Harman Stove Company PF 100 User manual

  • Hello! I am an AI chatbot trained to assist you with the Harman Stove Company PF 100 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
R4
SAFETY NOTICE
PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND USE YOUR NEW ROOM HEATER. FAILURE TO
FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJURY, OR EVEN DEATH.
FOR USE IN THE U.S. AND CANADA. SUITABLE FOR INSTALLATION IN MOBILE HOMES
IF THIS HARMAN PELLET FURNACE IS NOT PROPERLY INSTALLED, A HOUSE FIRE MAY RESULT. FOR YOUR
SAFETY, FOLLOW INSTALLATION DIRECTIONS.
CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION
REQUIREMENTS IN YOUR AREA.
CONTACT YOUR LOCAL AUTHORITY (SUCH AS MUNICIPAL BUILDING DEPARTMENT, FIRE DEPARTMENT, FIRE
PREVENTION BUREAU, ETC.) TO DETERMINE THE NEED FOR A PERMIT.
CETTE GUIDE D'UTILISATION EST DISPONIBLE EN FRANCAIS. CHEZ VOTRE CONCESSIONNAIRE DE HARMAN STOVE
COMPANY.
SAVE THESE INSTRUCTIONS.
The Harman PF 100 Pellet Pro Furnace
Installation & Operating Manual
“Ce manuel est disponible en Français sur demande”
R7
2
PF100
Combustion
Blower
Combustion
Blower cover
Fan Control
Hopper Lid
Latches
Control Cover
3 Speed Switch
Viewing Glass
Outer Door
Vent Pipe
Heat Exchanger
Shaker Handle
Outer Door Latches
Filter Box
Hopper
PF100 Parts
3PF100
Assembly 4
Venting 10
Installation 15
Operation 21
Maintenance 29
Troubleshooting 34
Feeder Parts 35
Specifications 36
Wiring Diagram 37
Parts List & Options 38
Warranty 39
Testing Label 40
Quick Reference Start-Up 41
Please read this entire manual before you install and use your new
furnace. Failure to follow instructions may result in
property damage, bodily injury, or even death.
SAVE THESE INSTRUCTIONS
Harman Stove Company
352 Mountain House Road
Halifax, PA 17032
Table of Contents
DO NOT INSTALL IN A MOBILE HOME.
4
PF100
Venting
Use 4” pellet vent pipe to vent your PF 100.
A combustion blower is used to extract the com-
bustion gases from the firebox. This creates a negative
pressure in the firebox and a positive pressure in the
venting system as shown in fig. 2. The longer the vent
pipe and more elbows used in the system, the greater
the flow resistance. Because of these facts we recom-
mend using as few elbows as possible and 30 feet or
less of vent pipe. The maximum horizontal run should
not exceed 18 feet.
Be sure to use wall and ceiling pass through
fittings (which are approved for pellet vent pipe )
when going through combustible materials. Be sure
to use a starting collar to attach the venting system to the
stove. The starting collar must be sealed to the
stove flue collar with high temp silicone caulking
or aluminum tape, and screwed into the stove flue
collar at least three (3) places.
Vent Pipe
4” pellet venting pipe ( also known as PL vent ) is
constructed of two layers with air space between the
layers. This air space acts as an insulator and reduces
the outside surface temperature to allow a clearance to
combustibles of only 2 inches. This 2 inch clearance is
also approved by the pipe manufacturers. See images
on left. See page 14 (Fig. 24 and 26) for larger images.
The sections of pipe lock together to form an air
tight seal in most cases; however, in some cases a per-
fect seal is not achieved. For this reason and the fact
that the PF100 operates with a positive vent pressure,
we specify that all joints within the structure should
also be sealed with clear silicone.
Fig. 1
Fig. 2
Clearances and Venting
The shaded areas are the clear-
ances for the PL vent pipe that must
be maintained at 3”. After the vent-
ing leaves the shaded area it may be
installed at 2 to combustibles.
(Only UL listed wall pass-throughs
and fire stops must be used.)
See NOTES:
on page 12
NOTE:Use only 4” diameter type “L” or “PL”
venting system. Be sure to inspect and clean
exhaust venting system frequently.
The first thing that needs to be done is deciding
where and how the furnace will be installed.
Things that need to be taken into consideration are
VENTING, SUPPLY& RETURN DUCTING, ELEC-
TRICAL, and Condensation drainage (if A/C is in-
stalled). Don’t forget access to the furnace for service.
When the return air inlet position is known the filter
box and distribution blower can be installed. See pages
5, 6, 7, 8.
When the furnace is set into place venting can be
done.
Design
Assembly
5PF100
Filter Box
(Cold Air Return)
This Edge Toward
Furnace
Assembling Filter Box
The cold air return filter box can be assembled
with the filter frame on either side or the back, pro-
vided there is access to the combustion blower and flue
area.
It is not recomended that the filter frame be installed
on the same side as the ash door due to the need to
access the combustion blower, filter, and flue pipe for
service.
1. Place the bottom on the floor. The edge closest
to the knockouts will be the edge towards the furnace.
See Fig. 4.
2. Place the desired vertical panel inside the bot-
tom tray and hold into place with one Tek screw in the
bottom middle hole. (solid panel shown) See Fig 4.
Bottom
Solid Side Panel
Fig. 4
Knockouts
Tek screw from outside
Bottom (same as
top)
Top (same as bottom)
Filter Frame Panel
Solid Side Panel
Blower access Panel
Blower access
Panel Cover
Fig. 3
Switch
NOTE:Read and follow all of the vent pipe
manufacturers instructions on the proper
installation and support of the vent pipe. Adhere to
all clearances.
Assembly
6
PF100
3. Place the filter frame panel inside the bottom
and inside the solid panel corner. See Fig. 6 for corner
detail. Make sure that the filter opening is up.See Fig. 5
Hold the filter panel to the solid panel with a Tek screw
in the middle hole of the solid panel, and one in the bot-
tom middle hole under the filter opening.
NOTE: Do not put any screws into any of the top
holes at this time.
4. Place the remaining panel, (in this case the
blower access panel) in the bottom panel and into the
corner of the solid panel. See Fig. 7. Make sure that the
panel is in the upright position. There are no cover mount-
ing holes in the bottom edge of this panel. Hold the panel
into place with one Tek screw in the middle hole of the
solid panel and one in the bottom middle hole of the
blower access panel.
Fig. 5
Fig. 6
Fig. 7
Filter Frame Panel
Open Side Panel
Assembling Filter Box, Cont’d
Filter opening must be up
Assembly
7PF100
Fig. 8
Fig. 9
Fig. 10
5. Place the top on the filter box as shown in figure 8. At
this time all Tek screws can be inserted around the filter
box.
Top
Access Panel
Cover opening
3 Speed Switch
Note: Except for the (6) screws that attach the
blower access panel in place. There should not be any
screws protruding from the box on the side toward the
furnace. Also DO NOT put a screw into the top center
of the filter panel as a screw in this location will interfere
with the filter access cover.
6. Pry out the two knockouts in the top of the box
and install the flex connector and the switch. See Fig. 9.
Note: Dont forget the HI-MED-LO switch label
on the switch before the locknut.Make sure that the set-
screw on the flex connector is not pointing toward the
furnace end of the box when the locknut is fully
tightened.The filter box is now ready to install onto the
furnace.
Follow the Blower mounting instructions on page
8 before continuing to step #7.
Note: The blower should be mounted on the fur-
nace before the filter box for ease of distribution blower
installation.
Note: It is best to wait until the blower , filter box,
and cold air return duct work is installed before install-
ing the filter and side panel.
7. After the Filter Box is installed on the furnace
the electrical wiring to the three speed switch needs to
be completed. WHITE to WHITE, VIOLET to the
center terminal of the switch, and the BLACK, RED,
BLUE to the terminals shown.
Note: The optional 1500 CFM blower is a single
speed blower, therefore the three speed switch will not
be used. The optional 2000CFM blower is a 4 speed,
only hook up the three colors shown and tape off the
orange wire. See Fig. 10.
8. Install the access panel cover by hooking the lip
at the bottom of the cover over the edge in the filter box.
Use 6 Tek screws to secure the access panel.
9. To install the filter, insert the filter into the filter
slot and slide completely into the frame. Take note to
the air flow arrow on the filter when installing.Slide the
filter access cover over the opening with the upright angle
toward the filter box. If a Tek was put into the middle
hole by mistake, remove the screw to allow the access
cover to fit properly.
Assembling Filter Box, Cont’d
Violet 120VAC
Yellow on 2000 CFM motor
Flex connector
Assembly
8
PF100
Mounting Screws
Fig. 11
Fig. 13
Fig. 14
Fig. 12
Blower Assembly
Install the blower mounting brackets on the blower
as shown in Fig. 11.
1. Install ( 4) Tek screws on each side where shown
in Fig. 11. Start with the two center screws.
NOTE: There are two small holes in the discharge
end of the blower that match the two center holes on the
small angle of the blower bracket. The two (2) outer
holes are drilled by theTek screws.
2. Mount blower with brackets installed on the
furnace as shown in Fig. 12. Each side will require 6
Tek screws.
NOTE: The furnace blower opening is made large
enough for the use of a 1500 or 2000 CFM blower.
The blower mounting brackets will fit either blower. The
inner hole pattern is for the 1000 CFM blower and the
outer pattern is for the 1500 or 2000 CFM blower.
NOTE: These Blower Motors are not designed to
be operated without any positive static back
pressure. OPERATION WITHOUT SUPPLY
DUCTWORK OR IN FREE AIR WILL CAUSE
MOTOR OVERLOAD AND PREMATURE
FAILURE.
3. Mount the filter box on the furnace with ( 8 )
10 x 3/4 Tek screws, 3 on each side. Visually locate
these holes so you are familiar with their location on the
filter box and the furnace. Access to the mounting holes
can be gained through the blower access panel cover
and the filter opening. See Fig. 14.
Note: Two pieces of 2x4 stacked laying flat on
the floor 12 inches from the blower opening will support
the filter box during installation.
CAUTION: Regardless of the supply air duct size
installed, the Distribution Blower Motor MUST be
checked for running Amperage. Check the motor name
plate for the full load AMPS. If the amperage is running
higher than that listed, a supply air restricting damper
may be required to increase the supply plenum positive
static pressure.
Assembly
9PF100
Firebrick
Firebrick installation-required
The firebrick is shipped in the ashpan. It will need
to be placed on the brick shelf as shown in Fig. 15. It
can be installed with either face to the fire. Hold the
brick longways and slide it down into the slot on the
shelf. There is a stop at the rear of the shelf to stop the
rearward travel.The brick just sits on the shelf in the
upright position.
Fig. 15
Fig. 17
Baffle installation
The upper heat exchanger baffle comes shipped
along side the ashpan. Remove the ashpan and the baffle.
This upper baffle needs to be installed before operating
the furnace.
The baffle has a long 45 degree bend on the bot-
tom of the firebox side. See Fig. 17.
The top has a 90 degree bend on the same side to
use as a handle.
On the opposite side there are four hooks that will
support the baffle.
On the front and rear of the firebox walls there are
brackets that these hooks fit into. See Fig. 16
Slide the upper baffle down on to the brackets,
while you hold the baffle against the heat exchanger. You
will notice that the upper baffle will hold the lower baffle
plate into position. See Fig.17.
Note how the upper and lower baffles are held
into position because they will need to be removed
during heat exchanger cleaning.
Fig. 16
Baffle support bracket
Upper heat
exchanger baffle
45
o
bend
Assembly
10
PF100
The minimum vent configuration is a 90
o
or Tee on
a starter collar and a 24” length horizontal through an
exterior wall. A cap or other bird screen on the end
should direct the flue gasses down and away from the
structure. See Fig. 18.
The maximum horizontal length is 18 feet. The mini-
mum termination height above the exterior grade is 18”.
The maximum total length of any configuration is 30 feet*.
* ( see venting graph on page 13 for exceptions )
NOTE: Cleanout Tee’s should always be used on
the transitions to horizontal pipe to allow easy access
for cleaning.
The venting gragh allows for (one) 90 deg. or Tee
fitting in any configuration.
If more 90’s, Ts, or 45s are needed the total length
must be adjusted to allow for the added restriction.
Up to four (4) additional 90s, Tees, or equivalent
45’s can be added as long as the overall length is ad-
justed in accordance with the values listed below.
( See the venting graph on page 12.)
Each Vertical ---- 90 deg. or T subtract 2.5 feet
Each Vertical ---- 45 deg. subtract 1.5 feet
Each Horizontal - 90 deg. or T subtract 5.0 feet
Each Horizontal - 45 deg. subtract 2.5 feet
Any exterior venting (vent pipe exposed to out-
side ambiant temperatures) should be kept to a
minimum, due to potential condensation problems.
This is especially important in high humidity cold
weather climates, such as maritime areas, lake shores,
and low river valleys.
4” Type “L” or
“PL” Vent pipe
This is the minimum venting configuration.
NOTE: This would only be allowed with non-
combustible walls.
Fig. 18
Venting
NOTE: All installation clearnaces and restrictions
must be adhered to.
NOTE: Read and follow all of the vent pipe
manufacturers instructions on the proper
installation and support of the vent pipe. Adhere to
all clearances.
Keep combustible materials such as grass, leaves, etc.
at least 3 feet away from the point directly under the
vent termination. (between the vent and the ground)
WARNING
KEEP COMBUSTIBLES AWAY
FROM FLUE OUTLET.
CAUTION
DO NOT INSTALL IN SLEEPING ROOM
WARNING
DO NOT INSTALL A FLUE DAMPER IN THE
EXHAUST VENTING SYSTEM OF THIS UNIT.
DO NOT CONNECT THIS UNIT TO A
CHIMNEY FLUE SERVING ANOTHER
APPLIANCE.
INSTALL VENT WALL PASS-THROUGHS AT
CLEARANCES SPECIFIED BY THE VENT
MANUFACTURER
INSTALLATION IS TO BE PERFORMED BY A
QUALIFIED INSTALLER.
NOTE: Use only 4” diameter type “L” or “PL
venting system. Be sure to inspect and clean
exhaust venting system frequently.
Venting
11PF100
Fig. 19
Venting Configuration Graph
Venting
12
PF100
Requirements for Terminating the Venting
WARNING: Venting terminals must not be recessed
into a wall or siding.
NOTE: Only PL vent pipe wall pass-throughs and
fire stops should be used when venting through com-
bustible materials.
NOTE: Always take into consideration the effect
the prevailing wind direction or other wind currents will
cause with flyash and /or smoke when placing the termi-
nation.
In addition, the following must be observed:
A. The clearance above grade must be a minimum
of 18".
1
B. The clearance to a window or door that may
be opened must be a minimum of 48" to the side, 48"
below the window/door, and 12" above the window/
door.
1
( with outside air installed, 18” )
C. A 12" clearance to a permanently closed win-
dow is recommended to prevent condensation on the
window.
D. The vertical clearance to a ventilated soffit lo-
cated above the terminal within a horizontal distance of
2 feet (60 cm) from the center-line of the terminal must
be a minimum of 18".
E. The clearance to an unventilated soffit must be
a minimum of 12".
F. The clearance to an outside corner is 11" from
center of pipe.
G. The clearance to an inside corner is 12".
H. A vent must not be installed within 3 feet (90
cm) above a gas meter/regulator assembly when mea-
sured from the horizontal center-line of the regulator.
1
I. The clearance to service regulator vent outlet
must be a minimum of 6 feet.
1
J. The clearance to a non-mechanical air supply
inlet to the building or the combustion air inlet to any
other appliance must be a minimum of 48”.
1
K. The clearance to a mechanical air supply inlet
must be a minimum of 10 feet.
1
(with outside air installed, 6 feet )
L. The clearance above a paved sidewalk or a
paved driveway located on public property must be a
minimum of 7 feet.
1,2
M. The clearance under a veranda, porch, deck
or balcony must be a minimum of 12 inches.
1,3
NOTE: The clearance to vegetation and other
exterior combustibles such as mulch is 36 as measured
from the center of the outlet or cap. This 36” radius
continues to grade or a minimum of 7 feet below the
outlet.
1
Certain Canadian and or Local codes or regula-
tions may require different clearances.
2
A vent shall not terminate directly above a side-
walk or paved driveway which is located between two
single family dwellings and serves both dwellings.
3
Only permitted if veranda, porch, deck, or bal-
cony is fully open on a minimum of 2 sides beneath the
floor.
V
A
= Vent terminal
= Air supply inlet
Fixed
Closed
Openable
Openable
Fixed
Closed
Inside
Corner
Detail
= Area where terminal is not permitted
Fig. 20
NOTE: Where passage through a wall, or partition
of combustible construction is desired, the
installation shall conform to CAN/CSA-B365. (if in
Canada)
Venting
13PF100
Clearances to combustibles
If installing the furnace in a room separated from the
remaining living spaces, the minimum size of the room must
be no smaller than 8’ x 8’. See Fig. 21. The reason for this
is heat build-up and required space for service and normal
operation.
This is the minimum size of the room even if it is built
of non-combustible material.
High and low air vents MUST be installed between
the room and the remaining living space. Each vent should
be at least 72 square inches in area. ( The vent size will
need to be increased if there is no return air ducting sys-
tem.)
The striped areas are the minimum clearances to com-
bustibles which is 36” from stove body, not hopper or
blower.
The shaded area indicates the required floor protec-
tion area. The PF100 requires 48” x 52” of floor protec-
tion centered around the skidplate footprint. Flooring should
be a minimum of 26 gauge sheet metal covering the instal-
lation clearance area and 18” in front of, and 8” to either
side of the ash pan door.
The 18clearance on the hopper end is a manufactur-
ers recommendation for adding pellets and or servicing the
feeder mechanism.
The minimum ceiling height is 6’6”. This is set by the
clearance to combustibles ( 28” ) from the top of the
of the furnace. See Fig. 22.
The minimum clearance to the top of the plenum is 4”.
Note the minimum height to the bottom of the supply
duct if it crosses the hopper.
The minimum duct configuration to a living space above
the furnace is as shown in below. An offset of at least 24”
MUST be installed between the plenum and the floor regis-
ter. The register size MUST have an area of at least 240
square inches.
CAUTION: When installing a floor
register, the temperature of the
discharge air MUST be taken into
consideration (The discharge air
temperature may be high enough to
cause burns if not properly operated
and maintained.)
CAUTION: The Blower Motor full
load AMPS MUST be checked.A
plenum damper may be required to
adjust the motor full load AMPS to the
motor nameplate rating.
Fig.21
Fig. 22
18”
52” long
PF100
Skidplate
Footprint
Floor Protector
48” wide

NOTE: Install vent at clearances
specified by the vent manufacturer.
Venting and Clearances
14
PF100
Chimneys taller than 20’ above the connection will re-
quire a draft test to determine if the draft is too high.
Note: The High Burn Draft should not exceed .85
IWC. Some form of a restrictor plate may be required at the
top of high chimneys to reduce the draft. See page 20 for
the Draft Test procedure.
16
18
1
/
8
18
1
/
8
Fig. 23
See NOTES: on
page 13
16
Fig. 26
Fig. 24
The shaded areas are the clearances for the PL vent
pipe that must be maintained at 3. After the venting leaves
the shaded area it may be installed at 2” to combustibles.
(Only listed 4” pellet vent wall pass-throughs and fire stops
must be used.) See Fig. 23 & 25.
Fig. 25
Creosote - Formation and Need for Removal - When wood is burned slowly, it produces tar and other organic vapors,
which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney flue
of a slow-burning fire. As a result, creosote residue accumulates on the flue lining. When ignited, this creosote makes an
extremely hot fire. The pellet vent pipe should be inspected at least twice monthly during the heating season to determine
if a creosote buildup has occurred. If creosote has accumulated it should be removed to reduce the risk of a chimney fire.
Guidance on minimizing creosote formation and the need for periodic creosote removal: The chimney should be
inspected during the heating season to determine if a creosote build-up has occurred. If a significant layer of creosote has
accumulated (3mm or more) it should be removed to reduce the risk of a chimney fire.
The PF100 furnace may be used and installed into an
existing masonary or Class A metal chimney.
Certain Canadian and Local Codes may require that
the chimney be fully relined. See Fig. 24.
It Can Not be installed in a chimney serving another
appliance.
The chimney should be cleaned and or inspected be-
fore installation.
Venting and Installation
15PF100
Outside Air
Outside air is optional, although it may be required
by some building codes. The benefit of outside air is
higher efficiency and reduced venting restrictions mainly
noticed in small and very tight houses.
To install outside air, use 2 3/4" I.D.galvinized steel
flex pipe, part # 2-00-08544 ( 12’ 6” length) or part #
2-00-08545 ( 25’ length). There is a break-away hole
on the rear panel which must be removed before con-
necting the flex pipe. See Fig. 28. The pipe should be
run outside and terminate 3 feet or more below or 1
foot or more to the side of the vent pipe outlet. Never
terminate the outside air above the vent pipe outlet. The
maximum length of this pipe is 25 feet. Inlet cover part
number 1-10-09542 should be used to keep birds, ro-
dents etc.out of the inlet pipe. See Fig. 27.
NOTE: If outside air is installed, the inlet cover
should not be placed in an area where drifting of snow
or ice will build up, blocking the intake air supply.
The Outside Air knockout is located on the face
of the Feeder Cover. It is pre-cut except for several
small tabs. There is also a filler plate screwed to the
inside to cover the top of the hole after the Outside Air
Pipe has been installed. This will allow for removal of
the Feeder Cover without disconnecting the Outside Air
Pipe. See Fig. 28.
Only metal Intake Flex should be used for the
Outside Air Supply connection.
Only a screened or rodent protected Outside Air
Intake cover should be used as an outside weather cover.
The Outside Air Intake Pipe is inside the Feeder
Cover and to the right of the feeder motor. The 2 3/4”
steel flex pipe is made to slide over the outside of the Air
Intake Pipe. See Fig. 29. It should be held into place
with some silicone, foil tape, or a hose clamp. ( not sup-
plied )
HRV
When installing in a house with a Heat Reclaiming
Ventilation System (HRV) be sure the system is balanced
and is not creating a negative pressure in the house.
Inlet Cover part#
1-10-09542
Fig. 29
Note: If the furnace is installed with the outside air
system no adjustments to the HRV should be necessary.
Fig. 27
Outside Air Inlet Pipe
Installation
Fig. 28
Outside Air Pipe Knockout
16
PF100
The Wall Control sends and receives it’s informa-
tion from the control board through a 4 wire Datacom
cable. There is a 100’ length of this cable supplied with
the furnace. 100’ lengths of this cable can also be or-
dered separately, part # 3-20-02583. Or any Datacom
cable -CAT 3 - 2 twisted pair 24ga solid wire can be
acquired at a local electrical supply house. Also any CAT
3- 24ga. solid wire 2, 3, or 4 pair cable can be used
because they all have the same pair color combinations.
The maximum length of wall control wiring is 200 feet.
The furnace connecting point is a 4 pole screw ter-
minal block on the side of the hopper just around the
corner to the right of the control. Follow the wiring
instructions on the label alongside the terminal block.
See Fig. 31.
CAUTION: With this small of wire gauge, care
must be taken not to overtighten the terminal screws,
thus breaking the wire.
There are tie-wrap holes in the face of the hopper
aprox. every 6” to keep the cable secure and out of the
way.
The Wall Control is made to fit on a standard wall
case electrical box. It could also be mounted directly to
a stud using 2 drywall screws. In either case the screws
should be turned in and tested for a snug fit when the
Wall Control is slid down over the screws. The Wall
Control only hangs on the screws so a good fit is impor-
tant.
Remove the Wall Control and make the Datacom
cable connections with the UY auto splicers provided.
DO NOT STRIP THE WIRES. Following the wiring
diagram on the inside of the Wall Control make each
splice. See Fig. 32. Insert the two matching color wires
fully into the two holes of one of the UY connectors. A
pair of standard Channel-lock pliers works ideally to
squeeze the raised button down into the UY connector
body. Extra UY connectors can be purchased.
Part # 3-20-00200
NOTE: A pair of needle nose pliers may be nec-
essary to insert the BLUE T-stat wires fully into the con-
nector. Visually inspect to see that the wires are fully
inserted before squeezing the UY splicer.
Orange - Red (+ LED )
Orange/White - White or Black ( - LED)
Blue - Blue ( Tstat )
Blue/White - Blue ( Tstat )
Datacom Wall Control
Cable
Fig. 32
Wall Control Wiring
L
OW
F
UEL
65
60
75
80
70
NOTE: The PF100 furnace Can Not be
installed with any other brand or type of wall
thermostat.
Fig. 30
Installation
Fig. 31
17PF100
The Harman PF100 may be connected to a gas or
oil-fired central furnace or heat pump duct system. Prior
to installation, determine whether all requirements for
installation including all clearnaces can be met.
The PF100 warm air supply and the cold air return
must be installed in a parallel arrangement. EXAMPLE:
The warm air supply duct from the PF100 is to be con-
nected to the warm air supply of the existing furnace.
Also the cold air return duct from the existing furnace is
to be connected to the cold air return duct of the PF100.
Isolation dampers (2) should be installed in the ductwork.
(1) in the warm air supply duct for the existing furnace
and (1) in the warm air supply duct of the PF100 after
or downstreamof the high limit/fan control. These
dampers can be manually operated or fully automatic.
In either case, the unit that is not being used must be
prevented from being operated. (This also can be done
manually or automatically.) NOTE: Any control wiring,
power wiring needed should be performed by a quali-
fied installer and/or electrician.
The warm-air supply outlet of the PF100 shall not
be connected to the cold-air return inlet of the central
furnace because a possibility exists of components of
the central furnace overheating and causing the central
furnace to operate other than as intended.
We recommend that the warm air supply plenum
be constructed of sheet metal.
Fig. 33
Installing Duct
Installing Duct
18
PF100
Adding Air Conditioning to the PF100 furnace.
The PF100 furnace can be fitted with an air condi-
tioning coil mounted in the supply air plenum.
The Harman Stove Co. is not responsable for
sizing,duct placement, or interconnections. However we
have made adding A/C to the furnace easier with the
information listed below.
There is a factory installed junction box ready to
accept your A/C relay. The A/C fan control center with
40 va transformer must have a DPDT relay.
STEVECO # 90-112 - Harman part # 3-20-38056
Other brands are available at local supply houses.
The wiring should be done as per Fig. 34. The low
voltage wiring to the outside condensing unit and the
cooling thermostat are not shown, see condensing unit
diagrams for that information.
This style relay is used to lock out the feeder sys-
tem of the furnace when the A/C unit is calling for cool-
ing. This is a fail-safe against both units operating at the
same time. See the NOTE in the lower left corner.
Recommendations for Supply Air and Return Air
duct sizing.
The speed or velocity of air moving through duct
systems increases as the duct decreases in size with the
same CFM blower. The sound of air flowing through
the duct increases as the velocity increases. Therefore
the largest size duct practial should be used.
The velocity to sound level must be taken into con-
sideration when connecting this furnace into an existing
duct sustem.
As a primary source furnace the duct system can
be installed to fit the customers needs.
These are recommended Supply Air duct sizes (in
square inches)for the different CFM blowers that may
be used with this furnace.
Velocity 500fpm 700fpm 900fpm Static
I.W.C. .3 min. to .6 max.
1000CFM 270sq.in 210sq.in. 160sq.in.
1500CFM 360sq.in. 290sq.in. 220sq.in.
2000CFM 470sq.in. 360sq.in. 290sq.in.
(These duct sizes are only recommendations. )
The Return Air duct system should be sized aprox.
10 percent larger for heating only systems and 20 per-
cent larger if airconditioning is installed.
It is highly recomended that the
furnace control be turned to the
OFF position whenever air
conditioning is being used, whether
or not it is interconnected.
An easy rule of thumb for A/C CFM blower size
is, .75 to 1 CFM for each square foot of conditioned
space. (std. 8’ ceiling height )
CAUTION: Regardless of the supply air duct
size installed the Distribution Blower Motor MUST be
checked for running Amperage. Check the motor name
plate for the full load AMPS. If the amperage is running
higher than that listed, a supply air restricting damper
may be required to increase the supply plenum positive
static pressure.
Fig.34
NOTE:
Installing Duct/Air Conditioning
Installing Duct
19PF100
NOTE: KEEP THE FAN/LIMIT CONTROL
INSTRUCTIONS WITH THE OWNERS
MANUAL FOR FUTURE REFERENCE.
1. The Fan Control must be placed in the discharge
plenum approximately 11 inches above the discharge open-
ing of the furnace as close to center as possible.
Note: The best place is on the same side as the ash
door because of ease of access. See Fig. 35.
Note: Care must be taken when installing the Fan
Control when an air conditioning A Coil is used. The Fan
Control must always be installed below the A Coil in low
plenum installations.
2. Install the flex and wiring.
3. Make sure that the flue venting will not interfere
with the flex to the Fan Control.
4. Pry out one of the bottom knockouts of the Fan
Control. Install the 90 degree flex connector as shown in
Fig. 36. One of the locknuts stays on the outside of the
box and one goes on the inside to tighten the connector
into place. This allows for maximum room for the wires
around the switches.
5. REMOVE THE COPPER JUMPER BE-
TWEEN THE LIMIT AND CONTROL
SWITCHES. (It is not needed.) Figure 36 shown with
copper jumper that has already been removed.
6. Connect the two VIOLET wires to the FAN
CONTROL switch. ( It doesn’t matter which wire is on
which screw). See Fig. 36.
7. Connect the WHITE and SKY BLUE wires to
the LIMIT switch. ( It doesn’t matter which wire is on
which screw). See Fig. 36.
8. Make sure that all of the wires are out of the way
when closing the cover. ( Excess twisting and pinching of
the wires could cause a short circuit.)
9. HIGH LIMIT setup is simple, just rotate the high
limit pointer clockwise until it is against the tamper-proof
screw. (Never adjust this screw)
10. FAN CONTROL setup: Move both fan control
pointers together until they touch, then rotate both pointers
together until the gap between them is directly over the
middle 0 of 100. See Fig 36.
Note: This is the best fan control position we have
found during factory testing. These fan control limits can
be adjusted if desired.
Fig. 35
FAN/HIGH LIMIT CONTROL
Installation & Set-up
High limit fan control
NOTE: If fans are used in the fuel storage area,
they should be installed so as not to create negative
pressures in the room where the solid-fuel-burning
appliance is located.
High Limit
Setpoint
CONTROL
Fig. 36
Fan Control
Setpoint
LIMIT
Locknuts outside and inside
Installation
20
PF100
Installing Electrical Power:
To install power to the furnace first remove the cover
on the circuit breaker junction box shown.
Inside you will find the main terminal block.(See wir-
ing diagram on page 36 for location of main terminal block
and proper power connections). In the bottom of the box a
knockout hole is provided for the incoming wire.
The minimum recommended circuit is 15 Amp 120
V.A.C. 60 Hz. This furnace should be the only appliance
on the circuit.
This furnace should never be powered by the use
of an extension cord.
The recommended high and low voltages are, 130
V.A.C. 60 Hz maximum high voltage, and 113 V.A.C. 60
Hz minimum low voltage.
The furnace will continue to operate at voltages as
low as 105 V.A.C. , although it can not be guaranteed that
automatic ignition will occur. Also there is the possibility of
a distribution blower motor overload.
NOTE: If other sources of electrical power are
to be used ( such as a generator ) for normal opera-
tion or emergency operation, this source should be
checked before installation. Many generators and
inverters may not supply 120V.A.C. 60Hz. power
stable enough to operate the control board properly.
(Control board damage could occur). Checking & Re-
cording the Low Draft:
Fig. 37
After the venting is completed, the firebox low draft
will need to be checked and possibly adjusted. After re-
moving the 3/8bolt from the draft hole shown in Fig. 38,
insert the draft meter tube. The inner ash door and the
hopper lid must be latched during this test. ( It is recom-
mended that the draft meter have a scale of 0 to 1” WC.)
Turn the Furnace Control to Test”. this will start the
combustion blower and allow you to check and record the
High Draft ______ - IWC date _______ (There is no
adjustment for the High Draft)
After the first 60 seconds the Test” mode lowers the
combustion blower voltage to the Low Burn voltage. (The
Testmode cycles the voltage from high to low every 60
seconds).During this lowered voltage cycle the Low Burn
Draft must be checked and adjusted if necessary. The
recommended low draft setting should be between -.25 &
-.35 IWC. Depending on the amount of vertical rise, it may
not be possible to get a low draft reading in this range. In
this case, a maximum low draft of -.55 is acceptable.
The adjustment screw is through the small hole to the
right of the Igniter Light. See Fig. 39. Adjusted the Low
Draft to __________ -IWC.
Don’t forget to turn the control back to #4.
Installation
Draft meter bolt
Furnace Control
Fig. 38
Low Draft Adjustment Pot
Test”
Fig.39
/