INSTRUCTION MANUAL FOR MICROWAVE MOTION SENSOR
Model No.:HC419VRC
Technical Specifications
PRODUCT TYPE: Microwave Motion Sensor
OPERATING VOLTAGE: 120-277VAC 50Hz/60Hz
HF SYSTEM: 5.8GHz CW radar
RATED LOAD: 120VAC / 3.4A / 400W
230VAC / 3.5A / 800W
277VAC / 3.7A / 1000W
DETECTION ANGLE: 30 ~150
POWER CONSUMPTION: <1W
DETECTION RANGE: Max. 12 x 6m (DxH)
TIME SETTING: 5s~30min.
DAYLIGHT SENSOR: 2~50Lux; disable
STAND-BY PERIOD: 0s, 10s~1h, +
STAND-BY DIMMING LEVEL: 10%~30%
MOUNTING:Indoors,ceiling & wall mounted
WORKING TEMP.: -20 ~ +60
HC419VRC HRC-05
The sensor is an active motion detector; it emits a high-frequency electro-magnetic wave 5.8GHz and receives its echo. The sensor detects the change
in echo from movement in its detection zone. A microprocessor then triggers the switch light ON command. Detection is possible through doors, panels
of glasses thin walls.
Note: the high-frequency output of this sensor is <0.2mW; approximately just 0.2of the transmission power of a mobile telephone
IMPORTANT
PLEASE READ THESE INSTRUCTIONS CAREFULLY PRIOR TO INSTALLATION AND RETAIN THIS LEAFLET IN A KNOWN
AND SAFE PLACE FOR FUTURE REFERENCE.
SECTION 1 INSTALLATION AND WIRING
1.1 Ensure that the electricity supply is switched off before installing or servicing this product.
1.2 Wiring diagram
°°
(capacitive load)
Sensor antenna
Buzzer LED indication
Detection area
Infrared remote receiver
Hold-time
Daylight threshold
Stand-by period
Stand-by dimming level
Daylight sensor
Installation hole
Push
L
N
L ’
SYNC
SYNC
1-10V
+
Stand-by dimming level
Detection range
ON/
OFFAuto ModeReset
Power
80%
Test
2s
10%20%
30s 1min
100%
30min10min5min
0s 10s1min
30%
SC1 SC2
SC3
Scene mode
10min
50%10%
30min
Hold-time
Stand-by period
5min
Lux
Disable
2Lux
10Lux
50Lux
Daylight Sensor
SC4
Power
100% +
-
Dim
M/A
8
Note: this 1-10V output is isolated, SELV output.Do not connect the
1-10V terminals on driver X to Driver Y.
Wiring diagram for synchronization function
LED Driver
LED1-10V
SYNCV01-1
LED Driver ( X )
LED1-10V
V01-1V01-1
LED1-10V LED Driver ( Y )
Max.10pcs
SYNC SYNC
.
3rd Floor, block C, complex building, 155#, Bai'gang road south,
Bai'gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023
Tel:86-752-2772020 F:86-752-2777877
E: [email protected] W:www.hytronik.com
CHINA FACTORY
Room D, 10/f, Tower A, Billion Center, 1 wang Kwong Road,
Kowloon Bay, Kowloon, Hongkong
T: 00852-35197525 F: 00852-30116936
HYTRONIK INDUSTRIAL LIMITED
SECTION 2 REMOTE CONTROL
Permanent ON/OFF [ ]
1. Press button , to select permanent ON or permanent OFF mode.
2. Press button to resume automatic operation. (Please refer to explanation below)
3. The mode will change to AUTO Mode after power failure.
Auto Mode [ ]
Press button to in initiate automatic mode. The sensor starts working and all settings remain as before the light was switched ON/OFF.
RESET [ ]
Press button , all settings go back to the value of DIP switch settings.
Test 2s function [ ]
1.Press button ,the sensor goes into testmode (hold time2s). N.B. the stand-by period and daylight sensor settings are disabled in test mode.
2.Press button to exit from this mode, and the sensor settings are changed accordingly.
Ambient daylight threshold [ ]
Press button , the latest surrounding lux value overwrites previous lux value learned, and is set as the daylight threshold. This feature enables the fixture
to function well in any environment.
Detection range[ ]
Press buttons in zone to set detection range at 100% / 50% / 10%.
Hold time [ ]
Press buttons in zone to set hold time at 30s / 1min / 5min / 10min / 30min.
Stand-by period [ ]
Press buttons in zone to set the stand-by period at 0s / 10s / 1min / 10min / 30min / +∞.
Note: “0s” means on/off control; “+∞” means bi-leve of dimming control, the light will never switch off.
(i.e. the light remains at the stand-by dimming level until motion is detected.)
Stand-by dimming level [ ]
Press buttons in zone to set the stand-by dimming level at 10% / 20% / 30% .
Daylight sensor [ ]
Press buttons in zone to set daylight sensor at 2lux / 10lux / 50lux.
1
2
3
234
button 1
button 2
button 3
8
3
10
6
Press button ,the sensor goes to manual override or semi-auto function.
15
11
13
12
7
4
11
button 8
button
10
Power output [ ]
Press button , the output shifts between 80% and 100%, for energy saving purposes.
5
button 5
Dim +/- [ ]
Press button to adjust the light brightness between 10%~100% during hold-time.“+” increases the light level, “-” will decrease the light level.
9
button 9
Lux disable [ ]
Press button , the built-in daylight sensor is disabled, the light will always operate upon detection regardless of ambient light level.
14
button
14
Manual override/ Semi-auto [ ]
Note: The buzzer beeps twice if it is in manual override mode, and beeps once if shifts to semi-auto mode.
button
15
zone 6
zone
11
zone
12
zone
7
zone 13
5
9
4
11
12
Stand-by dimming level
Detection range
ON/
OFFAuto ModeReset
Power
80%
Test
2s
10%20%
30s 1min
100%
30min10min5min
0s 10s1min
30%
SC1SC2
SC3
Scene mode
10min
50%10%
30min
Hold-time
Stand-by period
5min
Lux
Disable
2Lux
10Lux
50Lux
Daylight Sensor
SC4
Power
100% +
-
Dim
M/A
3
1
2
7
8
6
10
13
14
15
HRC-05
Note: the buzzer beeps one time when RC
receives signal successfully
SECTION 3 SETTINGS
This is the time period setting to keep at the low light output level before it is completely switched off in the long absence of people.
Stand-by period (corridor function)
This is the dimmed low light output level setting after the hold-time has expired.
Stand-by dimming level
The daylight threshold can be set on the DIP switches, suit to the particular application.
Daylight sensor
Detection area can be tuned by selecting the combination on the DIP switches to fit precisely for each specific application.
This setting determines the time period the lamp will remain at 100% upon detection.
Note: The timer is reset upon each motion detection.
Hold-time
Detection area
I – 100%
II – 50%
I – 0s
II – 10s
III – 1min
IV – 5min
V – 10min
VI – 30min
VII – 1h
VIII – +∞
I – Disable
II – 50Lux
III – 10Lux
IV – 2Lux
I – 10%
II – 30%
I – 5s
II – 3min
III – 10min
IV – 30min
1h
10min
30min
5min
1min
10s
8
76
+
0s
50%
100%
1
I
II
54
50Lux
10Lux
2Lux
Disable
I
II
III
IV
I
II
III
IV
V
VI
VII
VIII
30%
10%
1
I
II
32
3min
10min
30min
5s
I
II
III
IV
Note: “0s” means on/off control;
+ means bi-level control, fixture never switches off when daylight sensor is disabled.
8
Scene mode options [ ]
Note: the end-user can fine tune the settings by pressing buttons of detection range / hold time / stand-by period / stand-by dimming level
/daylight sensor , the last setting will over-write that feature of the pre-set scene.
611
13
12
7
zone 4
There are 4 scene modes built into the remote control for different applications:
Scene options Detection range Hold time Stand-by period Stand-by dimming leve Daylight sensor
SC1 100% 1min 10min 10% 2Lux
SC2 100% 5min 10min 10% 2Lux
SC3 100% 10min 30min 10% 10Lux
SC4 100% 10min + 10% 50Lux
8
SECTION 5 TROUBLE SHOOTING
SECTION 4 FUNCTIONS
4.1 Zero-cross Relay Operation
4.2 Synchronization Function
4.3 Manual Override
4.4 Absence Detection Function
4.5 Daylight Monitoring Function
Designed in the software, the sensor switches on/off the load right at the zero-cross point, to ensure the in-rush current is minimised, enabling the
maximum life-time of the relay.
Note: if the surrounding natural light of the sensor which detects movement is sufficient,all lights in the group will remain off.
By connecting the “SYNC” terminals in parallel (maximum 10pcs, see wiring diagram), no matter which sensor detects motion, all HC419VRC/R in
the group will turn on the lights when surrounding natural light is below the daylight threshold. The sensor antenna is shared and the detection
area could be widely enlarged in this way. Other settings such as hold-time, stand-by period, stand-by dimming level and daylight threshold on
each individual unit stay the same.
The motion sensor is employed, but only activated on the maunal press of the push switch, light will remain on in presence, and dimmed down in
the absence, and eventually switch off automatically in the long absence.
Hytronik specially designed this function in software for deep energy-saving purpose. A built-in daylight sensor is designed to provide a “smart
photocell” function. This function can only be activated when stand-by period is set to “+∞”. In this mode the lamp will automatically illuminate at the
dim level setting when the natural light goes below the threshold setting. The fixture will also switch off as the natural light returns.
This sensor maybe over-ridden by the end-users to switch on/off the lights manually, or adjust the maximum brightness during motion hold-time
with the push-switch. This makes the product more user-friendly and offers more options to fit for extra-ordinary demands.
* Short push (<1s): on/off function;
ON → OFF: the light turns off immediately and cannot be lighten for a certain time (equals to hold time preset) even there is movement is
detected. After this period, the sensor goes back to auto sensor mode.
OFF → ON: the light turns on 100% and goes to auto sensor mode, even when ambient Lux level exceeds the daylight threshold.
* Long push (>1s): adjust the maximum brightness (between 10% and 100%) during hold-time. Both the settings on DIP switch and manual
override can overwrite each other, the latest action controls.
* If no end-user adjustment is desired, simply leave this terminal disconnected.
MALFUNCTION CAUSE REMEDY CAUSE REMEDY
The light will not come on
The lamp is always on
The lamp will not work
despite movement Check detection area setting
The lamp is on without any
identifiable movement
Incorrect light-control setting selected
Continuous movement in the detection zone
The sensor is not mounted for reliably
detecting movement
Movement occurred, but not identified by the
sensor (Movement behind wall, movement of
small object in immediate lamp vicinity etc.)
Rapid movements are being suppressed to
minimize malfunctioning or the detection
radius is too small.
Faulty lamp
No power supply
Adjust daylight threshold setting
Replace lamp
Check power to sensor
Check detection area setting
Securely mount enclosure
1. Reduce sensitivity.
2. Check the movement behind
walls to avoid facilities such as
water pipe, fan, which may
mis-trigger the sensor.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Hytronik HC419VRC Premium Version User manual

Category
Motion detectors
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI