Satec PM170 User manual

Type
User manual
Series PM170
Powermeters
Communications
Manual
LIMITED WARRANTY
The manufacturer offers the customer an 24-month
functional warranty on the instrument for faulty
workmanship or parts from date of dispatch from the
distributor. In all cases, this warranty is good for 36
months from the date of production. This warranty is on a
return to factory basis.
The manufacturer does not accept liability for any damage
caused by instrument malfunction. The manufacturer
accepts no responsibility for the suitability of the
instrument to the application for which it was purchased.
Failure to install, set up or operate the instrument
according to the instructions herein may void the warranty.
Your instrument should only be opened by a duly
authorized representative of the manufacturer. The unit
should only be opened in a fully anti-static environment.
Failure to do so may damage the electronics and will void
the warranty.
NOTE
The greatest care has been taken to manufacture and
calibrate your instrument. However, these instructions do
not purport to cover all possible contingencies that may
arise during installation, operation or maintenance, and all
details and variations of this equipment do not purport to
be covered by these instructions.
For additional information regarding installation, operation
or maintenance of this instrument, contact the
manufacturer or your local representative or distributor.
BG0045 REV. F
i
Table of Contents
CHAPTER 1 INTRODUCTION.................................................... 1
1.1 USING THE COMMUNICATIONS PORT.......................................... 1
1.2 EIA INTERFACE STANDARDS ..................................................... 2
1.2.1 EIA RS-232 Standard......................................................... 2
1.2.2 EIA RS-422 and EIA RS-485 Standards ............................ 2
1.3 RESPONSE TIME ......................................................................... 2
1.4 SETUP PARAMETERS .................................................................. 3
1.4.1 Handshaking ...................................................................... 3
CHAPTER 2 PRINT MODE.......................................................... 5
2.1 CONFIGURING THE PRINT MODE PARAMETERS .......................... 5
2.2 CABLE CONNECTIONS ................................................................ 5
2.3 FLOW CONTROL ......................................................................... 5
2.4 PRINTOUT FORMAT .................................................................... 6
CHAPTER 3 ASCII COMMUNICATIONS PROTOCOL......... 8
3.1 ASCII FRAMING ....................................................................... 8
3.2 EXCEPTION RESPONSES.............................................................. 9
3.3 ASCII MESSAGE DESCRIPTION ................................................ 10
3.3.1 Read Data Registers ........................................................ 10
3.3.2 Read Basic Setup.............................................................. 12
3.3.3 Write Basic Setup............................................................. 14
3.3.4 Reset/Clear Functions...................................................... 14
3.3.5 Reset Powermeter ............................................................ 15
3.3.6 Read Firmware Version Number ..................................... 15
3.3.7 Read Real Time Clock...................................................... 16
3.3.8 Write Real Time Clock ..................................................... 16
CHAPTER 4 MODBUS COMMUNICATIONS PROTOCOL . 17
4.1 MODBUS FRAMING................................................................ 17
4.1.1 Transmission Mode.......................................................... 17
4.1.2 The RTU Frame Format .................................................. 18
4.1.3 Address Field ................................................................... 18
4.1.4 Function Field.................................................................. 18
4.1.5 Data Field ........................................................................ 19
4.1.6 Error Check Field ............................................................ 19
4.1.7 Data Conversion .............................................................. 21
4.1.8 Data Addressing Modes................................................... 23
4.2 MODBUS MESSAGE FORMATS ............................................... 24
4.2.1 Function 03 - Read Multiple Registers ............................ 24
ii
4.2.2 Function 04 - Read Multiple Registers ............................ 24
4.2.3 Function 20 - Read Multiple Registers ............................ 25
4.2.4 Function 06 - Write Single Register................................. 26
4.2.5 Function 16 - Write Multiple Registers............................ 27
4.2.6 Function 21 - Write Multiple Registers............................ 27
4.2.7 Function 08 - Loopback Communications Test ............... 28
4.3 EXCEPTION RESPONSES ............................................................ 29
4.4 POWERMETER REGISTERS ........................................................ 29
4.4.1 Data Registers.................................................................. 29
4.4.2 Basic Setup Registers ....................................................... 32
4.4.3 Real Time Clock Registers ............................................... 35
CHAPTER 5 DNP V3.00 COMMUNICATIONS PROTOCOL36
5.1 DNP PROTOCOL....................................................................... 36
5.1.1 Introduction...................................................................... 36
5.1.2 PM170 Deviation from Standard..................................... 36
5.1.3 DNP Request/Response Overview.................................... 37
5.2 DNP INTERFACE ...................................................................... 37
5.2.1 General ............................................................................ 37
5.2.2 DNP Address.................................................................... 38
5.2.3 Transaction Timing .......................................................... 38
5.2.4 Object Format.................................................................. 39
5.3 SERIES PM170 REGISTERS ....................................................... 39
5.3.1 Data Registers.................................................................. 39
5.3.2 Basic Setup Registers ....................................................... 42
5.3.3 Resetting Energy and Demands ....................................... 43
APPENDIX A DNP APPLICATION MESSAGES .................... 44
APPENDIX B DNP DEVICE PROFILE...................................... 46
INDEX .............................................................................................. 51
WARNING
Ensure that all incoming AC power and other power sources are
turned OFF before performing any work on the instrument. Failure
to do so may result in serious or even fatal injury and/or
equipment damage.
This manual is intended for users of communications protocols with the Series
PM170 Powermeters. For installation and setup instructions refer to the Series
PM170 Powermeters Installation and Operation Manual.
For the safety of personnel and equipment, it is essential to read
this manual prior to using the equipment.
Chapter 1 Introduction 1
Chapter 1 Introduction
1.
1.1 Using the Communications Port
The Series PM170 communications port supports EIA RS-
232, RS-422 and RS-485 standard interfaces allowing
connection to a computer, PLC or a printer. The
communications port can operate at baud rates up to 9,600
bps. Various communications options may be selected by the
user via the front panel.
The communications port can operate in one of two modes:
• computer mode, where a host computer polls the
instrument in order to receive data, or to read or
program the Powermeter setup parameters
• print mode, where output is provided in printable
format.
In the computer mode, the instrument uses a two-way
communications protocol. The communications works on a
master-slave basis where the Powermeter is the slave, i.e. it
responds to host computer requests, but does not transmit
information on its own initiative.
The instrument can support two communications protocols:
(1) the domain ASCII, and (2) Modicon's Modbus RTU
(standard) or DNP V3.00 (option). Each of these protocols
can be used by a third-party host-based software to access all
data and configuration registers of the Powermeter. Chapters
3, 4 and 5 provide the complete information necessary to
develop a third-party communications software capable to
communicate with Series PM170 Powermeters. With the
ASCII protocol, the Powermeter is capable of connection to
a master computer via a modem.
In print mode, the Powermeter can be connected to a serial
printer to output a fixed format printed report at user-defined
intervals.
2 Chapter 1 Introduction
1.2 EIA Interface Standards
1.2.1 EIA RS-232 Standard
RS-232 is a serial interface standard that may be used for
single connections (one computer serial port connected to
one instrument), at distances up to 15 meters. It may be
possible to extend this range using lower transmission rates,
shielded cabling, or repeaters. This standard is generally
used when connecting one instrument to a printer. Print
mode is available only with EIA RS-232.
1.2.2 EIA RS-422 and EIA RS-485 Standards
Both RS-422 and RS-485 are serial differential interface
standards, permitting reliable communications for distances
up to 1200 meters. Due to the differential mode used, line
noise is nullified.
In the RS-422 standard, the interconnection of instruments
with a computer is performed via two pairs of lines, one pair
for transmission, and one for reception (full duplex). In the
RS-485 standard, instruments are connected to a computer
via a pair of lines. The same pair is used both for
transmission and reception (half duplex).
1.3 Response Time
The minimum response time of the Powermeter (to allow the
master PC to switch a communications port) is at least 1.75
character time, depending on the baud rate used.
The maximum response time depends on the
communications protocol. In ASCII protocol, the
Powermeter response time will not exceed 80 ms plus 1.75
character time. For the Modbus RTU protocol, the maximum
response time is 80 ms plus 3.50 character time.
Chapter 1 Introduction 3
1.4 Setup Parameters
The Powermeter communications port must be configured
before connecting it to a master computer or printer. The
port and computer/printer configurations must match. Setup
instructions are found in the Series PM170 Powermeters
Installation and Operation Manual.
1.4.1 Handshaking
This optional flow control parameter is used to define the
flow control protocol that may be necessary to adjust
transmission rate of the Powermeter to the needs of a master
computer or a printer. If you do not need to use this
parameter, you can leave it on its default setting.
It may be necessary to compensate for the Powermeter's
ability to send characters faster than they can be accepted by
a modem or printed on a serial printer, when the incoming
data buffer is too small. The Powermeter allows hardware
and software handshaking.
Hardware handshaking is applicable only in RS-232
communications mode. You can use it to provide DTR/DSR
or RTS/CTS flow control protocol by connecting the DTR
and RTS/CTS lines to the appropriate pins on the
communication connector of the computer or printer.
When hardware handshaking is selected, the Powermeter
will not send characters to the communications port until the
DSR/CTS signal is asserted high. If the DSR/CTS is
dropped during transmission, the Powermeter suspends data
transmission until the DSR/CTS is restored.
When hardware handshaking is selected, the DTR signal is
permanently asserted high. This outgoing signal may be
necessary with certain modems, serial printers or signal
converters.
Software handshaking is applicable only in ASCII RS-232
and RS-422 full-duplex communications modes. When a
physical connection between the Powermeter and a master
4 Chapter 1 Introduction
computer or a printer is impossible or where hardware flow
control is not supported, software handshaking can be used
instead. Software handshaking supports the character flow
control protocol known as XON/XOFF. The master should
send an XOFF character (ASCII DC3) when it wishes the
Powermeter to pause in sending data, and an XON character
(ASCII DC1) when it wishes the Powermeter to resume
transmission.
NOTES
In RS-485 half-duplex communications mode, neither
hardware nor software handshaking are applicable.
If you do not need full-duplex mode, you can use the RS-
485 standard in both 4-wire and 2-wire connections (see
Communications Cable Connections, Series PM170
Powermeters Installation and Operation Manual).
Chapter 2 Print Mode 5
Chapter 2 Print Mode
2.
2.1 Configuring the Print Mode
Parameters
When a serial printer is connected to the Powermeter, you
should configure communications mode to Prnt/232, and
select the appropriate printout period. Baud rate and data
format should be configured in the Powermeter as those on
the printer. See the Series PM170 Powermeters Installation
and Operation Manual for instructions on configuration of
the Powermeter communications parameters.
2.2 Cable Connections
Cable connections to the printer may depend on the printer
connector type. Most serial printers have a DTE 25-pin male
connector, but some may have a DCE 25-pin female
connector. Refer to the Series PM170 Powermeters
Installation and Operation Manual for cable drawings of
both connector types.
2.3 Flow Control
Most printers provide a few bytes of buffer storage where
characters can wait their turn to be printed. If the buffer size
is sufficient to accept a full print report, i.e., when a printer
has at least 256 bytes of input buffer, flow control is not
needed. If the buffer size is less than 256 bytes, you should
provide hardware handshaking, otherwise the printer output
will become garbled. Use the DSR/CTS signal to provide
hardware flow control. In the Powermeter, configure the
handshaking mode to HArd .
With a serial-to-parallel converter, you can use a parallel
printer as well. When a converter is used, hardware
handshaking is required. For setup instructions and cable
6 Chapter 2 Print Mode
drawings, refer to the Series PM170 Powermeters
Installation and Operation Manual.
2.4 Printout Format
The instrument sends a fixed format printed report at
user-defined intervals. After power up or completing the
current page, the value heading is printed on the top of the
new page. The printing page height is 62 rows. Each row is
terminated by ASCII characters CR (ASCII 13) and LF
(ASCII 10). On each page, along with a header, 20 readings
are printed. The following illustrations show the printout
formats for the Series PM170 models:
PM170
1 2 3 4 5 6 7 8 9
V1
4
chars
V2
4
chars
V3
4
chars
A1
5
chars
A2
5
chars
A3
5
chars
KW
6
chars
PF
4
chars
FREQ
4
chars
10 11 12
A_MD1
5
chars
A_MD2
5
chars
A_MD3
5
chars
PM170E
1 2 3 4 5 6 7 8 9
V1
4
chars
V2
4
chars
V3
4
chars
A1
5
chars
A2
5
chars
A3
5
chars
KW
6
chars
PF
4
chars
FREQ
4
chars
10 11 12 13 14 15 16
KWH
6
chars
KVAR
6
chars
KVARH
6
chars
A_MD1
5
chars
A_MD2
5
chars
A_MD3
5
chars
MAX_DM
6
chars
PM170M
1 2 3 4 5 6 7 8 9 10
V1
4
chars
V2
4
chars
V3
4
chars
A1
5
chars
A2
5
chars
A3
5
chars
KVA
6
chars
KW
6
chars
KVAR
6
chars
PF
4
chars
10 11 12 13 14 15 16 16
KVAH
7
chars
KWH
6
chars
KVARH
6
chars
A_MD1
5
chars
A_MD2
5
chars
A_MD3
5
chars
KVA_MD
6
chars
KW_MD
6
chars
I_UB
5
chars
FREQ
4
chars
Chapter 2 Print Mode 7
Table 2-1 lists all measured items presented in the print
report with their respective labels and resolution.
Table 2-1 Print Parameters
Parameter
label
Description Resolution
(no.digits)
V1, V2, V3 Voltage per phase L1/L12,
L2/L23, L3/L31
4
A1, A2, A3 Current per phase L1, L2, L3 5
A_MD
1,2,3
Maximum ampere demand per
phase L1, L2, L3
5
I_UB Unbalanced current 5
PF Total power factor 4
FREQ Frequency 4
KVA kVA total 6
KW kW total 6
KVAR kvar total 6
MAX_DM Maximum kW demand 6
KW_MD Maximum kW demand 6
KVA_MD Maximum kVA demand 6
KVAH kVAh 6
KWH kWh net 6
KVARH kvarh net 6
8 Chapter 3 ASCII Communications Protocol
Chapter 3 ASCII
Communications Protocol
3.
This chapter explains how data is transferred between a
master computer station and the Powermeter when the
ASCII serial communications protocol is used.
All messages within the ASCII communications protocol are
designed to consist only of printable characters.
3.1 ASCII Framing
The following specifies the ASCII message frame:
#1
Sync
!
#2
Message
length
#3
Slave
address
#4
Message
type
#5
Message
body
#6
Check
sum
#7
Trailer
SYNC - synchronization character: one character '!' (ASCII
33) used for starting synchronization.
Message length - length of the message including only
the number of bytes in fields #2, #3, #4 and #5. Contains
three characters between '006' and '252'.
Slave address - two characters between '00' and '99'. The
Powermeter with address '00' responds to requests with any
incoming address. For RS-422/RS-485 communications
(multidrop mode), this field must NEVER be zero.
Message type - one character representing the type of a
host request. A list of the message types is shown in Table 3-
1.
Message body - contains the message parameters in
ASCII representation. All parameter fields have a fixed
format. The data fields vary in length depending on the data
type. If not indicated otherwise, the parameters should be
right justified and left-padded with zeros.
Chapter 3 ASCII Communications Protocol 9
The parameters are transferred in a decimal notation ‘as is’,
i.e., no conversion is needed. When a value is between 0 and
1, a decimal point must be placed in the data field. When the
value range exceeds the field range, it is divided by 1000
and truncated to the right. A decimal point is placed after the
thousands to denote that the value has been truncated and
must be multiplied by 1000 before processing.
Check sum - arithmetic sum, calculated in 2-byte words
over fields #2, #3, #4 and #5 to produce a one-byte check
sum in the range of 22h to 7Eh (hexadecimal) as follows:
[Σ(each byte - 22H)] mod 5CH + 22H
Trailer - two ASCII characters, CR (ASCII 13) and LF
(ASCII 10).
NOTE
Fields #3 and #4 of the Powermeter response are always
the same as those in the host request.
Table 3-1 ASCII Message Types
Message type Description
Char ASCII Hex
0 30h Read data registers
1 31h Read basic setup
2 32h Write basic setup
4 34h Reset/clear function
8 38h Program reset
9 39h Read version number
3.2 Exception Responses
The instrument will send the following error codes in the
message body field in response to incorrect host requests:
XK -
Powermeter is in programming mode
XP - invalid setup value or setup is not available
XM - invalid request type
NOTE
When check or framing error is detected, the Powermeter
will not act on or respond to the master's request.
10 Chapter 3 ASCII Communications Protocol
3.3 ASCII Message Description
3.3.1 Read Data Registers
This request is used to retrieve a predefined set of the data
measured by the Powermeter. All electrical parameters are
averaged values over the specified number of the real-time
measurements (see the averaging buffer size in Table 3-5).
Host request:
Message type - '0'.
Message body - none.
Response:
Message type - '0'.
Message body - see Table 3-2.
The message body length: PM170/170E - 163 characters
PM170M - 225 characters
Table 3-2 Response '0' body
No. Offset
(bytes)
Length
(bytes)
Description Unit Range e
1 0 4 Voltage L1/L12 V/kV c 0 to Vmax
2 4 4 Voltage L2/L21 V/kV c 0 to Vmax
3 8 4 Voltage L3/L31 V/kV c 0 to Vmax
4 12 5 Current L1 A 0 to Imax
5 17 5 Current L2 A 0 to Imax
6 22 5 Current L3 A 0 to Imax
7 f 27 6 kW L1 kW/MW c -Pmax to Pmax
8 f 33 6 kW L2 kW/MW c -Pmax to Pmax
9 f 39 6 kW L3 kW/MW c -Pmax to Pmax
10f 45 4 Power factor L1 -.99 to 1.00 d
11f 49 4 Power factor L2 -.99 to 1.00 d
12f 53 4 Power factor L3 -.99 to 1.00 d
13 57 6 kW total kW/MW c -Pmax to Pmax
14 63 4 Power factor total -.99 to 1.00 d
15f 67 6 kWh net kWh/MWh c -999.9 to 9999.9
16g 73 5 Unbalanced current A 0 to Imax
Chapter 3 ASCII Communications Protocol 11
No. Offset
(bytes)
Length
(bytes)
Description Unit Range e
17 78 4 Frequency Hz 45.0 to 65.0
18g82 6 kvar L1 kvar/Mvarc -Pmax to Pmax
19g88 6 kvar L2 kvar/Mvarc -Pmax to Pmax
20g94 6 kvar L3 kvar/Mvarc -Pmax to Pmax
21g100 6 kVA L1 kVA/MVA c 0 to Pmax
22g106 6 kVA L2 kVA/MVA c 0 to Pmax
23g112 6 kVA L3 kVA/MVA c 0 to Pmax
24f118 6 kvarh net kvarh/Mvarh
c
-999.9 to 9999.9
25f124 6 kvar total kvar/Mvar c -Pmax to Pmax
26g130 6 kVA total kVA/MVA c 0 to Pmax
27f136 6 Maximum kW
demand
kW/MW c 0 to Pmax
28f142 6 Accumulated kW
demand
kW/MW c 0 to Pmax
29 148 5 Maximum ampere
demand L1
A 0 to Imax
30 153 5 Maximum ampere
demand L2
A 0 to Imax
31 158 5 Maximum ampere
demand L3
A 0 to Imax
32g163 2 N/A
33g165 6 Maximum kVA
demand
kVA/MVA c 0 to Pmax
34g171 6 Accumulated kVA
demand
kVA/MVA c 0 to Pmax
35g177 4 N/A
36g181 4 N/A
37g185 4 N/A
38g189 4 N/A
39g193 4 N/A
40g197 4 N/A
41g201 8 kVAh kVAh 0 to 9999999
42g209 6 kW demand kW/MW c 0 to Pmax
43g215 6 kVA demand kVA/MVA c 0 to Pmax
44g221 4 Power factor at
maximum kVA
demand
-.99 to 1.00 d
12 Chapter 3 ASCII Communications Protocol
Fields indicated by an N/A mark are padded with ASCII
zeros.
c When the value width is over the field resolution, the reading is
converted to higher units and transmitted with a decimal point.
The right most digits of the reading are truncated.
d For negative power factor, the minus sign is transmitted before a
decimal point as shown in the table.
e The parameter limits are as follows:
Vmax = 660 [V] if PT Ratio = 1.0 and Vmax = 144*PT Ratio [V] if
PT ratio > 1.0, for the instruments with 660 V input option
Vmax = 144*PT Ratio [V], for the instruments with 120 V input
option
Imax = 1.2 * CT primary current [A]
Pmax = (Imax * Vmax * 3)/1000 [kW] if wiring mode is 4L-N
Pmax = (Imax * Vmax * 2)/1000 [kW] if wiring mode is 4L-L, 3-OP,
or 3DIR
f These parameters are actual for the PM170E/170M only. In the
PM170 response, they are passed as zeros.
g These parameters are present in the PM170M response only.
NOTES
The voltage parameters throughout the protocol can
represent line-to-neutral or line-to-line voltages depending
on the wiring mode selected in the Powermeter. When a 4L-
N wiring mode is selected, they will be line-to-neutral
voltages, and when another mode is selected, they will be
line-to-line voltages.
In 3-wire connection schemes, unbalanced current and the
phase readings for power factor, active power, and reactive
power will be zeros, because they have no meaning. Only
the total three-phase power values can be used.
3.3.2 Read Basic Setup
This request is used to retrieve the current basic setup
parameters.
Host request:
Message type - '1'.
Message body - see Table 3-3.
Chapter 3 ASCII Communications Protocol 13
Table 3-3 Request '1' body
Field
number
Offset
(bytes)
Length
(bytes)
Description
1 0 3 Parameter identifier (see Table 3-5)
Response:
Message type - '1'.
Message body - see Table 3-4.
Table 3-4 Response '1' body
Field
number
Offset
(bytes)
Length
(bytes)
Description
1 0 3 Parameter identifier (see Table 3-5)
2 3 4 Not used (permanently set to 00.0)
3 7 6 Parameter value (see Table 3-5)
Table 3-5 Basic Setup Parameters
Parameter Identifier Unit Parameter Range
Wiring mode
W40 0 = 3OP, 1 = 4L-N,
2 = 3DIR, 3 = 4L-L
PT ratio U14 1.0 to 6500.0
CT primary
current
I17 A 1 to 50000
Power demand
period
D11 min 1,2,5,10,15,20,30,60 min
255 = external synchronization
Ampere demand
period
C12 sec 0 to 1800
0 = measuring peak currents
Averaging buffer
size
S41 8, 32
Reset
enable/disable
R42 0 = disable, 1 = enable
14 Chapter 3 ASCII Communications Protocol
3.3.3 Write Basic Setup
This request allows you to change any basic setup
parameter.
Host request:
Message type - '2'.
Message body - see Table 3-6.
Table 3-6 Request '2' body
Field
number
Offset
(bytes)
Length
(bytes)
Description
1 0 3 Parameter identifier (see Table 3-5)
2 3 4 Not used (set to 00.0)
3 7 6 Parameter value (see Table 3-5)
Response:
Message type - '2'
Message body - see Table 3-6.
3.3.4 Reset/Clear Functions
This request is used to clear accumulated values stored by
the Powermeter.
Host request:
Message type - '4'
Message body - see Table 3-7.
Table 3-7 Request '4' body
Field
number
Offset
(bytes)
Length
(bytes)
Description Range
1 0 1 Reset function see Table 5-8
Chapter 3 ASCII Communications Protocol 15
Table 3-8 Reset/Clear Functions
Function Description
1 Clear energy registers
2 Clear maximum demand registers
Response:
Message type - '4'
Message body - the same as that for the host request.
3.3.5 Reset Powermeter
This request causes the Powermeter to perform full reset and
restart, such as in the event of power up.
Host request:
Message type - '8'.
Message body - none.
Response: None
3.3.6 Read Firmware Version Number
This request is used to retrieve the version of the firmware
installed in the Powermeter.
Host request:
Message type - '9'.
Message body - none.
Response:
Message type - '9'.
Message body - see Table 3-9.
Table 3-9 Response '9' body
Field
number
Offset
(bytes)
Length
(bytes)
Description
1 0 3 Firmware version number
16 Chapter 3 ASCII Communications Protocol
3.3.7 Read Real Time Clock
This request allows the user to obtain the present RTC
indication.
Host request:
Message type - 'S'.
Message body - none.
Response:
Message type - 'S'.
Message body - see Table 3-10.
Table 3-10 Response 'S' body
Field
number
Offset
(bytes)
Length
(bytes)
Description Range
1 0 2 Second 0-59
2 2 2 Minute 0-59
3 4 2 Hour 0-23
4 6 2 Day 1-31
5 8 2 Month 1-12
6 10 2 Year 0-99
3.3.8 Write Real Time Clock
This request allows the user to set up the Powermeter RTC.
Host request:
Message type - 'T'.
Message body - see Table 3-11.
Table 3-11 Request 'T' body
Field
number
Offset
(bytes)
Length
(bytes)
Description Range
1 0 2 Second 0-59
2 2 2 Minute 0-59
3 4 2 Hour 0-23
4 6 2 Day 1-31
5 8 2 Month 1-12
6 10 2 Year 0-99
Response:
Message type - 'T'.
Message body - the same as that for the host request.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55

Satec PM170 User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI