BC-HSP VI.73.K1.02 Danfoss 6/92 7
g) Min. boiler temperature
The boiler temperature can be set within
a range of 10-70 °C. The factory setting
is 10 °C, however, the min. allowable
boiler temperature is to be set according
to the boiler manufactorer instructions.
h) Boiler temperature difference
Fixed difference
Set the fixed difference between the start
and stop temperatures within the range
2-20 K.
Automatic difference (AUTO)
Set potentiometer in position AUTO and
start and stop temperature will be
automatically adapted to the boiler type
and system load. This function is suitable
for low thermal capacity boilers (reduces
the start/stop frequency). The factory
setting is 12 K, however the setting is to
follow the boiler manufactorer instruc-
tions.
h) Setting reduced temperature level
The reduced temperature level can be
set at a fixed value (1-8) or at an
outdoor-temperature-dependent value
(AUTO). The basic setting for reduced
temperature is 5. Each graduation on the
scale corresponds to about 1 degree in
the room.
Reduced temperature
The scale shows room temperature drop
during reduced temperature period.
Different settings are given (–2, –4, –6,
–8 and AUTO).
If no room sensor is used, the control
calculates the parallel displacement to
give the set room temperature drop.
j) Setting the hot water service
temperature
The hot water service temperature can
be set with potentiometer j) within
30-70 °C.
The basic setting is 50 °C.
Time control of hot water service circuit
A 2-channel digital clock or a control
panel ECA 9020 - channel 3 can time
control the hot water service circuit. The
hot water service temperature is reduced
to 10 °C at reduced operation.