Heat & Glo REVO series Install Manual

Category
Fireplaces
Type
Install Manual
1
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16
Models:
Installation Manual
Installation and Appliance Setup
Pour demander un exemplaire en français de ce Manuel
du propriétaire, visitez www.heatnglo.com/translations.
INSTALLER: Leave this manual with party responsible for use and operation.
OWNER: Retain this manual for future reference.
REVO-V12
REVO-S21
REVO-H31
NOTICE: DO NOT discard this manual!
In the Commonwealth of Massachusetts installation must be
performed by a licensed plumber or gas tter.
See Table of Contents for location of additional Commonwealth
of Massachusetts requirements.
This appliance may be installed as an OEM
installation in manufactured home (USA
only) or mobile home and must be installed
in accordance with the manufacturer’s
instructions and the Manufactured Home
Construction and Safety Standard, Title 24
CFR, Part 3280 in the United States, or the
Standard for Installation in Mobile Homes,
CAN/CSA Z240 MH Series, in Canada.
This appliance is only for use with the type(s)
of gas indicated on the rating plate. This
appliance is not convertible for use with other
gases, unless a certi ed kit is used.
DO NOT store or use gasoline or other am-
mable vapors and liquids in the vicinity of this
or any other appliance.
What to do if you smell gas
- DO NOT try to light any appliance.
- DO NOT touch any electrical switch. DO
NOT use any phone in your building.
- Leave the building immediately.
- Immediately call your gas supplier from
a neighbor’s phone. Follow the gas sup-
plier’s instructions.
- If you cannot reach your gas supplier, call
the re department.
Installation and service must be performed
by a quali ed installer, service agency, or the
gas supplier.
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly
could result in serious injury, death, or
property damage.
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of
burns from the hot viewing glass is provided
with this appliance and shall be installed for
the protection of children and other at-risk
individuals.
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16 2
Safety Alert Key:
• DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury.
• WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
• CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
• NOTICE: Used to address practices not related to personal injury.
Table of Contents
Installation Standard Work Checklist . . . . . . . . . . . . . . . . . . . . 3
1 Product Speci c and Important Safety Information
A. Appliance Certi cation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
B. Glass Speci cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
C. BTU Speci cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
D. High Altitude Installations . . . . . . . . . . . . . . . . . . . . . . . . . . 4
E. Non-Combustible Materials Speci cation. . . . . . . . . . . . . . 4
F. Combustible Materials Speci cation . . . . . . . . . . . . . . . . . 4
G. Electrical Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
H. Requirements for the Commonwealth of Massachusetts . . 5
2 Getting Started
A. Design and Installation Considerations . . . . . . . . . . . . . . . 6
B. Tools and Supplies Needed . . . . . . . . . . . . . . . . . . . . . . . . 6
C. Inspect Appliance and Components . . . . . . . . . . . . . . . . . . 6
D. Installation Methods:On-Wall or In-Wall . . . . . . . . . . . . . . . 7
3 Framing and Clearances
A. Appliance/Decorative Front Dimension Diagrams . . . . . . . 8
B. Clearance to Combustibles . . . . . . . . . . . . . . . . . . . . . . . 12
C. Constructing the Appliance Chase . . . . . . . . . . . . . . . . . . 13
D. Floor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
E. Clearances (On-Wall and In-Wall) . . . . . . . . . . . . . . . . . . 14
F. Clearances - Venting with an Elbow Directly Off the
Back of Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4 Termination Location and Vent Information
A. Vent Termination Minimum Clearances . . . . . . . . . . . . . . 16
B. Chimney Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
C. Approved Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
D. Use of Elbows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
E. Measuring Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
F. Vent Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5 Vent Clearances and Framing
A. Pipe Clearances to Combustibles . . . . . . . . . . . . . . . . . . 27
B. Wall Penetration Framing/Firestops . . . . . . . . . . . . . . . . . 27
C. Ceiling Firestop/Floor Penetration Framing . . . . . . . . . . . 28
D. Install Attic Insulation Shield . . . . . . . . . . . . . . . . . . . . . . . 28
6 Appliance Preparation
A. Vent Collar Preparation - Sealing the Firestop . . . . . . . . 29
B. Install Appliance Corrugated Template . . . . . . . . . . . . . . . . .
(On-Wall Installation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
C. Install Appliance Outer Wrap (On-Wall Installation) . . . . 33
D. Install Appliance Into Outer Wrap (On-Wall Installation) . . 35
7 Venting and Chimneys
A. Assemble Vent Sections. . . . . . . . . . . . . . . . . . . . . . . . . . 36
B. Installing Slip Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
C. Secure the Vent Sections . . . . . . . . . . . . . . . . . . . . . . . . . 37
D. Disassemble Vent Sections . . . . . . . . . . . . . . . . . . . . . . . 38
E. Vertical Termination Requirements . . . . . . . . . . . . . . . . . . 39
F. Horizontal Termination Requirements . . . . . . . . . . . . . . . 41
8 Electrical Information
A. General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
B. Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
9 Gas Information
A. Fuel Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
B. Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
C. Gas Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
D. High Altitude Installations . . . . . . . . . . . . . . . . . . . . . . . . . 44
E. Air Shutter Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
10 Finishing (On-Wall Installation)
A. Facing and Finishing - Studio and Frame Decorative
Fronts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
B. Facing and Finishing - Radius Decorative Front
(1 Inch Max. Non-Combustible) . . . . . . . . . . . . . . . . . . . . 48
C. Facing and Finishing - Radius Decorative Front
(4 Inch Maximum Non-Combustible) . . . . . . . . . . . . . . . . . . 50
D. Mantel Projections (All Fronts) . . . . . . . . . . . . . . . . . . . . . 52
E. Mantel Leg and Wall Projections . . . . . . . . . . . . . . . . . . . 53
11 In-Wall Installation
A. Wall and Appliance Preparation . . . . . . . . . . . . . . . . . . . . 54
B. In-Wall - Minimum Combustible Facing Clearances . . . . 58
C. In-Wall - Minimum Non-Combustible Facing Clearances 59
D. In-Wall Mantel and Wall Projections . . . . . . . . . . . . . . . . 60
E. In Wall - Finishing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
12 Appliance Setup
A. Removing Fixed Glass Assembly . . . . . . . . . . . . . . . . . . . 62
B. Remove the Shipping Materials . . . . . . . . . . . . . . . . . . . 62
C. Clean the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
D. Decorative Fronts/Mesh . . . . . . . . . . . . . . . . . . . . . . . . . . 62
13 Reference Materials
A. Vent Components Diagrams . . . . . . . . . . . . . . . . . . . . . . 63
B. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
= Contains updated information.
3
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16
Installation Standard Work Checklist
Customer:
Lot/Address:
Model (circle one): REVO-V12 REVO-H31
REVO-S21
Date Installed:
Location of Fireplace:
Installer:
Dealer/Distributor Phone #
Serial #:
Comments: Further description of the issues, who is responsible (Installer/ Builder/ Other Trades, etc) and corrective
action needed _____________________________________________________________________________________
_________________________________________________________________________________________________
Comments Communicated to party responsible ____________________ by ______________________on ___________
(Builder / Gen. Contractor/) (Installer) (Date)
Appliance Install YES IF NO, WHY?
Veri¿ ed that the area behind appliance is insulated and sealed as required. (Pg. 12) ___________________________
Required non-combustible board installed.(In-Wall Installation only) (Section 11) ___________________________
Veri¿ ed clearances to combustibles. (Section 3) ___________________________
Required In-Wall Kit installed if back of appliance outer wrap penetrates
the sheetrock/¿ nish wall material (In-Wall Installation only) ___________________________
Verified appliance is installed a minimum of 4 inches above finished floor. (Sections 3,5,6,11) ___________________________
Veri¿ ed ¿ replace is leveled and secured. (Pg. 33,54) ___________________________
Venting/Chimney Section 7 (Pg 36-41)
Venting con¿ guration complies with allowable vent requirements. ___________________________
Venting installed, locked and secured in place with proper clearances. ___________________________
Interior/Exterior ¿ restops installed and sealed (In-Wall Installation only). ___________________________
Attic insulation shield installed. (Pg 28) ___________________________
Terminations/Roof À ashing installed and sealed. ___________________________
Termination cap extension installed and sealed (In-Wall Installation only)(Section 11) ___________________________
Electrical Section 8 (Pg 42-43)
120VAC unswitched power provided to the appliance. ___________________________
Veri¿ ed ON/OFF switch wires properly installed. ___________________________
Gas Section 9 (Pg 44-45)
Appliance con¿ guration matches fuel type. ___________________________
Was a conversion performed? ___________________________
Leak check performed and inlet/outlet pressure veri¿ ed. ___________________________
Set air shutter for optimal À ame appearance. ___________________________
Finishing Section 10 (Pg 46-53)
Combustible materials not installed in non-combustible areas. ___________________________
Veri¿ ed all clearances meet installation manual requirements. ___________________________
Mantels and wall projections comply with installation manual requirements. ___________________________
Appliance Setup Section 12 (Pg 62)
All packaging and protective materials are removed from inside/under /on
the appliance. ___________________________
Glass assembly installed and secured, glass retainers removed,gasket sealed. ___________________________
Accessories installed properly. ___________________________
Mesh, doors, or decorative front properly installed. ___________________________
Manual bag and all of its contents are removed from inside/under
the appliance and given to party responsible for use and operation. ___________________________
Operated appliance. Veri¿ ed no gas leaks exist and proper appliance operation. ___________________________
2273-982F 11/16
Î = Contains updated information.
Hearth & Home Technologies recommends the following:
• Photographing the installation and copying this checklist for your ¿ le.
• This checklist remain visible at all times on the appliance until the installation is complete.
This standard work checklist is to be used by the installer in conjunction with, not instead of, the instructions contained in this
installation manual.
WARNING! Risk of Fire or Explosion! Failure to install appliance according to these instructions can
lead to a ¿ re or explosion.
ATTENTION INSTALLER:
Follow this Standard Work Checklist
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16 4
B. Glass Speci cations
This appliance is equipped with 5 mm ceramic glass. Re-
place glass only with 5 mm ceramic glass. Please contact
your dealer for replacement glass.
C. BTU Speci cations
A. Appliance Certi cation
E. Non-Combustible Materials Speci cation
Material which will not ignite and burn. Such materials are
those consisting entirely of steel, iron, brick, tile, concrete,
slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in
a Vertical Tube Furnace at 750 ºC shall be considered
non-combustible materials.
F. Combustible Materials Speci cation
Materials made of or surfaced with wood, compressed pa-
per, plant bers, plastics, or other material that can ignite
and burn, whether ame proofed or not, or plastered or
unplastered shall be considered combustible materials.
G. Electrical Codes
NOTICE: This appliance must be electrically wired
and grounded in accordance with local codes or, in the
absence of local codes, with National Electric Code
ANSI/NFPA 70-latest edition or the Canadian Electric
Code CSA C22.1.
A 110-120 VAC circuit for this product must be pro-
tected with ground-fault circuit-interrupter protection,
in compliance with the applicable electrical codes,
when it is installed in locations such as in bathrooms
or near sinks.
NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE.
This appliance is tested and approved as either supplemen-
tal room heat or as a decorative appliance. It should not be
factored as primary heat in residential heating calculations.
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced,
these rules do not apply. Check with your local gas utility
or authorities having jurisdiction.
When installing above 2000 feet elevation:
In the USA: Reduce input rate 4% for each 1000 feet
above 2000 feet.
In CANADA: Input ratings are certi ed without a reduction
of input rate for elevations up to 4500 feet (1370 m)
above sea level. Please consult provincial and/or
local authorities having jurisdiction for installations at
elevations above 4500 feet (1370 m).
Check with your local gas utility to determine proper
ori ce size.
NOTICE: This installation must conform with local codes.
In the absence of local codes you must comply with the
National Fuel Gas Code, ANSI Z223.1-latest edition in
the U.S.A. and the CAN/CGA B149 Installation Codes in
Canada.
1
1 Product Speci c and Important Safety Information
Models
(U.S. or Canada)
Maximum
Input BTU/h
Minimum
Input
BTU/h
Ori ce
Size (DMS)
Revo-V12
(NG) (0-2000 FT) 14,250 8,200 #50
Revo-V12
(LP) (0-2000 FT) 13,350 8,500 #58
Revo-S21
(NG) (0-2000 FT) 18,800 10,900 .083 in.
Revo-S21
(LP) (0-2000 FT) 18,950 10,800 1.25 mm
Revo-H31
(NG) (0-2000 FT) 24,000 12,700 #42
Revo-H31
(LP) (0-2000 FT) 20,000 10,850 0.053 in.
MODELS: Revo-V12, Revo-S21, Revo-H31
LABORATORY: Underwriters Laboratories, Inc. (UL)
TYPE: Direct Vent Heater
STANDARD: ANSI Z21.88-2014/CSA 2.33-2014
This product is listed to ANSI standards fo “Vented Gas
Fireplace Heaters” and applicable sections of “Gas Burn-
ing Heating Appliances for Manufactured Homes and
Recreational Vehicles”, and “Gas Fired Appliances for
Use at High Altitudes”.
5
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16
H. Requirements for the Commonwealth of
Massachusetts
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7)
feet above nished grade in the area of the venting, in-
cluding but not limited to decks and porches, the following
requirements shall be satis ed:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gas tter
shall observe that a hard wired carbon monoxide detector
with an alarm and battery back-up is installed on the oor
level where the gas equipment is to be installed. In addi-
tion, the installing plumber or gas tter shall observe that
a battery operated or hard wired carbon monoxide detec-
tor with an alarm is installed on each additional level of
the dwelling, building or structure served by the side wall
horizontal vented gas fueled equipment. It shall be the
responsibility of the property owner to secure the services
of quali ed licensed professionals for the installation of
hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fu-
eled equipment is installed in a crawl space or an attic,
the hard wired carbon monoxide detector with alarm and
battery back-up may be installed on the next adjacent
oor level.
In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply
with the above requirements; provided, however, that dur-
ing said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accor-
dance with the above provisions shall comply with NFPA
720 and be ANSI/UL 2034 listed and IAS certi ed.
Signage
A metal or plastic identi cation plate shall be permanent-
ly mounted to the exterior of the building at a minimum
height of eight (8) feet above grade directly in line with the
exhaust vent terminal for the horizontally vented gas fu-
eled heating appliance or equipment. The sign shall read,
in print size no less than one-half (1/2) in. in size, “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB-
STRUCTIONS”.
Inspection
The state or local gas inspector of the side wall horizon-
tally vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector ob-
serves carbon monoxide detectors and signage installed
in accordance with the provisions of 248 CMR 5.08(2)(a)1
through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition
of NFPA 54 as adopted by the Board; and
Product Approved side wall horizontally vented gas fu-
eled equipment installed in a room or structure separate
from the dwelling, building or structure used in whole or
in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting
system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
Detailed instructions for the installation of the venting
system design or the venting system components; and
A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall
horizontally vented gas fueled equipment does not pro-
vide the parts for venting the ue gases, but identi es
“special venting systems”, the following requirements
shall be satis ed by the manufacturer:
The referenced “special venting system” instructions
shall be included with the appliance or equipment in-
stallation instructions; and
• The “special venting systems” shall be Product Ap-
proved by the Board, and the instructions for that sys-
tem shall include a parts list and detailed installation
instructions.
A copy of all installation instructions for all Product Ap-
proved side wall horizontally vented gas fueled equip-
ment, all venting instructions, all parts lists for venting
instructions, and/or all venting design instructions shall
remain with the appliance or equipment at the completion
of the installation.
See Gas Connection section for additional Common-
wealth of Massachusetts requirements.
Note: The following requirements reference various
Massachusetts and national codes not contained in this
document.
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16 6
2
2 Getting Started
A. Design and Installation Considerations
Heat & Glo direct vent gas appliances are designed to
operate with all combustion air siphoned from outside of
the building and all exhaust gases expelled to the outside.
No additional outside air source is required.
Installation MUST comply with local, regional, state and
national codes and regulations. Consult insurance carrier,
local building inspector, re of cials or authorities having
jurisdiction over restrictions, installation inspection and
permits.
Before installing, determine the following:
• Where the appliance is to be installed.
• Whether the REVO will be installed On-Wall or In-Wall
(See Section 2.D),
• The vent system con guration to be used.
• Gas supply piping requirements.
• Electrical wiring requirements.
• Framing and nishing details.
Whether optional accessories—devices such as a wall
switch or remote control—are desired.
C. Inspect Appliance and Components
Carefully remove the appliance and components from
the packaging.
The vent system components and decorative doors and
fronts may be shipped in separate packages.
Report to your dealer any parts damaged in shipment,
particularly the condition of the glass.
Read all of the instructions before starting the instal-
lation. Follow these instructions carefully during the
installation to ensure maximum safety and bene t.
WARNING! Risk of Fire or Explosion! Damaged parts
could impair safe operation. DO NOT install damaged, in-
complete or substitute components. Keep appliance dry.
B. Tools and Supplies Needed
Before beginning the installation be sure that the following
tools and building supplies are available.
Tape measure Framing material
Pliers Hammer
Phillips screwdriver Manometer
Gloves Framing square
Voltmeter Tin Snips
Plumb line Safety glasses
Level Reciprocating saw
Stud Finder Flat blade screwdriver
Electric drill: 1/2 in. bit, 1/4 in. masonry bit (masonry wall
installation only)
Non-corrosive leak check solution
1/2 - 3/4 in. length, #6 or #8 Self-drilling screws
Caulking material (300ºF minimum continuous exposure
rating)
Hearth & Home Technologies disclaims any responsibility for,
and the warranty will be voided by, the following actions:
Installation and use of any damaged appliance or vent
system component.
• Modi cation of the appliance or vent system.
Installation other than as instructed by Hearth & Home
Technologies.
Improper positioning of the gas logs or the glass door.
Installation and/or use of any component part not approved
by Hearth & Home Technologies.
Any such action may cause a re hazard.
WARNING! Risk of Fire, Explosion or Electric Shock!
DO NOT use this appliance if any part has been under
water. Call a quali ed service technician to inspect the
appliance and to replace any part of the control system
and/or gas control which has been under water.
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. For
assistance or additional information, consult a quali ed
service technician, service agency or your dealer.
Installation and service of this appliance should be performed by
quali ed personnel. Hearth & Home Technologies recommends
HHT Factory Trained or NFI certi ed professionals.
7
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16
D. Installation Methods:On-Wall or In-Wall
When installing the REVO model, you may choose from one of two installation options.
1. On-Wall Installation:
The REVO can hang on a sheet rock/combustible wall
2. In-Wall Installation:
The REVO can be partially recessed into a wall using the In-Wall Tub Assembly
The On-Wall installation is the most common and least dif cult method. On-Wall installation information is located in Sec-
tions 3, 6, and 10. In-Wall installation information is isolated in Section 11. Section 11 will discuss preparation, clearances
and nishing speci c to the In-Wall method. Consult the table of contents for topics common to both methods, such as vent
con gurations, gas and electrical information.
On-Wall Installation In-Wall Installation
The REVO can hang on a sheet rock/combustible wall.
See Sections 3, 6 and 10 for On-Wall installation
information.
The REVO can be partially recess into a wall using
the In-Wall Kit. See Service Parts section in Owner’s
Manual and contact your dealer to order. See Section
11 for installation information.
FRAMING
FRAMING + SHEETROCK
MATERIAL CAN BE
COMBUSTIBLE
I.E. SHEETROCK
FRAMING + SHEETROCK
+ APPLIANCE OUTER WRAP
FRAMING + SHEETROCK
+ APPLIANCE OUTER WRAP + HOLE CUT
CUT OUT MATERIAL
FOR VENT
APPLIANCE
OUTER WRAP
APPLIANCE
OUTER WRAP
7-5/16 IN.
SIDE VIEW
(DECORATIVE FRONT INSTALLED)
FINISHED INSTALLATION
TOP VIEW
TOP VIEW WITH
TUB INSTALLED
VERTICAL
2 X 6 STUDS
2 X 6 HEADER
TUB ASSEMBLY
TUB ASSEMBLY
INSULATION ZONE
BEFORE
AFTER
3-1/2 IN.
2 IN.
NON-COMBUSTIBLE
BOARD
SHEETROCK/COMBUSTIBLE
FACING MATERIAL
RECESSED
IN-WALL TUB
4-13/16 IN.
SIDE VIEW
(DECORATIVE FRONT INSTALLED)
FRAMING
APPLIANCE
INSTALLED
4 IN. TO
FINISHED
FLOOR
NON-COMBUSTIBLE
BOARD
FRAMING + IN-WALL TUB
+ APPLIANCE
Figure 2.1 On-Wall Installation Method Figure 2.2 In-Wall Installation Method
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16 8
C
B
A
E
D
K
J
G
F
I
H
L
M
3
3 Framing and Clearances
A. Appliance/Decorative Front Dimension Diagrams
Dimensions are actual appliance dimensions. Use for reference only. For framing dimensions and clearances refer to Section 3
and Section 5.
Appliance Dimensions Table
Figure 3.1 Appliance Dimensions - Revo-V12
Location Inches Millimeters
A 36-1/8 918
B 12 305
C 24 610
D 16-5/8 422
E 19-1/4 489
F 6-1/8 156
G 28-1/2 724
H 9-5/8 245
I 6-5/8 168
J3 76
K 4-1/4 108
L 6-3/8 162
M 7-7/8 200
REVO-V12
9
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16
Figure 3.2 Appliance Dimensions - Revo-S21
C
B
G
A
E
D
H
F
ML
I
K
J
Location Inches Millimeters
A 33-5/8 854
B 21-1/8 537
C 21-3/8 543
D 25-3/4 654
E 28-1/2 724
F 6-1/4 159
G 26 660
H 14-1/4 362
I 6-5/8 168
J3 76
K 4-5/16 109
L 6-3/8 162
M 7-7/8 200
Appliance Dimensions Table
REVO-S21
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16 10
Figure 3.3 Appliance Dimensions - Revo-H31
C
BG
A
E
D
H
F
ML
I
K
J
Appliance Dimensions Table
Location Inches Millimeters
A 29-1/8 740
B 31 787
C 17 432
D 35-5/8 905
E 38-1/4 972
F 6-1/8 156
G 21-1/2 546
H 19-1/8 486
I 6-5/8 168
J3 76
K 4-3/16 106
L 6-3/8 162
M 7-7/8 200
REVO-H31
11
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16
STUDIO/FRAME DECORATIVE FRONTS
Figure 3.4 Appliance Dimensions - Studio and Frame Decorative Fronts
Figure 3.5 Appliance Dimensions - Radius Decorative Front
RADIUS DECORATIVE FRONT
32-3/4 IN.
34-1/8 IN.
23-1/2 IN.
37-15/16 IN.
REVO-V12
42-9/16 IN.
30-3/16 IN.
REVO-S21 REVO-H31
36-5/8 IN.
36-15/16 IN.
46-15/16 IN.
32-11/16 IN.
27-5/8 IN.
39-1/2 IN.
REVO-V12 REVO-S21 REVO-H31
See Section 10.A, 10.B, 10.C, and 11.C for facing and nishing detail.
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16 12
B. Clearance to Combustibles
When selecting a location for the appliance it is important
to consider the required clearances to walls (see Figure
3.6).
WARNING! Risk of Fire or Burns! Provide adequate
clearance around air openings and for service access.
Due to high temperatures, the appliance should be lo-
cated out of traf c and away from furniture and draperies.
NOTICE: Illustrations re ect typical installations and are
FOR DESIGN PURPOSES ONLY. Illustrations/diagrams
are not drawn to scale. Actual installation may vary due to
individual design preference.
Figure 3.6 Appliance Locations
WARNING! Risk of Fire! Maintain speci ed air space
clearances to appliance and vent pipe:
Insulation and other materials must be secured to prevent
accidental contact.
The chase must be properly blocked to prevent blown
insulation or other combustibles from entering and
making contact with replace or chimney.
Failure to maintain airspace may cause overheating and
a re.
See Figure 3.6, 3.7, 3.8, 3.9, and 3.11 for framing
dimension requirements and required clearances.
41 IN.
(1041 mm)
20-1/8 IN.
(511 mm)
50-13/16 IN.
(1291 mm)
27-1/16 IN.
(687 mm)
37-1/16 IN.
(941 mm)
17-5/16 IN.
(440 mm)
34-5/16 IN.
(872 mm)
15-3/8 IN.
(391 mm)
REVO-H31
REVO-V12
REVO-V12
REVO-V12
REVO-S21
REVO-H31
REVO-S21
1 IN. MINIMUM
(25 mm) ZERO CLEARANCE
ZERO CLEARANCE
Refer to Sections 10.D and 10.E for
mantel and wall projection information.
12 IN.
(305 mm)
12 IN.
(305 mm)
1 IN. MINIMUM
(25 mm)
Note: The REVO-V12 is the only REVO appliance that can be vented with a 45 degree elbow directly off the
back positioned horizontally. See Section 4.F.
13
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16
C. Constructing the Appliance Chase
A chase is a vertical box-like structure built to enclose the
gas appliance and/or its vent system. In cooler climates
the vent should be enclosed inside the chase.
NOTICE: Treatment of ceiling restops and wall shield
restops and construction of the chase may vary with the
type of building. These instructions are not substitutes
for the requirements of local building codes. Therefore,
you MUST check local building codes to determine the
requirements to these steps.
To further prevent drafts, the wall shield and ceiling re-
stops should be caulked with caulk with a minimum of
300ºF continuous exposure rating to seal gaps. Gas
line holes and other openings should be caulked with
caulk with a minimum of 300ºF continuous exposure rating
or stuffed with unfaced insulation. If the appliance is being
installed on a cement surface, a layer of plywood may be
placed underneath to prevent conducting cold up into the
room.
D. Floor Protection
WARNING! Risk of overheating! Install appliance a
minimum of 4 inches off of nished oor.
• Convection air ow could be compromised and cause
overheating.
• Decorative fronts will not t properly.
• The nished oor below the appliance does not have to
be non-combustible, due to the required 4 inch minimum
clearance from bottom of appliance to nished oor.
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16 14
MINIMUM CLEARANCES FROM APPLIANCE OUTER WRAP
MODEL
A B C D* E** F*** G
Rough
Opening
(Vent Pipe)
Clearance
to Ceiling
Minimum
Clearance
to Finished
Floor
Clearance
to
Combustible
Flooring
Behind
Appliance
Outer
Wrap
Clear-
ance to
Adjacent
Wall
Front of
Appliance
Measured from
Mesh
Revo-V12
in. 10-1/8 22 4 0 0 12 36
mm 257 559 102 0 0 305 914
Revo-S21
in. 10-1/8 22 4 0 0 12 36
mm 257 559 102 0 0 305 914
Revo-H31
in. 10-1/8 22 4 0 0 12 36
mm 257 559 102 0 0 305 914
D* = Clearance to combustible oor not required due to 4 inch minimum on Dimension C.
E** = The appliance outer wrap can attach directly to combustible material, i.e. sheetrock.
F*** = See Section 10.D and 10.E for combustible and non-combustible mantel legs.
A
(CUT OUT MATERIAL
FOR VENT PIPE)
C
D
F
B
(TO CEILING)
E
APPLIANCE OUTER
WRAP
G
Figure 3.7
E. Clearances (On-Wall and In-Wall)
WARNING! Risk of overheating! Install appliance a
minimum of 4 inches off of nished oor.
• Convection air ow could be compromised and cause
overheating.
• Decorative fronts will not t properly.
15
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16
1-1/2 IN. PIPE CLEARANCE
IN ZONE ABOVE ELBOW
AND BEHIND APPLIANCE
OUTER WRAP
ZERO CLEARANCE
SHEETROCK/
COMBUSTIBLE
MATERIAL
APPLIANCE
OUTER WRAP
NOTE: VERTICAL WALL
STUDS NOT SHOWN
10-3/4 IN.
COMBUSTIBLE
ZONE
13-1/4 IN.
FRAMING HEADER TURNED VERTICAL
FOR CLEARANCE
COMBUSTIBLE
ZONE
ON WALLIN WALL
SHEETROCK/
COMBUSTIBLE
MATERIAL
ATTIC ABOVE
9 IN.
9 IN.
See Section 5 for information regarding ceiling restop.
Figure 3.11 Ceiling Penetration Framing Requirements
Figure 3.9 Clearance Requirements
1-5/8 IN.
CUT LINE
NOTE: The firestop heat shield will need to be cut when using
an elbow directly off the back of the appliance. See Figure 3.9.
Figure 3.10 Wall Firestop Clearances
CLEAR SPACE
3 FT. IN
FRONT OF
FIREPLACE
MESH
4 IN. MIN.TO
FINISHED FLOOR
FLOOR CAN BE
COMBUSTIBLE
Figure 3.8 Clear Space Requirement - All Models
F. Clearances - Venting with an Elbow
Directly Off the Back of Appliance
Note: The restop shield will need to be trimmed when
venting with a 90 degree elbow directly off the back of the
appliance. See Figure 3.10.
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16 16
A. Vent Termination Minimum Clearances
Roof Pitch H (Min.) Ft.
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5*
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
Figure 4.1 Minimum Height From Roof To Lowest Discharge
Opening
HORIZONTAL
OVERHANG
VERTICAL
WALL
GAS DIRECT VENT
TERMINATION CAP
12
X
ROOF PITCH
IS X/ 12
LOWEST
DISCHARGE
OPENING
2 FT.
MIN.
20 INCHES MIN.
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
4
4 Termination Location and Vent Information
Fire Risk.
Maintain vent clearance to combustibles as
speci ed.
DO NOT pack air space with insulation or other
materials.
Failure to keep insulation or other materials away
from vent pipe may cause overheating and re.
WARNING
Figure 4.2 Staggered Termination Caps
Gas, Wood or Fuel Oil
Termination Cap
B
Gas
Termination
Cap **
A *
*If using decorative cap cover(s), this distance may need to be
increased. Refer to the installation instructions supplied with the
decorative cap cover.
**
AB
6 in. (minimum) up to 20 in.
152 mm/508 mm
18 in. minimum
457 mm
20 in. and over 0 in. minimum
In a staggered installation with both gas and wood or fuel oil
terminations, the wood or fuel oil termination cap must be
higher than the gas termination cap.
* H minimum may vary depending on regional snowfall.
Refer to local codes.
17
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16
O
N
P
R
Q
X= AIR SUPPLY INLET
V= VENT TERMINAL
= AREA WHERE TERMINAL IS NOT PERMITTED
C
JB
D
B
F
B
A
E
V
V
V
V
V
V
M
H or i
V
G
X
VH
A
VV
H
Electrical
Service
V
K
V K
V
L
C
V
Measure horizontal clearances from this surface.
Measure vertical clearances from this surface.
CLEARANCE = 6 IN.
B. Chimney Diagram
Figure 4.3 Minimum Clearances for Termination
A = 12 inches.................clearances above grade, veranda,
porch, deck or balcony
B =
12 inches.................clearance to window or door that may
be opened, or to permanently closed
window
C = 18 inches.................clearance below unventilated sof t
18 inches.................clearance below ventilated sof t
30 inches .................clearance below vinyl soffits and
electrical service
D = 9 inches...................clearance to outside corner
E = 6 inches...................clearance to inside corner
F = 3 ft. (Canada) ..........not to be installed above a gas me-
ter/regulator assembly within 3 feet
horizontally from the center-line of the
regulator
G = 3 ft ...........................clearance to gas service regulator
vent outlet
H = 9 inches (U.S.A)
12 inches (Canada). clearance to non-mechanical (unpow-
ered) air supply inlet, combustion air
inlet or direct-vent termination
i = 3 ft. (U.S.A.)
6 ft. (Canada) ...........clearance to a mechanical (powered)
air supply inlet
All mechanical air intakes within 10 feet of a termination cap
must be a minimum of 3 feet below termination.
J = 7 ft. ......................... On public property: clearance above
paved sidewalk or a paved driveway.
A vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings
and serves both dwellings.
N = 6 inches ........... non-vinyl sidewalls
12 inches ......... vinyl sidewalls
O = 18 inches ......... non-vinyl sof t and overhang
42 inches ......... vinyl sof t and overhang
P = 8 ft.
QMIN RMAX
1 cap 3 feet 2 x Q ACTUAL
2 caps 6 feet 1 x Q ACTUAL
3 caps 9 feet 2/3 x Q ACTUAL
4 caps 12 feet 1/2 x Q ACTUAL
QMIN = # termination caps x 3 RMAX = (2 / # termination caps) x QACTUAL
Covered Alcove Applications
(Spaces open only on one side and with an overhang)
CAUTION! Risk of Burns! Termination caps are HOT,
consider proximity to doors, traf c areas or where people
may pass or gather (sidewalk, deck, patio, etc.). Listed cap
shields available. Contact your dealer.
Local codes or regulations may require different
clearances.
Vent system termination is NOT permitted in screened
porches.
Vent system termination is permitted in porch areas with
two or more sides open.
Hearth & Home Technologies assumes no responsibility
for the improper performance of the appliance when the
venting system does not meet these requirements.
Vinyl protection kits are suggested for use with vinyl siding.
M = 18 inches .................... clearance under veranda, porch, deck,
balcony or overhang
42 inches ................vinyl or composite overhang
Permitted when veranda, porch, deck or balcony is fully open
on a minimum of 2 sides beneath the oor.
K = 6 inches................. clearance from sides of electrical
service
L = 12 inches................ clearance above electrical service
Location of the vent termination must not interfere with access to the
electrical service.
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16 18
C. Approved Pipe
This appliance is approved for use with Hearth & Home
Technologies SLP venting systems. Refer to Section
13.A for vent component information and dimensions.
DO NOT mix pipe, ttings or joining methods from differ-
ent manufacturers.
The pipe is tested to be run inside an enclosed wall.
There is no requirement for inspection openings at each
joint within the wall.
WARNING! Risk of Fire or Asphyxiation. This appli-
ance requires a separate vent. DO NOT vent to a pipe
serving a separate solid fuel burning appliance.
D. Use of Elbows
Diagonal runs have both vertical and horizontal vent as-
pects when calculating the effects. Use the rise for the
vertical aspect and the run for the horizontal aspect. See
Figure 4.4.
Two 45º elbows may be used in place of one 90º elbow.
On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216
mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A
length of straight pipe is allowed between two 45º elbows.
See Figure 4.4.
Figure 4.5 shows the vertical and horizontal offsets for
SLP elbows.
Figure 4.4
HORIZONTAL
VERTICAL
RUN
RISE
EFFECTIVE
LENGTH
Y
X
X
X
Vent Type X
Inches Millimeters
SLP 11-1/4 286
Figure 4.5 Vertical and Horizontal Offset for SLP Elbows
Vent
Type
XY
Inches Millimeters Inches Millimeters
SLP 5 127 11-3/4 298
SLP
Pipe
Effective Length Rise/Run
Inches Millimeters Inches Millimeters
SLP4 4 102 2-3/4 70
SLP6 6 152 4-1/4 108
SLP12 12 305 8-1/2 216
SLP24 24 610 17 432
SLP36 36 914 25-1/2 648
SLP48 48 1219 34 864
SLP6A 3 to 6 76 to 152 2-1/8-4-1/4 54-108
SLP12A 3 to 12 76 to 305 2-1/8-8-1/2 54-216
19
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16
E. Measuring Standards
Vertical and horizontal measurements listed in the vent
diagrams were made using the following standards.
Pipe measurements are shown using the effective length
of pipe. See Section 13.A for information on effective
length of pipe components.
Horizontal terminations are measured to the outside
mounting surface ( ange of termination cap) (see Figure
4.3).
Vertical terminations are measured to bottom of
termination cap.
• Horizontal pipe installed level with no rise.
General Rules:
• 90º elbows can be replaced with two 45º elbows.
SUBTRACT 3 ft. from the total H measurement for each
90º elbow installed horizontally.
SUBTRACT 1-1/2 ft. from the total H measurement for
each 45º elbow installed horizontally.
A maximum of three 90º elbows (or six 45º elbows) may
be used in any vent con guration. Some elbows may be
installed horizontally. See Figure 4.9 and Figure 4.12 .
When penetrating a combustible wall, a wall shield
restop must be installed. See Figure 5.1.
When penetrating a combustible ceiling, a ceiling restop
must be installed. See Figure 5.4.
• Horizontal runs of vent do not require vertical rise;
horizontal runs may be level.
Horizontal termination cap should have a 1/4 inch
downward slant to allow any moisture in cap to be
released. See Figure 4.6.
F. Vent Diagrams
Heat & Glo • REVO-V12, REVO-S21, REVO-H31 Installation Manual • 2273-980 Rev. K • 11/16 20
Figure 4.6
Figure 4.7
Horizontal Termination
No Elbow
One 45º Elbow
H = 12 in. (305 mm) Maximum
H Maximum
V12 12 in. (305 mm)
S21 Not allowed
H31 Not allowed
H
H
Note: This vent con guration is
not allowed with the REVO-S21
or REVO-H31 models.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69