Panel Division 888-852-2778 INHINBC 071301
CAUTION: When the panel cover is
open, power to the panel must be off
at all times to avoid exposure to the
line-voltage wiring. If you remove the
cover while the panel is powered up,
use extreme caution. Do not touch
any wiring, particularly outside the
interior’s low-voltage barrier.
EMERGENCY SERVICE OR SUPPORT:
888-852-2778
Troubleshooting
If no relays respond to switches …
Check the power supply LEDs. If they
are off, check:
1.the power supply plug-in connection to
the motherboard terminal J1
2.the power feed circuit to the power
supply
If they are still off …
Replace the power supply.
If an individual relay does not
respond …
Remove the switch connections and
check the relay operation directly with a
jumper.
If it still does not work …
Turn off all power to the panel and
replace the defective relay.
Check power supply LEDs. Both should be on.
Test the relay. If defective, replace.
Relay Output Ratings
Both General Electric* RR7P/RR9P and
Reliant Relay* H2R7P/H2R9P relays
may be installed in The Watt Stopper
interiors, including those listed herein.
The GE R7P/RR9P relay output power
contacts are rated as follows:
20A Tungsten, 125VAC
20A Ballast, 277VAC
20A Resistive, 277VAC
1
⁄2HP @ 110-125VAC
1
1
⁄2HP@ 220-277VAC
The Reliant Relay H2R7P/H2R9P relay
output contacts are rated as follows:
20A Tungsten
20A Ballast
20A General use
1HP @ 120VAC, 50-60Hz
Compatibility with GE Total Lighting
Control enclosures
All Watt Stopper interiors are fully
compatible with respective GE tubs,
covers and power supplies as defined in
the table below. All Watt Stopper
warranties apply whether the interior is
used in a Watt Stopper or General
Electric enclosure.
The Watt Compatible Compatible
Stopper GE Tub/Cover GE Power
Cat.# Cat.# Supply Cat.#
HINxxy12BC RTUB12/RCOV12xx RPWRxxx
HINxxy24BC RTUB24/RCOV24xx RPWRxxx
HINxxy48BC RTUB48/RCOV48xx RPWRxxx
In Watt Stopper interiors, the xx stands for the number of
installed relays and the y indicates the type: G for General
Electric or R for Reliant Relay.
* All trademarks are the property of the respective parties.
HINxxy12BC/24BC/48BC Lighting Control Panel Interior — Installation and Setup
Note: The view shown above is of a Complete
Control lighting panel interior. It is representative of
Basic Control troubleshooting.