WEG SCA06 User manual

Type
User manual
Motors | Automation | Energy | Transmission & Distribution | Coatings
Servo Drive
Servoconvertidor
Servoconversor
SCA06 - STO Option Board
User’s Manual
Manual del Usuario
Manual do Usuário
Safety Manual
Series: SCA06
Document: 10004016577 / 01
Models: 4 A / 220 ... 230 V single-phase
5 A / 220 ... 230 V three-phase
8 A / 220 ... 230 V three-phase
16 A / 220 ... 230 V three-phase
24 A / 220 ... 230 V three-phase
5.3 A / 380 ... 480 V three-phase
14 A / 380 ... 480 V three-phase
Date: 07/2016
English
English
4 | SCA06
Summary of Revisions
Version Revision Description
- R00 First edition
- R01 General review
Summary
English
English
1 APPROVALS ......................................................................................... 7
2 GENERAL INFORMATION ................................................................ 10
2.1 ABOUT THE MANUAL ............................................................................. 10
2.2 PRELIMINARY RECOMMENDATIONS ................................................. 10
2.3 SAFE TORQUE OFF ................................................................................ 11
3 INSTALLATION .................................................................................. 13
3.1 TYPES OF INSTALLATION ...................................................................... 16
4 COMMISSIONING ............................................................................. 18
5 MAINTENANCE ................................................................................. 19
6 DECOMMISSIONING ........................................................................ 21
7 SAFETY DATA ....................................................................................22
English
English
SCA06 | 7
Approvals
English
English
1 APPROVALS
EC DECLARATION OF CONFORMITY
Manufacturer’s name:
WEG Drives & Controls - Automação Ltda.
Manufacturer’s address:
Avenida Prefeito Waldemar Grubba, 3000
Jaraguá do Sul - SC - Brazil
89256-900
And our representative established within the European Community:
WEG Germany GmbH
Industriegebiet Türnich 3, Geigerstraße 7, 50169
Kerpen Türnich - North Rhine-Westphalia
Germany
We hereby declare that the safety functions of the following product
Product Name:
SSC 1.00 option board to be used with WEG SCA06 family products
Product Identification:
10859533 - CARTÃO ELETRÔNICO SSC1.00
Product Safety Functions:
Safe Torque Off according to EN 61800-5-2 standard
fulfills all of the relevant safety component requirements of Machinery Directive,
2006/42/EC.
Notified body that carried out the EC type examination:
01/205/5493.00/16
NB-No.: 0035
V Rheinland Industrie Service GmbH
Alboinstr. 56
12103 Berlin / Germany
The following standards and/or technical specifications referenced below were used:
IEC 61508 - 1 to 7: 2010
Functional safety of electrical/electronic/programmable electronic safety-related
systems
EN 61800-3:2004+A1:2011
Adjustable speed electrical power drive systems
Part 3: EMC requirements and specific test methods
EN 61800-5-1: 2007
Adjustable speed electrical power drive systems
Part 5: Safety requirements / Section 1: Electrical, thermal and energy
8 | SCA06
Approvals
English
English
EN 61800-5-2: 2007
Adjustable speed electrical power drive systems
Part 5: Safety Requirements / Section 2: Functional
EN ISO 13849-1: 2008 + AC:2009
Safety of machinery – Safety-related parts of control systems
Part 1: General principles for design
EN ISO 13849-2:2012
Safety of machinery – Safety related parts of control systems
Part 2: Validation
EN 60204-1: 2006 + A1:2009 + AC:2010
Safety of machinery – Electrical equipment of machines
Part 1: General requirements
EN 62061: 2005 + AC:2010 + A1:2013
Safety of machinery – Functional safety of safety-related electrical, electronic and
programmable control systems
IEC 61326-3-1
Electrical equipment for measurement, control and laboratory use – EMC requirements
Part 3-1: Immunity requirements for safety-related systems and for equipment intended
to perform safety-related functions (functional safety) – General industrial applications
EN 50178: 1997
Electronic equipment for use in power installations
UL 508C: 2004
Power Conversion Equipment
Signature
In Jaraguá do Sul, 29
th
of January, 2016.
Norton Petry
R&D Manager
SCA06 | 9
Approvals
English
English
10 | SCA06
General Information
English
2 GENERAL INFORMATION
NOTE!
These are the original instructions.
2.1 ABOUT THE MANUAL
This manual provides the necessary information to install and configure the Safety
Function Safe Torque Off of the SCA06 servodrive. This manual must be used together
with the User’s Manual and the Programming Manual of the SCA06 servodrive.
For further details about the installation, how to perform commissioning, technical
characteristics and how to identify and fix the most common problems of the SCA06
servodrive, refer to the User’s Manual.
For information about programming the SCA06, refer to the Programming Manual.
All manuals are available for download on WEG website – www.weg.net.
2.2 PRELIMINARY RECOMMENDATIONS
DANGER!
Only duly qualified personnel, familiar with Functional Safety, with
the SCA06 servodrive and related equipment must plan or perform
the installation, commissioning, operation and maintenance of this
equipment.
The personnel must follow the safety instructions described in this
manual and/or defined by local standards.
The noncompliance with the safety instructions may result in
deathrisk and/or equipment damage.
NOTE!
For the purposes of this manual, qualified personnel are those trained
in order to be able to:
1. Install, ground, power up and operate the SCA06 in accordance with
this manual and the safety legal procedures in force;
2. Use the protective equipment according to the relevant standards;
3. Give first aid.
SCA06 | 11
General Information
English
DANGER!
Always disconnect the general power supply before touching any
electrical component associated to the servodrive.
Many components may remain charged with high voltages and/or
moving (fans), even after the AC power supply input is disconnected
or turned off.
Wait for at least ten minutes so as to guarantee the full discharge
of the capacitors.
Always connect the frame of the equipment to the protection
grounding (PE) at the proper point.
ATTENTION!
The electronic boards have components sensitive to electrostatic
discharges. Do not touch directly the components or connectors.
If necessary, first touch the grounded metallic frame or use proper
grounding strap.
2.3 SAFE TORQUE OFF
The SCA06 servodrive can be equipped with a redundant dual channel Safe Torque
Off (STO) function.
The STO function acts on the removal of torque from the motor, i.e., no power that can
cause torque is present on the motor after enabling the Safe Torque Off function. The
difference of the Safe Torque Off function from a normal way to disable the motor is
that the first one does it with very high levels of reliability against unexpected motor
starts, even under a fault condition. For this reason, it is allowed to be used where safety
must be guaranteed. See safety specifications presented at the end of this chapter.
Once activated, the STO function removes the power from the electronics, causing
the motor to coast due to the load inertia. See Figure 2.1 on page 12.
ATTENTION!
While the Safe Torque Off mode is activated, hazardous voltages may
still be present on the motor. Before any intervention on electrical parts,
the whole system must be deenergized.
ATTENTION!
In circumstances where external influences, e.g., falling of suspended
loads are present, additional measures like mechanical brakes, for
example, may be necessary to prevent any hazard.
A risk analysis must be performed by the end user in order to identify
and cover all possible risks and hazards.
12 | SCA06
General Information
English
t
STO
Motor
speed
Figure 2.1: Safe Torque Off behavior
NOTE!
The Safety of whole system depends on the final certification of
the equipment/safety function where the servodrive is applied. This
certification is responsibility of the final equipment manufacturer. WEG
is not liable for damage and/or losses due to the use or application of
the servodrive. For the same reasons, WEG is not liable for applications
based on figures and examples described in this manual, which are
presented for illustrative purposes only.
NOTE!
This function should not be used as a control for starting and/or
stopping the motor.
NOTE!
The Safe Torque Off function takes priority over all other functions of
the servodrive.
SCA06 | 13
Installation
English
3 INSTALLATION
The servodrive must be installed according to the instructions of the SCA06 User’s
Manual.
If pollution degree 2 cannot be guaranteed, IP54 protection class must be used.
The connections of the Safety signals are made at connector X7, located at the bottom
of the servodrive, according to Figure 3.1 on page 13 and Figure 3.2 on page 14.
Additionally, the type of safety signals coming from the installation must be chosen at
a Dip Switch. See location at Figure 3.1 on page 13. The Dip Switch must be set
before energization, according to the description below:
“D” for Dry Contact devices, i.e., all devices that have electromechanical output
contacts, like relays.
“O” for OSSD (Output Signal Switching Device), i.e., devices that have outputs
containing test pulses.
NOTE!
The 24 Vdc power supply must attend Low Voltage Directive (2006/95/
EC), applying the specifications of IEC 61131-2:2007, Programmable
controllers - Part 2: Equipment requirements and tests and must attend
one of the following specifications:
Safety extra-low voltage (SELV) type, according to EN60950.
Protected extra-low voltage (PELV) type, according to EN60204.
The minimum installation necessary to operate the safety function is shown at Figure
3.3 on page 15.
Figure 3.1: X7 connector and OSSD selector
14 | SCA06
Installation
English
Tabl e 3.1: Dry Contact / OSSD selector
Dip Switch Configuration Description
Both switches set to Dry Contact. This configuration must
be chosen when the safety signals are commanded by dry
contacts, for example, relay contacts, as shown on Figure 3.4
on page 16
One switch set to “D” (Dry contact) and another set to “O”
(OSSD). This is a not valid combination and results on a Fault
state (F0160) shown by the servodrive after energization. The
servodrive will not work
One switch set to “D” (Dry contact) and another set to “O”
(OSSD). This is a not valid combination and results on a Fault
state (F0160) shown by the servodrive after energization. The
servodrive will not work
Both switches set to OSSD. This configuration must be chosen
when the safety signals are commanded by OSSD (Output
Signal Switching Device), for example, safety relays, as shown
on Figure 3.5 on page 17
X7
1
3
5
2
4
6
Pin Name Description
1 GND Reference for +24Vdc PELV/SELV supply
2 STO2 Safety input n°2
3 SP2 Safety signal for STO2 input
4 STO1 Safety input n°1
5 SP1 Safety signal for STO1 input
6 +24Vdc
+24Vdc PELV/SELV supply, provided by the
customer.
Provided by the customer
Figure 3.2: X7 connector description
SCA06 | 15
Installation
English
For X7 control cabling consider the following:
Wire stripping length: 6.0 mm (0.236 in).
Wire gauge from 0.5 mm² (20 AWG) to 1.0 mm² (16 AWG).
Screw M2, maximum tightening torque of 0.20 N.m (1.8 lbf.in).
Run the cables separated from the remaining circuits (power, 110V / 220Vac
control, etc.).
AC input
3Ø
24 Vdc
PELV /
SELV
STO 1
X5
X7
STO 2
R
S
T
PE
Figure 3.3: Basic Installation
16 | SCA06
Installation
English
3.1 TYPES OF INSTALLATION
+24 Vdc
6
4
2
5
3
Safety Board
X7
1
STO1
STO2
GND
Figure 3.4: Installation using Dry Contacts
Table 3.2: Truth table for Dry contacts operation
STO1
(Contact
Between
X7:4-5
Terminals)
STO2
(Contact
Between
X7:2-3
Terminals)
Safety Stop
Function
Servodrive Behavior
Open Open
Activated
(enabled)
Servodrive remains in STO state and does
not accept commands. The servodrive
indicates “STO” on the keypad
Open Closed
Fault
Servodrive trips to Fault “F0160” if this status
lasts longer than 1 s
To reset the fault, both contacts must be at
the same status and the +24Vdc supply must
be deenergized and reenergized
Closed Open
Closed Closed Disabled Servodrive accepts commands normally
SCA06 | 17
Installation
English
Safety Board
X7
6
4
2
5
3
1
STO1
STO2
GND
Figure 3.5: Installation using OSSD signals
Table 3.3: Truth table for OSSD signals
STO1
(Voltage
Between
X7:1-4
Terminals)
STO2
(Voltage
Between
X7:1-2
Terminals)
Safety Stop
Function
Servodrive Behavior
0 V 0 V
Activated
(enabled)
Servodrive remains in STO state and does
not accept commands. The servodrive
indicates “STO” on the keypad
0 V 24 V
Fault
Servodrive trips to Fault “F0160” if this status
lasts longer than 1 s
To reset the fault, both contacts must be at
the same status and the +24Vdc supply must
be deenergized and reenergized
24 V 0 V
24 V 24 V Disabled Servodrive accepts commands normally
18 | SCA06
Commissioning
English
4 COMMISSIONING
The sequence to of commissioning is:
1) The installation is completed and according to the servodrive’s manual.
2) The Dip Switch is set according to the type of safety signals.
3) The safety signals are not present, i.e., the contacts are open or, for OSSD type
signals, 24V is not present.
4) The motor is not coupled to the machine or, if coupled, it can run in any direction
without any risk of human harm or machine damages.
5) Turn on the power stage (Three-phase input). The led “power on” is set.
6) Turn on the electronics power supply (24Vdc power supply). The Human-machine
interface of the SCA06 turns on.
7) Program the servodrive according to the product programming manual and the
application necessity. At the end, enable the motor, via P0099 parameter, digital
input or communication network and check if the motor is running.
8) Enter the Safe State by opening STO1 and STO2 contacts or removing STO1 and
STO2 signals simultaneously. See Figure 3.4 on page 16 and Figure 3.5 on
page 17.
9) Check if the motor coasts to stop.
10) Check if the message “STO” is shown at the servodrives display.
11) Stop the Safe State by closing STO1 and STO2 contacts or replacing STO1 and
STO2 signals simultaneously. See Figure 3.4 on page 16 and Figure 3.5 on
page 17.
12) Check if the motor restarts. Depending on the programmed parameters, maybe
necessary to enable the motor again.
13) Check all other machine functionalities in order to verify the correct working and
safety parameters of the machine.
NOTE!
In order to verify the complete machine or system working and safety,
other steps may be necessary. The presented steps are the minimum
necessary to verify the integrity of the servodrive’s safety function.
The machine manufacturer is responsible for the final verification and
certification of the safety of the machine or system where the servodrive
is applied.
NOTE!
Simultaneously activation of the STO inputs means that the time between
the activation or deactivation of the inputs must be less than 1 s. This
time is also known as discrepancy time. If the time is longer than 1 s,
a fault code “F0160” will be shown on the display of the product. To
reset the fault code, it is necessary to set the STO switches to the same
state and then turn off the 24 Vdc power supply of the servodrive and
turn it on again.
NOTE!
Test pulses present at OSSD outputs are tolerated and do not trigger
the STO function since they do not last more than 1 ms.
SCA06 | 19
Maintenance
English
5 MAINTENANCE
The servodrive is equipped with several self-diagnosis functions and messages on
it display to help the user to identify abnormalities and problems with the servodrive
or it installation.
The Safe Torque Off function, in special, is equipped with a very accurate self-diagnosis
circuit, which guarantees that even under a fault, the safety is not affected. Faults
in the safety installation are reported as “F0160”. This includes also some external
misconnections of the safety signals.
Examples of external faults that may cause the Fault “F0160:
Discrepancy time between STO inputs higher than 1 s.
One of the STO inputs is not operating, i.e., closing or opening when commanded.
One of the STO signals has a Stuck-at fault.
The STO signals are short-circuited.
There is a misconnection at the connector X7. See Figure 3.4 on page 16 and
Figure 3.5 on page 17.
If the Fault “F0160” is shown at the servodrive’s display and no external faults can be
identified, than is possible that there is an internal fault on the Safety Board. In this
case, the servodrive must be submitted to Service. Contact your local WEG supplier
to get information on how to proceed.
NOTE!
If a fault on the servodrive is identified, it shall be submitted only to a
WEG Service center. Never try to fix or allow a person non authorized
by WEG to fix the servodrive. In the same way, do not use spare parts
to repair the product. The safety of the product depends not only on
values of components but also on type and quality of the components
used. The safety guarantee of the product is automatically lost if any
violation of the product occurs.
NOTE!
The Functional Safety circuits of the SCA06 were designed in such a
way that no maintenance or regular tests are necessary. The circuit
checks itself at determined intervals and the servodrive informs if any
problem is detected. Additionally, if a malfunction occurs, the safety
circuits are designed in such a way that it fails in a safe way.
20 | SCA06
Maintenance
English
NOTE!
In case of maintenance of the machine or system, the complete safety
of the machine must be retested in order to check the integrity of safety
of the machine or system.
Additionally, in case of a change or modification, the validation of the
safety function must be repeated and documented.
ATTENTION!
If, during the activation of the Safe Torque Off, occurs a simultaneous
fault on two or more IGBTs of the servodrive, the servodrive can deliver
sufficient energy to cause a magnetic alignment of the rotor and the
internal magnetic poles of the motor. This movement can be up to a
maximum of 180° of the motor shaft, depending on the number of
poles of the motor. Be sure that this movement cannot cause harm to
people or damages to machinery.
SCA06 | 21
Decommissioning
English
6 DECOMMISSIONING
For decommissioning, the machine or system shall preferably be switched off from
any type of energy supply. If this is not possible, all electrical connections, i.e, power
connections and the control connections of the servodrive must be switched off
before any decommissioning activities on the servodrive.
DANGER!
After switching off the power connections of the servodrive, it may
remain loaded with high voltages and/or moving (fans), even after the
mains power supply and the 24 Vdc power supply are disconnected
or turned off. Wait for at least 10 minutes in order to guarantee the
full discharge of internal components. Additionally, the “POWER” led,
located on the front part of the servodrive, can be monitored visually
to certify that the DC Link capacitors are discharged.
DANGER!
Before decommissioning, it is necessary to make an analysis of the
safety of the machine or system during decommissioning. Hanging
loads, brakes or rotating parts may require energy to stay in safe state
and the power removal can lead to unsafe conditions. Be sure that
power removal can be realized in a safe way.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66

WEG SCA06 User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI

in other languages