2 RC8BL202 © Danfoss 10/2004 Fanpack 2800
A. Control panel The control panel is located in front of the frequency converter. The settings are changed via the
control keys.
B. Control keys
The QUICK MENU & + keys must be pressed at the same time to give access to all parameters .
Keys + & – are used to selecting parameters and for changing parameter value.
CHANGE DATA is used for changing a setting. The key is also used for confi rming a change of para-
meter settings.
- Power on the frequency converter, open START input on terminal 18 and press simultaneously on the
keys QUICK MENU & +.
- Fill in, in the same order, the settings below :
Para-
meter
Value
Example for 2 motors of 0,55A and pressure of 10 Bar
Value
100 1 Process closed loop (To use internal PI-controller) 1
101 2 VT High (To use “variable torque” for fans) 2
105 fi ll in here the sum of the fans current 1.1
201 0 Hz Freq. low limit 0
202 50 Hz Freq. high limit 50
204 0 Bar Ref. min. (corresponding to range of transmitter) 0
205 25 Bar Ref. max. (corresponding to range of transmitter) 25
207 3 s Ramp up 3
208 3 s Ramp down 3
305 0 No. op. 0
308 0 No. op. 0
314 2 Feedback (signal on terminal 60) 2
315 4 mA Minumum output from transmitter 4
415 25 FB max (same as par 205) 25
437 1 Inverse (Increased pressure = higher speed) 1
440 2 Gain 2
441 2 s Time 2
002 1 Remote=0. Local=1 (local = internal reference, par
003)
1
003 ex. 10 Bar Pressure reference in bar 10
019 0 Power up action = Auto Restart (from SW ver.1.4x)
In parameter 003 set your desired condenser pressure directly in bar
When “local” is selected in par. 002 the connection between terminal 12 and 18 is not needed for giving
a start signal. The unit is simply started by pressing the “start” key on the keypad.