Hytronik HC403VRC-KD Reinforced Detached Version 1-10V Dimming Control User manual

Category
Motion detectors
Type
User manual
2. Section Installation And Wiring
1. Technical Specifications
Product Type Microwave Motion Sensor
Operating Voltage 120-277VAC 50Hz/60Hz
Hf System: 5.8GHz Cw Radar
Rated Load: 400w / 3.6a / 120v
(capacitive load) 800w / 3.6a / 230v
1000w / 3.6a / 277v
Detection Angle: 30°~150°
Power Consumption: <1w
Detection Range (dxh): Max. 12 X 6m(sam5)
Max. 12 X 6m(sam6)
Time Setting: 5s, 30s~30min.
Daylight Sensor: 2~50lux; Disable
Stand-by Period: 0s, 10s ~ 1h, +∞
Stand-by dimming level 10% ~ 50%
Mounting: Indoors,ceiling & walling mounted
Working Temp.: -20oC ~ +60oC
HC403VRC-KD-20170329-A1
Important
Please read these instructions carefully prior to installation and retain this leaflet in a known
and safe place for future reference.
SAM5
SAM6
HC403VRC-KD HRC-05
Adjustable
detection area Buzzer
Hold-time
Stand-by period
Stand-by
dimming level
Sensor antenna interface
Daylight threshold
1-10V
+
Stand-by dimming level
Detection range
ON/
OFFAuto ModeReset
Power
80%
Test
2s
10%20%
30s 1min
100%
30min10min5min
0s 10s1min
30%
SC1SC2
SC3
Scene mode
10min
50%10%
30min
Hold-time
Stand-by period
5min
Lux
Disable
2Lux
10Lux
50Lux
Daylight Sensor
SC4
Power
100% +
-
Dim
M/A
The sensor is an active motion detector; it emits a high-frequency electro-magnetic wave at 5.8GHz and receives
its echo.The sensor detects the change in echo from movement in its detection zone. A microprocessor then
triggers the switch light ON command. Detection is possible through doors, panes of glass and thin walls.
Note: the high-frequency output of this sensor is <0.2mW; approximately just 0.2‰ of the transmission power of
a mobile telephone.
2.1 Ensure that the electricity supply is switched off before installing or
servicing this product.
2.2 Wiring diagram
LED Driver
LED
Installation and Instruction Manual
HF MOTION SENSOR DETACHED VERSION HC403VRC-KD
30.7
35.9
40.4
16.2
25.2
6
2.5
11.2
1.8
6.8
5
22.5
4
Drill hole 9mm x 3mm
Drill hole 9mm x 3mm
Drill hole for cable entry is 10mm x 10mm in
square shape or 12mm in round shape
option 1
option 2
Slots for T8 tube
50.2
26.5
45.2
32.2
2.5
33.5
Slots for T5 tube
26.5
50.2
15
9
2
12
33.5
Drill hole 9mm x 3mm
Drill hole 9mm x 3mm
Drill hole for cable entry is 10mm x 10mm in
square shape or 12mm in round shape
22.5
2.5
13
4
HC403VRC-KD-20170329-A1
Hytronik Industrial Ltd. | www.hytronik.com
3rd Floor, block C, complex building, 155#, Bai'gang road south,
Bo'gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023
Tel: 86-752-2772020 Fax: 86-752-2777877
3. Section Remote Control
Detection area:
Detection range can be tuned by selecting the combination on the DIP switches to fit precisely
for each specific application.
3. Section Settings
Detection area:
Detection range can be tuned by selecting the combination on the DIP switches to fit precisely
for each specific application.
I – 100%
II – 75%
III – 50%
IV – 10%
50%
75%
100%
10%
21
I
II
III
IV
I – 5S
II – 30S
III – 1min
IV – 5min
V – 10min
VI – 20min
VII – 30min
3
21
5s
30s
1min
5min
10min
20min
30min
I
II
III
IV
V
VI
VII
This setting determines the time period the lamp will remain at 100% upon detection.
Note: the timer is reset upon each motion detection.
Hold-time
I – Disable
II – 50Lux
III – 10Lux
IV – 2Lux
21
Disable
50Lux
10Lux
2Lux
I
II
III
IV
The daylight threshold can be set on the DIP switches suit to the particular application.
Daylight sensor
5
9
4
11
12
Stand-by dimming level
Detection range
ON/
OFFAuto ModeReset
Power
80%
Test
2s
10%20%
30s 1min
100%
30min10min5min
0s 10s1min
30%
SC1SC2
SC3
Scene mode
10min
50%10%
30min
Hold-time
Stand-by period
5min
Lux
Disable
2Lux
10Lux
50Lux
Daylight Sensor
SC4
Power
100% +
-
Dim
M/A
3
1
2
7
8
6
10
13
14
15
HRC-05
Note: the buzzer beeps one time when RC receives signal successfully
Permanent ON/OFF [ ]
1. Press button , to select permanent ON or permanent OFF mode.
2. Press button to resume automatic operation. (Please refer to explanation below)
1
234
button 1
Auto Mode [ ]
2
button 2
Press button to in initiate automatic mode. The sensor starts working and all settings remain as
before the light was switched ON/OFF.
RESET [ ]
Press button , all settings go back to the value of DIP switch settings.
3
button 3
Test 2s function [ ]
1.Press button ,the sensor goes into testmode (hold time2s). N.B. the stand-by period and daylight
sensor settings are disabled in test mode.
8
2.Press button to exit from this mode, and the sensor settings are changed accordingly.
3 4
11
button 8
10
Ambient daylight threshold [ ]
Press button , the latest surrounding lux value overwrites previous lux value learned, and is set as the
daylight threshold. This feature enables the fixture to function well in any environment.
button
10
Power output [ ]
Press button , the output shifts between 80% and 100%, for energy saving purposes.
5
button
5
Dim +/- [ ]
Press button to adjust the light brightness between 10%~100% during hold-time.“+” increases the
light level, “-” will decrease the light level.
9
button 9
Lux disable [ ]
Press button , the built-in daylight sensor is disabled, the light will always operate upon detection
regardless of ambient light level.
14
button
14
Note: this button is disabled.
M/A [ ]
button
15
Detection range[ ]
Press buttons in zone to set detection range at 100% / 50% / 10%.
6
zone 6
Hold time [ ]
Press buttons in zone to set hold time at 30s / 1min / 5min / 10min / 30min.
11
zone
11
Stand-by period[ ]
Press buttons in zone to set the stand-by period at 0s / 10s / 1min / 10min / 30min / +∞.
Note: “0s” means on/off control; “+∞” means bi-leve of dimming control, the light will never switch off.
(i.e. the light remains at the stand-by dimming level until motion is detected.)
12
zone
12
Stand-by dimming level [ ]
Press buttons in zone to set the stand-by dimming level at 10% / 20% / 30% .
7
zone
7
Daylight sensor [ ]
Press buttons in zone to set daylight sensor at 2lux / 10lux / 50lux.
13
zone 13
Scene mode options [ ]
zone 4
There are 4 scene modes built into the remote control for different applications:
SC1 100% 1min 10min 10%
SC2 100% 5min 10min 10%
SC3 100% 10min 30min 10%
SC4 100% 10min +∞ 10%
Scene
options
Detection
range
Hold
time
Stand-by
period
Stand-by
dimming leve
Daylight
sensor
2Lux
2Lux
10Lux
50Lux
Note: the end-user can fine tune the settings by pressing buttons of detection range / hold time /
stand-by period / stand-by dimming level /daylight sensor , the last setting will over-write
that feature of the pre-set scene.
611
13
12
7
4. Section Functions
HC403VRC-KD-20170329-A1
Hytronik Industrial Ltd. | www.hytronik.com
3rd Floor, block C, complex building, 155#, Bai'gang road south,
Bo'gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023
Tel: 86-752-2772020 Fax: 86-752-2777877
Note: “Os” means on/off control;“+”means bi-level dimming control, fixture never switches off when
daylight sensor is disabled.
This is the dimmed low light output level setting after the hold-time has expired.
Stand-by dimming level
I – 10%
II – 20%
III – 30%
IV – 50% 30%
20%
10%
50%
21
I
II
III
IV
The light will not come on
The lamp is always on
The lamp is on without any
identifiable movement
The lamp will not work
despite movement
Incorrect light-control setting
selected
Faulty lamp
No power supply
Continuous movement in the
detection zone
The sensor is not mounted for
reliably detecting movement
Movement occurred, but not
identified by the sensor (Movem
ent behind wall, movement of
small object in immediate lamp
vicinity etc.)
Rapid movements are being supp
ressed to minimize malfunctioning
or the detection radius is too small.
5. Section Trouble Shooting
Cause Remedy
Malfunction Cause
Remedy
Adjust daylight threshold
setting
Replace lamp
Check power to sensor
Check detection area
setting
Securely mount enclosure
1. Reduce sensitivity.
2. Check the movement
behind walls to avoid
facilities such as water
pipe, fan, which may
mis-trigger the sensor.
Check detection area
settingng
I – 0s
II – 10s
III – 1min
IV – 5min
V – 10min
VI – 30min
VII – 1h
VIII – +
10s
1min
5min
10min
30min
1h
3
21
+
0s
I
II
III
IV
V
VI
VII
VIII
This is the time period setting to keep at the low light output level before it is completely switched off in
the long absence of people.
Stand-by period (corridor function)
Double L N terminal makes it easy for wire loop-in and loop-out, and saves the cost of terminal block
and assembly time.
4.3 Loop-in and Loop-out Terminal
4.1 Zero-cross Relay Operation
Designed in the software, the sensor switches on/off the load right at the zero-cross point, to ensure
the in-rush current is minimised, enabling the maximum life-time of the relay.
4.2 Daylight Monitoring Function
Hytronik specially designed this function in software for deep energy-saving purpose. A built-in
daylight sensor is designed to provide “smart photocell” function. This function can only be activated
when stand-by period is set to “+∞”. In this mode the lamp will automatically illuminate at the dim
level setting when the natural light goes below the threshold setting. The fixture will also switch off
as the natural light returns.
  • Page 1 1
  • Page 2 2
  • Page 3 3

Hytronik HC403VRC-KD Reinforced Detached Version 1-10V Dimming Control User manual

Category
Motion detectors
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI