) ON BOTH CO NTRO LS SET PMD FUNCTIO NS
20=b, 19=b, 18=00, 17=00, 14=a, 13=a, 12=65
DEGREES, 11= 5 DEGREES LESS THAN F10
5.) INHIBITING THE SAFETY SIDE SUPERSCAN (F12)
SHOULD OCCUR AT APPROX. 65-75 DEGREES.
SY NC CABLE
SUPERSCAN QUICK
DISCONNECT CAB LE
SUPERSCAN QUICK
DISCONNECT CAB LE
TITLE: BESAM CUP VER. 6.3,6.4 CONTROL
WITH LO-21P PARALLAX II SYSTEM
Q-DISCONNECT ON APPROACH SIDE
+ B RO W N
- O RANG E
WHITE
RED/WHIT E
(See Note #1)
(See Note #1)
(See Note #2)
RIGHT APPROACH SIDE
BLUE
VIOLE T
BLACK / WHITE
GRE EN
YELLOW
75.5079.09 LO-21P 20130325 Page 13 of 13
BODYGUARD
DK-12
DATA + 7
DATA - 6
N.C. 5
N.O . 4
COM 3
PO WER 2
PO WER 1
5 N/C
4 N/O
3 COM
2 PW R
1 PW R
SIZ E:
SHE E T:SCA LE :
A
PH: (412) 249-4100 FAX: (412) 249-4101
B.E.A., Inc.
100 Enterprise Drive Pittsburgh, PA 15275
DAT E:
www.beasensors.com
CAG E CO DE: DWG NO : F ILE O F : DRA WN BY : REV:
1 O F 1NTS
TITLE: BESAM CUP VER. 6.3,6.4 CONTROL
WITH LO-21P PARALLAX II SYSTEM
Q-DISCONNECT ON SAFETY SIDE
22 SEPT 2003
JED
B
80.0194
RED
BLACK
WHITE
BLACK
RED
8 PO WER
7 PO WER
6 CO M
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 PO WER
7 PO WER
6 CO M
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 PO WER
7 PO WER
6 CO M
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
8 PO WER
7 PO WER
6 CO M
5 N.O.
4 N.C.
3 INHIBIT +
2 INHIBIT GND
1 BLANK
BLACK
RED
LO-21P
WHITE
GRA Y
VIOLE T
BLACK / WHITE
LEFT APPROACH SIDE LEFT SAFETY SID E
RIGHT SAFETY SIDE RIGHT APPR OAC H SIDE
WHITE
RED
BROWN
BLACK
GREEN
GREEN
YELLOW
YELLOW
BROWN
EAGLE
HOLD OPEN
OFF
AUTO
Tech Support
NOT USED NOT USED NOT USED NOT USED
BLACK --
RED +
18 -24 VDC
17 +24 VDC
19 +18 VDC
14 SW ITCH 2
13 SW ITCH 1
12 SYNC
11 0 VDC
10 SYNC
8 OFF
9 MAT
5 P DET
4 COM
3 I IMP
CUP
SLAVE
CUP
MASTER
14 SW ITCH 2
18 -24 VDC
17 +24 VDC
19 +18 VDC
13 SW ITCH 1
SYNC 12
0 VDC 11
SYNC 10
OFF 8
9 MAT LOGIC
5 P DET
4 COM
3 I IMP
NOTE:
1.) REMOVE FROM PIN 6 AND PLACE A WIRE NUT ON THE
APPROACH SIDE SUPERSCAN'S WHITE WIRE.
INSTALL THE YELLOW WIRE INTO PIN 6.
2.) THE BODYG UARD RELAY OUTPUT FUNCTION
MUST BE CHANG ED TO #2.
3.) DO NOT PO WER ALL THE SENSO RS FROM O NE
CONTROL BOX .
4.) ON BOTH CO NTROLS SET PMD FUNCTIO NS
20=b, 19=b, 18=00, 17=00, 14=a, 13=a, 12=65
DEGREES, 11= 5 DEGREES LESS THAN F10
5.) INHIBITING THE SAFETY SIDE SUPERSCAN (F12)
SHOULD OCCUR AT APPROX. 65-75 DEGREES.
SY NC CABLE
RED/WHIT E
SUPERSCAN QUICK
DISCONNECT CABLE
SUPERSCAN QUICK
DISCONNECT CABLE
(See Note #2)
(See Note #1)
(See Note #1)
GRE EN
BLUE
- O RANG E
+ B RO W N
YELLOW
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13

BEA LO21 User guide

Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI