Satec AX-8 User manual

Type
User manual
AX
-
8
Analog Expander
Installation
and Operation
Manual
BG0259 Rev. A6
AX-8 Analog Expander
Installation and
Operation Manual
LIMITED WARRANTY
The manufacturer offers the customer a 24-month functional warranty on the
instrument for faulty workmanship or parts from date of dispatch from the
distributor. In all cases, this warranty is valid for 36 months from the date of
production. This warranty is on a return to factory basis.
The manufacturer does not accept liability for any damage caused by
instrument malfunction. The manufacturer accepts no responsibility for the
suitability of the instrument to the application for which it was purchased.
Failure to install, set up or operate the instrument according to the instructions
herein will void the warranty.
Your instrument may be opened only by a duly authorized representative of the
manufacturer. The unit should only be opened in a fully anti-static environment.
Failure to do so may damage the electronic components and will void the warranty.
NOTE
The greatest care has been taken to manufacture and calibrate your
equipment. However, these instructions do not cover all possible contingencies
that may arise during installation, operation or maintenance, and all details and
variations of this equipment are not covered by these instructions.
For additional information regarding installation, operation or maintenance of
this equipment, contact the manufacturer or your local representative or
distributor.
IMPORTANT
) Ensure that all incoming AC power and other power sources are turned
OFF before performing any work on the unit. Failure to do so may result in
serious or even fatal injury and/or equipment damage.
) Before connecting the unit to the power source, check the label on the rear
to ensure that your unit is equipped with the appropriate power supply.
) Do not connect the unit to a power source if it is damaged.
) Do not expose the unit to rain or moisture.
) Read this manual thoroughly before connecting the unit.
Table of Contents
1 Introduction.......................................................................................... 1
2 Field Setting .........................................................................................3
2.1 Default Setting................................................................................. 3
2.2 Changing the Communication Parameters (Firmware Version 0.10) ...... 3
3 Installation............................................................................................ 5
3.1 Mechanical Installation ....................................................................5
3.2 Electrical Installation........................................................................ 6
4 Operation.............................................................................................. 9
4.1 Power Up ........................................................................................9
4.2 Communication ...............................................................................9
5 Technical Specifications.....................................................................11
BG0259 Rev A6
1
1 Introduction
1.
The AX-8 Analog Expander is an instrument that enables Powermeters to
interface with other devices that require analog signals. The AX-8 can be
connected to any Powermeter equipped with an RS-422 communication
port and analog expander option.
The AX-8 provides up to 8 analog outputs. Two units can be connected in
sequence, providing as many as 16 analog outputs with use of one
Powermeter1. For information on analog output and analog expander
setup and connections, refer to the Installation and Operation Manual of
the specific Powermeter.
Features
Accuracy - The AX-8 provides 8 or 9 bit resolution on each analog output.
Output values on all channels are updated continuously at a rate of 0.3 to
0.5 seconds, depending on the speed of communication (baud rate).
Flexibility - The analog outputs are provided with current output options
of 0-20 mA and 4-20 mA, 0-1 mA and ±1 mA , and voltage output
options of 0-10V DC and ±10V DC. Depending on the specific model of
Powermeter, a wide range of output values are user-selectable, from the
Powermeter front panel or via communications software.
Installation - DIN rail or wall mounting. No auxiliary power supply is
required; an internal switching power supply with a wide AC/DC range is
provided.
Communications - The AX-8 is connected to the Powermeter using a
twisted pair cable via the RS-422 port, using ASCII, Modbus or DNP3.0
protocols. This allows communication over a distance of up to 1000 meters
at a baud rate of up to 19,200 bps. Installation of the AX-8 does not
interfere with the inclusion of the Powermeter in a communication network
(RS-422 or RS-485) of up to 31 Powermeters.
Figure 1-1 shows a typical communication network with two AX-8
expanders.
1 If your Powermeter supports 7 (14) channels, then the AX-8 will also provide 7
(14) channels.
2
Figure 1-1 AX-8 Analog Expanders in a Typical Communication Network
Figure 2-2 AX-8 Dimensions
INPUTS (PLC)
POWERMETER POWERMETER
AX-8
POWERMETER
RS-422/RS-485 UP TO 31 POWERMETERS
00-02021
USER'S ANALOG
CURRE NT
CURRE NT
CURRE NT
L3/L3 1
KV
L1/L12
VOLTAGE
VOLTAGE
L2/L23
V
KV
V
HARMONIC ANALYZER
VOLTAGE
KV
V
RESE T
SELECT
RESE T
MAX
PAGING
ENERGY
KVARH/MVARHKA
REACTIVE ENERGYMAX.AMP.DEMAND
290H
KVAR
MVAR
MAX.DEMAND
MAX.AMP.DEMAND
MAX.AMP.DEMAND
KA
A
A
ACTIVE POWER
ACTIVE ENERGY
REACTIVE POWER
KA
A
POWER FACTOR
UNBALANCED C UR R ENT
FREQUENCY
MW
KW
KWH/MWH
MAX.DEMAND
SATEC
A
Hz
SYSTE M 290
APPARENT POWER
MVA
KVA
CURRE NT
CURRE NT
CURRE NT
L3/L3 1
KV
L1/L12
VOLTAGE
VOLTAGE
L2/L23
V
KV
V
HARMONIC AN ALYZER
VOLTAGE
KV
V
RESET
SELECT
RESET
MAX
PAGING
ENERGY
KVARH/MVARHKA
REACTIVE ENERGYMAX.AMP.DEMAND
290H
KVAR
MVAR
MAX.DEMAND
MAX.AMP.DEMAND
MAX.AMP.DEMAND
KA
A
A
ACTIVE POWER
ACTIVE ENERGY
REACTIVE POWER
KA
A
POWER FA CTOR
UNBALANCED CURRENT
FREQUENCY
MW
KW
KWH/MWH
MAX.DEMAND
SATEC
A
Hz
SYST EM 290
APPARENT POWER
MVA
KVA
CURRENT
CURRENT
CURRENT
L3/L31
KV
L1/L12
VOLTAGE
VOLTAGE
L2/L23
V
KV
V
HARMONIC ANA LYZER
VOLTAGE
KV
V
RESET
SELECT
RESET
MAX
PAGING
ENERGY
KVARH/MVARHKA
REACTIVE ENERGYMAX.AMP.DEMAND
290H
KVAR
MVAR
MAX.DEMAND
MAX.AMP.DEMAND
MAX.AMP.DEMAND
KA
A
A
ACTI VE POWE R
ACTIVE ENERGY
REACTIVE POWER
KA
A
POWER FACTOR
UNBALANCED CU RRENT
FREQUENCY
MW
KW
KWH/MWH
MAX.DEMAND
SATEC
A
Hz
SYSTEM 290
APPARENT POWER
MVA
KVA
AX-8
ADDRESS 1
ANALOG OUTPUT
OUT
IN
#2 #31
#1
ADDRESS 0
IN
ANALOG OUTPUT
ANALOG EXPANDER AX-8
ANALOG OUTPUTS
ON
POWER SUPPLY
DC
AC
+
LN
_
NETWORK
RS-422 /RS-48 5
RX
RS-422
POWER METER
TX
TXRX
++ __
RX
+_
12 534 678
RXTX RXTXRXTX
__
++ +_+_+_+_+_+_+_
POWER METER
RX
ON
TX
_
NL
+
AC
DC
POWER SUPPLY
ANALOG EXPANDER AX-8
RX
_
TX
RS-422/RS-485
NETWORK
+
TXTXRX
__
++
RX
TX
RS-422
+
RX +
_
RX
1
_
+
ANALOG OUTP UTS
+
_
+
_
+
_
4325
__
+
_
+
_
+
876
RS
RS-422 ONLY
3
2 Field Setting
2.
2.1 Default Setting
The Analog Expander is set by the dip switches S1 and S2 on the PCB
located inside the AX-8 case. The default setting is as follows:
Expander address 0
1
Analog output range factory set as per order
Protocol ASCII
Data format 8N (8 bit, no parity)
Baud rate 9600 bps
If you require a change to this setting, open the case as per Sections 2.2 -
2.4 below and change the setting.
2.2 Changing the Communication Parameters
(Firmware Version 0.10)
1. Disassemble the AX-8 case: remove the 8 screws from the
outside of the case and take off the rear cover.
2. Set the DIP switches on the PCB (see Figure 2-1) as shown in
Tables 2-1 and 2-2 below.
3. Re-assemble the case: put the rear cover back on, insert and
tighten the 8 screws.
1 This address allows use of up to 7 or 8 analog outputs, according to the analog
output setup in the Powermeter. Use of additional outputs from one Powermeter
requires installation of an additional AX-8 unit with address ‘1’.
4
Figure 2-1 Location of Dip Switches on AX-8 PCB
Table 2-1 DIP Switch S1 * = default
AX-8 Option SW1
Addr0
SW2
Addr1
SW3
Addr 2
SW4
N/A
SW5
N/A
SW6 SW7 SW8
Factory Set
Address 0 OFF OFF OFF
Address 1 ON OFF OFF
Address 2 OFF ON OFF
Address 3 ON ON OFF
Address 4 OFF OFF ON
Address 5 ON OFF ON
Address 6 OFF ON ON
Address 7 ON ON ON
Table 2-2 DIP Switch S2 (Serial Port) * = default
AX-8 Option SW1
Mode
SW2
Data
SW3
Parity
SW4
N/A
SW5
Baud 0
SW6
Baud 1
SW7
Baud 2
SW8
Baud 3
ASCII mode OFF
Binary mode
(transparent) ON
7 bit/Even parity OFF ON
8 bit/No parity ON OFF
8 bit/Even parity ON ON
110 baud OFF OFF OFF OFF
300 baud ON OFF OFF OFF
600 baud OFF ON OFF OFF
1200 baud ON ON OFF OFF
2400 baud OFF OFF ON OFF
4800 baud ON OFF ON OFF
9600 baud OFF ON ON OFF
19200 baud ON ON ON OFF
CE5
R43
R27
R29
R28
C14
R30
1
1
C204
R204
R25
R35
R38
R36
+
+15V
C18
S1
R16
R18
R14
R26
R24
1
S2
+
C13
C12
D5
U6
L3
R42
R101
R109
U102
R103
R110
R107
R108
R104
R105
C101
C102
U101
R23
D7
CE4
+
CE7
R106
D8
+
TOP PC0117 REV.A1
1
1
43
127
6
58
00-03 008
8
67534
2
1
ON
ON
5
3 Installation
3.
3.1 Mechanical Installation
The AX-8 should be mounted in a dirt-free environment away from heat
sources and high electrical fields. Mounting may be either standard DIN
rail or wall mount. Only front access is required for wiring.
4.685"
(186.0)
5.118"
(130.0)
01-05001-1
2
.992"
ANALOG EXPANDER AX-8
7.323"
(76.0)
PANEL
(36.3)
1.430"
(165.0)
6.496"
Figure 3-1 Standard DIN Rail Mounting
6
ANALOG EXPANDER AX-8
PANEL
LOCK WASHER
SCREW
Figure 3-2 Wall Mounting
3.2 Electrical Installation
For AX-8 connections to the power supply, communications and analog
outputs, see Figures 3-3 (RS-422 network) or 3-4 (RS-485 network).
IMPORTANT: It is recommended to solder the wire ends
before attaching them to the connectors.
Power Supply
Use a dedicated breaker from a proper power source, from which the unit
can be turned off. All AX-8 analog outputs are provided with an internal
power supply; no external power supply for analog outputs is required.
Communications
The AX-8 is connected on one side to the Powermeter via the RS-422
input, and from the other side, to the multi-drop communication network
via the RS422 or RS-485 output, using the ASCII, Modbus or DNP3.0
protocol.
Communications may be over a distance of up to 1000 meters and at a
baud rate of up to 19,200 bps. A twisted pair cable of 0.33mm2/22AWG is
recommended.
7
Analog Output Options
Current output options Voltage output options
0-20mA, 4-20mA 0-10V DC and ±10V DC
0-1mA, ±1mA
Loads must be connected to analog outputs 1-8 according to their polarity.
Figure 3-3 AX-8 Connections in RS-422 Network
) Be sure that all incoming AC power and other power sources
are turned OFF before performing any connections.
00-03020
+Rx
-Rx
+Tx
-Tx
COMMUN.
PORT
AX-8
#2
POWERMETER
RS-422
(IBM PC OR PLC)
MASTER
RS-422
COMMUN.
PORT
#2
RS-422
TE RMI NAL
POWERMETER
TE RMI NAL
RS-422
#31
POWERMETER
NETWORKPOWERMETER
ANALOG EXPANDER AX-8
ANALOG OUTPUTS
ON
POWER SUPPLY
DC
AC
+
LN
_
NETWORK
RS-422/RS-485
RX
RS-422
POWER METER
TX
TX RX
++ __
RX
+_
12
RXTX RXTXRXTX
__
++ +_+_+_+_+_+_+_
OR 48V DC
OR 24V DC
OR 12V DC
POWER SUPPLY
110-230V AC/DC
*
76
53421
*
*
345678
8
LOADS
R
1
#1 -Rx
-Tx
+Rx
+Tx
+Tx
+Rx
-Tx
-Rx
UP TO
2
R
+Tx
+Rx
-Tx
-Rx
-Rx
-Tx
+Rx
+Tx
-Rx
-Tx
+Rx
+Tx
TERMINATION RESISTORS
R
2
R
1
= =200-500 OHM
0.5W
5A
*as per customer order
8
Figure 3-4 AX-8 Connections in RS-485 Network
) Be sure that all incoming AC power and other power
sources are turned OFF before performing any connections.
*as per customer order
00-03021
+Rx
-Rx
+Tx
-Tx
COMMUN.
PORT
AX-8
#2
POWERMETER
RS-422/ 485
(IBM PC OR PLC)
MASTER
RS-422
COMMUN.
PORT
#2
TERMINAL
POWERMETER
TERMINAL
#31
POWERMETER
NETWORK
POWERMETER
ANALOG EXPANDER AX-8
ANALOG OUTP UTS
ON
PO WE R S U PP LY
DC
AC
+
LN
_
NETWORK
RS-422/RS-485
RX
RS-422
PO WE R M ET ER
TX
TX RX
++ __
RX
+_
12
RXTX RXTXRXTX
__
++ +_+_+_+_+_+_+_
OR 48V DC
OR 24V DC
OR 12V DC
POWER SUPPLY
110-2 30V AC/DC
*
7653421
*
*
345678
8
LOADS
R1
#1 -Rx
-Tx
+Rx
+Tx
+Tx
+Rx
-Tx
-Rx
UP TO
2
R
+Tx
+Rx
-Tx
-Rx
-Rx
-Tx
+Rx
+Tx
-Rx
-Tx
+Rx
+Tx
TERMINATION RESISTORS
R
2
R
1= =200- 500 OHM
0.5W
RS-422/ 485
RS-422/ 485
5A
9
4 Operation
4.
Refer to the Installation and Operation Manual of the specific Powermeter
for instructions on Analog Expander and communication parameters
setup.
4.1 Power Up
Close the power feed breaker; the ‘ON’ LED will light up.
4.2 Communication
When you program your powermeter to output data to external analog
outputs, the powermeter periodically updates the AX-8 analog outputs
(each 300-500 ms) via the pair of wires on the RS-422 communications
link used for transmitting data. At that time, the transmission (output) line
of the AX-8 is disconnected from the external network, while the receive
line is directly connected to the powermeter port so that the instrument is
constantly ‘listening’ to the network.
When data is requested from the powermeter by a master computer (or
controller), the powermeter instructs the AX-8 to switch the transmission
line to the external network, and then sends the response. After the
response message is sent out, the transmission line is disconnected from
the network and the powermeter continues updating the AX-8 outputs.
The AX-8 can work with different ASCII and non-ASCII network protocols.
If you use an ASCII communications protocol, set the switch #1 on the DIP
switch block S2 to OFF in order to put the AX-8 into ASCII mode. The
ASCII message frame should be ended with two characters CR/LF (ASCII
13 and 10). If you are using non-ASCII communications protocol such as
Modbus or DNP 3.0, set the switch #1 on the DIP switch block S2 to ON to
put the AX-8 into binary (transparent) mode. In this event, the AX-8 will not
decode the message frame and the transmission line is disconnected in
3.5 character time after the response message is sent out.
Indicator LEDs
The AX-8 is provided with a single Rx LED (network indication) and a pair
of Rx-Tx LEDs (Powermeter indication) which operate as shown in Figure
4-1:
10
Transmission Status LED Indication
no transmission no LEDs lit up
Powermeter to AX-8 single Rx LED (‘1’ in Figure 4-1)
flashes
RS-422: master to Powermeter Powermeter Tx LED (‘2’) flashes
Powermeter to master Powermeter Rx LED (‘3’) flashes
RS-485: master to Powermeter
Powermeter to master Powermeter Rx and Tx LEDs flash
Figure 4-1 Detail of Communication LEDs on AX-8
NETWORK
RS-422/RS-485
RX
RS -4 22
POWER METER
TX
TX RX
++ __
RX
+
RXTX RXTXRXTX
__
++
1
2
3
11
5 Technical Specifications
5.
Instrument serial
communications
RS-422
Network serial communications RS-422 / RS-485
Baud rate (bps) 110, 300, 600,1200, 2400, 4800,
9600, 19200
Inter-channel separation > 95dB
Galvanic isolation:
Power Supply
Communication
2500V rms
1000V DC
Accuracy
Temperature coefficient
±1.0% of full scale for current output
up to 2500
±2.0% of full scale for current output
from 2500 to 10000
±50ppm/°C
Resolution 8 bits
Current output Span (factory set) External
resistance
Voltage output
4-20mA
± 1mA
0-20mA
0-1mA
0-10V DC
±10V DC
up to 750
up to 10000
up to 750
up to 10000
from 1000
from 1000
Power supply ratings (factory set)
120&230 V AC
and 110&220 V DC
option 12 V DC
option 24 V DC
option 48 V DC
85 - 265V AC 50/60 Hz
and 88 - 290V DC burden 10 W
9.6 - 19 VDC
19 - 37 VDC
37 - 72 VDC
Ambient temperature Operation: -20°C to +60°C
Storage: -25°C to +80°C
Humidity 95% max. non-condensing
Enclosure Aluminum, anodized
Mounting 35 mm DIN rail or wall mount
Weight 0.6 kg (1.32 lb.)
Dimensions 186 x 75 x 109 mm (7.33 x 2.95 x
4.3 inch)
12
Technical Specifications (continued)
Standards UL File # E129258
CE-EMC: 89/336/EEC as amended by 92/31/EEC and
93/68/EEC
CE-SAFETY: 72/23/EEC as amended by 93/68/EEC and
93/465/EEC
Harmonized standards to which conformity is declared:
EN55011:1991; EN50082-1:1992; EN61010-1:1993;
A2/1995
ANSI C37.90.1 1989 Surge Withstand Capability (SWC)
ANSI C62.41 - 1991 Standard Surge
EN50081-2 Generic Emission Standard - Industrial
Environment
EN50082-2 Generic Immunity Standard - Industrial
Environment
EN55022: 1994 Class A
EN61000-4-2
ENV50140: 1983
ENV50204: 1995 (900MHz)
ENV50141: 1993
EN61000-4-4:1995
EN61000-4-8: 1993
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15

Satec AX-8 User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI