ICP DAS USA I-2532 is a high-quality CAN to Fiber Converter that provides a reliable and efficient way to convert electrical CAN bus signals to fiber optic cables. With a transmission distance of up to 1.4 kilometers, the I-2532 is perfect for applications that require long-distance communication. The device supports a wide range of baud rates, making it compatible with most CAN networks. Additionally, the I-2532 is equipped with LED indicators that provide visual feedback on the status of the device. This makes it easy to troubleshoot any issues that may arise.

ICP DAS USA I-2532 is a high-quality CAN to Fiber Converter that provides a reliable and efficient way to convert electrical CAN bus signals to fiber optic cables. With a transmission distance of up to 1.4 kilometers, the I-2532 is perfect for applications that require long-distance communication. The device supports a wide range of baud rates, making it compatible with most CAN networks. Additionally, the I-2532 is equipped with LED indicators that provide visual feedback on the status of the device. This makes it easy to troubleshoot any issues that may arise.

I-2532 CAN to Fiber Converter Quick Start User Guide (ver. 1.1, 2008/10/03) -----1
Quick Start User Guide
1. Introduction
Fiber optic transmission medium is a good material to protect data
transmission from EMI/RFI interference and has been used in harsh
environment extensively. CAN bus is famous in industrial application.
More and more users build CAN networks to communicate their
controllers, sensors and actuators. In order to solve the problem between
different transmission medium, I-2532 is specially designed for converting
the electrical CAN bus signal to fiber optic cables.
The fiber length between two I-2532s can be up to 1.4km (4593ft), it is
mainly decided by the cable attenuation of fiber and the CAN bus baud. I-
2532 is the economic solution for applications which require protecting the
data transmission from electrical exposure, surges, lightning or chemical
corrosion. Generally, I-2532 can be used in CANopen, DeviceNet and all
the other CAN network which follows the ISO 11898-2 standard.
This quick-start describes how to implement the I-2532 module into
users’ applications in a quick and easy way. Therefore, it only provides the
basic concepts. If users want to know more detail information about the I-
2532, please refer to the user manual of I-2532 in the product CD or visit
our website as follows:
http://www.icpdas.com/products/Remote_IO/can_bus/i-2532.htm
The I-2532 CAN to Fiber Converter
I-2532
CAN Device
CAN Device
CAN Device
Fiber
Up to 1.4 Km
I-2532
CAN Device
62.5/125 µm multimode Fiber
Cable Attenuation of Fiber < 2.8 dB/Km
ISO 11898-2ISO 11898-2
I-2532 CAN to Fiber Converter Quick Start User Guide (ver. 1.1, 2008/10/03) -----2
2. Appearance
The following figure is the appearance of the I-2532.
3. Pin Assignment
Port Name Description
CAN_L CAN_Low, signal line of CAN Port.
CAN_H CAN_High, signal line of CAN Port.
CAN
CAN_GND
CAN_Ground, ground voltage level of CAN Port.
TXD Transmit data to fiber optic cable.
Fiber
RXD Receive data from fiber optic cable.
+VS Voltage Source Input. +10V
DC
~ +30V
DC.
GND Power Ground.
Power
F.G. Frame Ground.
LED Indicators
Front View Bottom View
Terminal Resistance Switch
Fiber Port
CAN Port
CAN_H
CAN_GND
CAN_L
N/A
1
2
3
4
5
6
7
8
RxD
TxD
POWER
TD
RD
F.G.
GND
+VS
T.R.
active
T.R.
inactive
Power Port
ISO 11898-2 standard
Connector Type: ST
Operating Wavelength: 850nm
Fiber Type:
Multi-Mode, 62.5/125µm
+10 ~ +30VDC between
GND and +VS
I-2532 CAN to Fiber Converter Quick Start User Guide (ver. 1.1, 2008/10/03) -----3
4. LED Indicators & Terminal Resistance
The table below shows the meanings of LED indicators on the I-2532.
Transmitting/receiving one message to/from fiber cable will flash the
TD/RD LED once. The TD/RD LED may always be turned on if there are
a lot of messages transmitted on fiber cable.
POWER LED
(Red Light)
TD LED
(Green Light)
RD LED
(Green Light)
on
module
active
flashing
messages
transmitting
flashing
messages
receiving
off
module
inactive
off
no message
transmitting
off
no message
receiving
The switch at bottom of I-2532 is used for adjusting terminal
resistance (120) on CAN Port. The switch functions are shown below.
5. Wire Connection
Roughly speaking, wiring of CAN_GND and FG can improve the
capability of anti-interference of CAN bus system, but this is not necessary.
CAN_H
CAN_L
CAN_GND
Earth Ground
Power GND
+10VDC ~ +30VDC
CAN_H
CAN_L
CAN_GND
Earth Ground
Power GND
+10VDC ~ +30VDC
Tx Tx
Rx Rx
Fiber
Metallic
Board
Interconnecting
ISO 11898-2 ISO 11898-2
Active
(Enable)
Inactive
(Disable)
I-2532 CAN to Fiber Converter Quick Start User Guide (ver. 1.1, 2008/10/03) -----4
6. Bus Length & Fiber Length
Higher attenuation of fiber will reduce the transmission distance. Users
can use following table to know the relationship between those two.
Attenuation [dB/km] Ideal Fiber Length [m]
2.8 <1400
4 <400
The limitation of baud on a CAN network is restricted by propagation
delay. On the other hand, long bus length leads to long propagation delay.
The relationship between baud and bus length is displayed below.
Baud [bit/sec] Ideal Bus Length [m]
500K < 100
250K < 250
125K < 500
50K < 1000
20K < 2500
10K < 5000
The definition of segments the relationship between segment length
(L
SEG1
, L
SEG2
…) and bus length (L
BUS
) in the same CAN bus system are
shown in the following figure.
When users add one pair of I-2532 into a CAN bus system, the ideal
bus length will reduce 50 meters because the propagation delay of one I-
2532 is equal to the propagation delay caused by 25 meters bus length.
For example, if users use baud 50Kbps and add two I-2532s into the CAN
network, the ideal bus length should less than 950 meters (1000-
25*2=950).
Fiber
I-2532 I-2532
ISO 11898-2ISO 11898-2
L
seg1
L
seg2
L
seg3
L
BUS
= L
seg1
+ L
seg2
+ L
seg3
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

ICP I-2532 User manual

Category
Network switches
Type
User manual

ICP DAS USA I-2532 is a high-quality CAN to Fiber Converter that provides a reliable and efficient way to convert electrical CAN bus signals to fiber optic cables. With a transmission distance of up to 1.4 kilometers, the I-2532 is perfect for applications that require long-distance communication. The device supports a wide range of baud rates, making it compatible with most CAN networks. Additionally, the I-2532 is equipped with LED indicators that provide visual feedback on the status of the device. This makes it easy to troubleshoot any issues that may arise.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI