McQuay Seasonpak PAB-020S Installation And Maintenance Data

Category
Split-system air conditioners
Type
Installation And Maintenance Data
BULLETIN NO.
IM
115
AUGUST 1967
FORM 206034Y
INSTALLATION AND
MAINTENANCE DATA
MODEL PAB
AIR COOLED WATER CHILLER
7-1/2
THRU 60 TONS
INC.. 13600 INDUSTRIAL PARK BLVD., P.O. BOX 1551, MINNEAPOLIS, MINNESOTA 55440
PHONE:
377-9750
AREA CODE: 612
STANDARD WARRANTY
McQuay, Inc. warrants to the extent of the purchase price that new
products of its manufacture are, when originally sold, free of defects
in material and factory workmanship if properly installed, cared for,
and operated, under normal conditions, with competent supervision.
McQuay’s obligations under this warranty shall be fully discharged by
correction of such defects in any part or parts which, within one year
of shipment of the products to the original purchaser, shall be re-
turned
in
sealed containers, tagged as to serial and model numbers,
with
transportatlon
charges prepaid, to the factory or service location
designated by McQuay. McQuay shall not be liable for any loss,
domage, or expense, directly or indirectly arising from defects
in
its
products, the use of its products,or any other cause. McQuay does
not assume responsibility for any expenses (including labor and
travel expenses) incurred in the field incidental to the repair or re-
placement of its products.
This warronty extends only to the original purchaser and shall not
apply to any products which must be replaced because of normal wear,
which have been the subject to misuse, negligence, or accident,
or
which have beer repaired or altered by persons other than those
authorized by McQuay to service its products, or to any
product on
which a serial number has been altered or removed.
This warranty
does not apply to any motor, switches, controls,
accessories,
or
other parts, manufactured by others and purchased by
McQuay unless
the manufacturer
warrants
the same to McQuay
and
then only to the
extent of such manufacturer’s warranty to
McQuay.
The
decision
of McQuay’s service department as to whether a defect
IS
within
the terms of this
warranty
shall
be final.
This warranty supersedes and is in lieu of
all
other warranties,
ex-
pressed or implied
ond no
representative,
dealer,
distributor or any
other person.
is
authorized
or permitted
to make
any other or further
warranty or to incur
to
obliga
te
McQuay to any other Lability not
strictly in accordan
further
warranty
is
h
this policy
(except to the extent that such
in
writing and signed by an official of Mc-
Quay for
additional
considerationn
in accordance with an established
policy for
such
further
warranties).
McQuay’s
failure
to
object
to provisions contained
in
a customer’s
purchase orders or other communications shall not be deemed a
waiver
of the terms or
conditions
hereof or acceptance of such pro-
visions
ADDITIONAL FOUR-Y EAR WARRANTY
OF MOTOR-COMPRES
In oddition to the standard warra
for further consideration, McQua
purchase price, that the motor
new unit is, when originall
factory workmanship if
under normal conditions
compressor assem
e extentof the
on
each such
ared for, and operated,
rvision.
The term
“motor-
lyconsisting
of the
stator,
suction valve,
dis-
in which these parts are enclosed.
warranty shall be fully discharged by
in any port or parts which, within four
ioni
of the standard one-year warranty, shall be
ainers, tagged OS to serial and model numbers,
arges prepaid, to the
factory
or service location
Mcf3irhy shall not be liable for any loss, damage, or expense, directly
sv
IndIrectly
arising from defects in its products, the use of its prod-
ucts, or ony other cause.
McQuay
does not assume any responsibility
for any expenses (including labor and travel expenses) incurred in the
field
incidental
to the repair or replacement of its products.
This warranty extends only to the
original
purchaser and shall not
apply to any products which must be
replaced
because of normal wear,
which have been subject to misuse, negligence, or accident, or which
hove been repaired or altered by persons other than those authorized
by
McQuay to service its products, or to any product on which a
serial
number has been altered or removed.
The
decision
of McQuay’s service department as to whether a defect
is
within
the terms of this warranty shall be
flnal.
This warranty supersedes and is
in
lieu of all other warranties, ex-
pressed or implied and no representative, dealer, distributor, or ony
other person.
is
authorized or permitted to make any other or further
warranty or to incur or obligate McQuay to any other liability not
strictly
in
accordance with this
policy.
INSTALLATION
GENERAL
SERVICEABILITY
Equipment of this type is intended for installation by
qualified servicemen’only. As a condition of the war-
ranty, the check, test, and start-up procedure must be
performed by such personnel and properly reported on
the form provided. Failure to do so voids the warranty.
Arrangement for service should be made prior to instal-
lation, as it is not included in the warranty or the
catalog price. See warranty terms on Page 3.
The compressor compartment is accessible from the
top and two sides by easily removed panels.
All control and starting equipment is located in the
control cabinet. The control panel is protected by a
weatherproof enclosure having a
gasketed
and hinged
door.
The condenser fan motors on belt driven units are
accessible through generously sized access doors for
checking the fan motor, belts, and drives.
INSPECTION
On belt drive units, the condenser fan bearings are
equipped with external lubrication fittings.
When the equipment is received, all items should be
carefully checked against the bill of lading to be sure
that ail crates and cartons have been received. All
units should be carefully inspected for damage when
received and all damage should be reported immedi-
ately to the carrier, and a claim filed for damage. The
unit nameplate should be checked to be sure it agrees
with the power supply available.
The direct drive fan motors are serviced through the
fan opening.
REFRIGERANT CHARGE
LOCATION
Every model PAB SEASONPAK air cooled water chiller
is supplied with a full refrigerant charge for the job
requirements
(see
Table
6,
Pages 8 and
9).
Charge for
specific units can
be
obtained
f’rom
the
nameplatc.
The
McQUAY
line of air cooled water chillers is de-
signed for outdoor application. The chiller unit should
be located so that all four sides of the unit have free
area for inlet air flow. The units have vertical conden-
ser air discharge, with air taken in from the underside
of the unit.
HANDLING
A level and sufficiently strong base is required to
support the SEASONPAK air cooled water chiller. If
necessary, additional supports should be provided to
transfer the weight of the unit to the nearest adequate
structural members of the building.
The unit location should be such that the service-
man has free access to the compressor compartment,
refrigerant system components (i.e., strainerdriers),
condenser fan motors, and electrical control cabinet.
\,‘ibration
isolators are recommended under all roof
mounted units or
where
vibration transmission is crit-
ical
Recommended
mounts are shown in
Table
1,
Page 6.
Care should be taken to avoid rough handling or shock
due to dropping the unit. Never push or pull the unit
from anything other than the skids. Do not drop either
end of unit off of truck tail gate. For lifting, slings
should be provided, with spreader bars to protect the
aluminum housing. The dual units are furnished with
permanent full length skids. The single compressor
units are shipped on wooden skids. Lifting adapter
holes are furnished on the dual unit skids. Lifting
lugs are furnished on the single unit side channels.
All legs have convenient holes for use in moving the
unit.
The
single compressor unit leg base
plates
have
three holes for convenient location of legs for fasten-
ing to “I” beam or channel bases.
Page
A
ELECTRICAL
ELECTRICAL CONTROL CENTER
The adjustable safety controls are separated from the
starting controls by means of a partition dividing the
control cabinet and individual access doors. The con-
trol box is further arranged with a dead-front panel
which covers all
exposed electrical contacts and
terminals, to provide absolute safety for the operator.
Figure 6, Page 10, shows dead-front panel removed to
show internal controls and wiring.
FIELD WIRING
A.
B.
C.
D.
E.
F.
G.
Wiring should be done in accordance with all ap-
plicable codes and ordinances.
Three main power leads must be hooked up to the
unit power terminal block. Table 8, Page 16, gives
the recommended lead wire sizes for three conduc-
tors in a raceway for a normal installation.
Maximum voltage variation equals 10% of nameplate
value. Phase voltage unbalance
must not
exceed 2%.
A flow switch (FC) is provided with the unit and
must be field wired across terminals as shown on
Diagrams 2 and 3, Pages 12 thru 15.
Refer to wiring diagrams provided with units for
specific wiring recommendations for each model.
Wiring Diagrams 2 and 3, Pages 12 thru 15, show
basic wiring and accessory circuits.
Always ground unit for safety.
FUSES AND CIRCUIT BREAKERS
The fuses and circuit breakers for the compressor,
condenser fan motor circuit and control circuit are
located in the control box. In addition, there are small
fuses for the compressor control circuit located in the
end of the compressor terminal box. Most local elec-
trical codes also require a disconnect switch in the
power supply, located within reach of the unit. In
many areas, the circuit breaker can be used in place
of
a
disconnect switch. Check on local
ordinances
covering
specific
rcquircments.
CRANKCASE HEATERS
The compressors are equipped with crankcase heaters.
Some models have heaters installed externally below
the crankcase and others have heaters inserted into
the crankcase.
When the system is to be started up initially, the
crankcase heater power should be turned on before
starting the system for a time sufficient for all
rcfrig-
erant in the crankcase to be evaporated. This should
be a minimum of 4 hours, and preferably over night.
The crankcase should be up to approximately 80 F.
before the system is started, to minimize the possibil-
ity of lubrication problems or valve damage on start
up.
LOCKOUT-TIMER OPERATION (Optional)
(Refer to Diagram
1)
A.
B.
C.
D.
E.
F.
G.
The desired time delay period is set by loosening
the nut at the actuator arm and adjusting the arm
in relation to the calibrated dial. The nut is
tightened.
The sustained contact switch is closed. (Normally
closed R2 in Diagram 2, Page 13).
The clutch motor is energized through the closed
r1
contact. (The relay remains unenergized).
The motor drives the actuator arm and winds
up
the reset spring during the timed delay
period.
At the end of the delay period, the actuator arm
closes the
r3
contact, energizing the
r
relay.
1.
The
r2
contact closes and holds the
r
relay
in.
2. The
r5
contact
closes,
energizing
the load.
3.
The
r1
contact opens,
de-energizing
the motor.
The motor and actuator are reset by the reset
spring. The r3 contact opens up again since it
is actuated only by the actuator arm and is in-
dependent of the relay coil.
When the sustained contact switch is opened, the
r
relay coil becomes deenergized. The r5 contact
opens up, de-energizing the load.
The timer is now ready for the next closing of the
sustained contact switch and timed delay period.
DIAGRAM 1
LOCKOUT-TIMER
(INTERNAL WIRING)
R2
(DIAC.
2 PAGE 13)
R3 & R4
(DIAG.
3 PAGE
II
II
I
LINKAGE
L---_----
Page
11
START-UP PROCEDURE
Do not start the SEASONPAK air cooled water chiller F.
until the following steps have been completed.
A.
B.
Check all auxiliary components of the installation.
G.
Open the compressor suction and discharge shut
off valves until back seated. Back seating the
valve closes the gauge ports; however, if gauges
are provided, close valve one turn toward the closed
H.
position. Always replace seal caps.
I.
Open the manual liquid line shut off valve at the
condenser.
Check that circuit breakers and system switch are J.
in “off” position. Throw the main power disconnect
to “on”.
K.
Check to see that the water temperature thermo-
stat is installed in the entering water line. The L.
thermostat well is to be full of heat conducting
compound and the bulb must be secured with the
retaining fitting.
Check the compressor oil level. Prior to start-up,
the oil level should be visible in the oil
sight-
glass.
Check the main system on-off switch to see that it
is in the“off’ position. The
pumpdown
switches
should be thrown to the “manual” position.
Check
resets of all safety controls.
Check
if crankcase heaters havewarmed the crank-
case of compressors. Start the auxiliary equipment
for the installation.
Set the circuit breakers to “on” position.
Turn on the system by pushing the system
“on-
off”
switch to “on”.
Start
unit(s)
by turning
pumpdown
switches to
“auto” position.
Page 17
OPERATION
During full load operation, check the compressor oil
level. It should be near the center of the oil sight
glass
during
operation.
A.
B.
C.
D.
E.
Check the refrigerant
charge
frequently at the
moisture/liquid indicator. A steady clear glass of
liquid refrigerant indicates sufficient charge. A
green colored button in the center of the moisture
indicator indicates a dry system (should moisture
enter the system, the color will turn yellow). The
button was
green before it left the factory and
should be green after a period of operation on
start-up. A filter-drier core change is recommended
for a persistent yellow indicator. (Page 26).
Check the temperature control
thecmostat
by ob-
serving operation at reduced loads. The thermostat
is factory set for 44F leaving chilled water tem-
perature when the entering temperature is 54F.
Refer to CHECKING CONTROLS section, Pages
20 and 21.
Checkvoltage and amperage of the compressor
mo-
tor(s)
and fan motors (see Field Wiring, Page
11).
When gauges ace furnished, close gauge
ports
by
back seating valves after readings ace checked.
This will prolong the gauge life and prevent
refrig-
erant loss. Replace seal caps.
See SERVICE INFORMATION section, Pages 28
and 29 for Trouble Shooting
Chart.
PERIODIC SERVICE
(At end of first week of operation and once a month
thereafter.)
A.
B.
C.
D.
A. Turn on water circulating pump.
Check
compressor oil level. Oil should cover ap-
proximately
l/2
of the oil level glass.
Copeland
Compressors ace furnished with oil fill plug on
the side of crankcase, should it be necessary to
add oil. (See Page 25, Paragraph E).
B. Turn
pumpdown
switches
S3
and S4
to "auto”
posi-
tion.
Check liquid sight glass ahead of expansion valve
for proper refrigerant charge.
C. Observe operation for several minutes, noting
un-
usual sounds, or possible unusual cycling of
compressors.
EXTENDED SHUTDOWN
On
belt driven units,
check
belt tension and ob-
serve condition of belts.
A. Close the liquid line shut-off valve.
Check the surface of the condenser coil for ob-
B. Wait for the compressor to pump down until it
struction.
If necessary, flush with cold water,
shuts off.
brush off, or use vacuum cleaner.
E. Make general inspection of entice system for any
unusual sound or condition.
NORMAL REFRIGERANT CHARGE
The condenser coil has a built-in subcooler. For opti-
mum operation. the liquid sight glass in the liquid line
between the receiver and
subcooler
should be substan-
tially free of bubbles. A completely clear sight glass
indicates a possible overcharged system. No adverse
affect need be expected unless overcharge is suffici-
ent to affect an excessive head pressure caused by
appreciable liquid flooding of condenser portion of
coil. The minimum charge at which the unit will
oper-
ate properly is with
clear
sight glass between
the
filterdrier and thermostatic expansion valve.
WEEK END OR SHORT PERIOD SHUTDOWN
A.
B.
Turn
pumpdown
switches
5%
and S4 to “man”
position. The compressor or compressors will con-
tinue to run for a short period, until the system
pumps down, and stops on opening of low pccssuce
control.
Turn off water circulating pump (Water circulating
pump is often left on the line as an assist against
damage by freezing of water).
WARNING:
Do not open main
electrical
discon-
nect
switch as heater
cable
and crankcase heater
will
be
de-energized.
START UP FOLLOWING WEEK END SHUTDOWN
Page 18
C.
D.
E.
F.
G.
OPERATION
Turn off the water circulating pump. (Water circu-
lating pump often is left on the line as an assist
against damage by freezing of water, if cooler is
not going to be drained).
Turn off the power to the compressor(s), condenser
fan motors, crankcase heaters, and water circu-
lating pump.
Be sure that the cooler section, and all outside
piping is properly protected from freezing down to
minus 20F.
However, it is advisable to drain the
cooler and all external piping for additional protec-
tion against extended power failure, or possible
electrical component failure.
Close the suction and discharge shut-off valves.
Tag all opened disconnect switches warning against
starting up the compressor before properly re-open-
ing the shut-off valves.
START-UP AFTER EXTENDED SHUTDOWN
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
Inspect all equipment.
Check surface of the condenser coil for paper
or
other obstruction.
Open the suction and discharge service valves.
Check circuit breakers; must be in “off’ position.
Turn on the electric power to the system.
Open the liquid line shut-off valve(s).
Check crankcase heaters and crankcase warmth.
Start the water circulating pump.
Throw
pumpdown
switches to “man” position.
Start the unit
(S1
and circuit breakers on, and
thermostat
TCl
calling for cooling).
Throw
pumpdown
switches
to
“auto”
for
restart
and normal operation.
L.
After the unit has run for several minutes, check
the oil level in the crankcase. and observe flow
through the refrigerant sight glass for sufficient
refrigerant
charge.
IMPEDANCE RELAY OVERLOAD PROTECTION
In order to provide reset of the unit from the con-
ditioned space or at the unit, an impedance
relay
is incorporated in the control circuit. Basically. this
type of control is centered around a relay with a
high impedance holding coil connected in series with
the basic relays and
contactors,
but also in
parallel
with the automatic safety
reset
control or controls.
The
impedance
relay normally closed contacts are lo-
cated in the safety control circuit.
A
normally open
reset button installed at the panel or remotely is con-
nected
in parallel with the relay contacts.
For typical operation. refer to Diagram
3,
Pages
14
and
15.
Note that coil of the impedance relay
R5
is in
series with the group of controls Ml,
M3,
and
R3.
The
coil is also in parallel with the
high
pressure control
HP1 and the normally closed
relay
contacts
R5.
In
normal operation, HP1 and
R5
are
closed
and,
there-
fore
there is no voltage across
relay
coil
R5.
However,
when
the
system goes out on high head pressure, con-
trol
HP1
opens:
R5
coil is now in
series
with
the
group
of
controls
Ml,
M3
and
R5.
Although the
relay
coil
R5
is in
series
with the group of controls. there is
suffi-
cient
voltage
across
it to open the normally closed
contact
R5.
When
the high
pressure
control
HP1
closes
againl
on reduction in head
pressure,
t he
normally
closed
contact
R5
is still held open
by
voltage across
coil
R5.
It is. therefore, necessary to push reset switch
S5
to jumper contact
R5
and drop out the impedance
relay
so that the system can start. A remote reset switch in
parallel with
S5
may
Be
installed for remotely restart-
ing the unit.
Where compressors have external overload protec-
tion. both the HPC and the external overload control
circuit is reset
by
the impedance circuit. Where com-
pressors have
internal
overload protection. automatic
reset,
only
the
HPC
outage
is
reset
by
the
imredance
circuit
Papa
I9
CHECKING
CONTROLS
All controls are checked and adjusted prior to leaving
the factory. However, after the unit has operated satis-
factorily for a reasonable length of time, a check of
the operation and safety controls can be made as
indicated below:
A.
B.
C.
Oil Pressur e Safety Switch
The oil failure pressure switch is activated by
pressure differential between the oil pump pres-
sure and the crankcase pressure. Upon start up,
the normally closed pressure actuated contact of
this control opens when the pressure differential
increases to about 15 psig. If oil pressure does not
reach this differential, the thermal time delay re-
mains energized and opens a bi-metallic safety
contact, de-energizing the complete control circuit.
If pressure reaches the prescribed differential
within 120 seconds, the thermal time delay is de-
energized and the control circuit remains closed.
If, during the operation, the oil pressure differen-
tial falls below 10 psig, the thermal time delay is
again energized and the control will shut down the
compressor.
To check the control, trip the circuit breaker to
the “off’ position. Throw control circuit to “on”
to pull in contactor. The contactor should drop out
after approximately 120 seconds. After checking
the control, wait approximately 2 to 3 minutes for
the bi-metal thermal element to cool and then reset
control manually. The compressor can then be
started. Repeated successive operations of the
control will require a longer period before it can
be reset, since the bi-metal thermal element will
get hotter and will take more time to cool.
High Pressure Control
The high pressure switch will shut down the com-
pressor and close the liquid line solenoid valve
when the compressor discharge pressure reaches
390
psig.
To check the control, shut down the con-
denser fan and observe the cut out point. During
testing, stand by the system on-off switch to shut
down the unit should the safety device malfunc-
tion. Be sure the gauges used are accurate. The
high pressure relief valve is set for 425 psig.
Low
Pressure
Control
This pressure switch is connected to the low side
of the system and its purpose is to shut down the
D.
E.
compressor at the end of the
pumpdown
cycle. It
will open at 35 psig and automatically reset at
approximately 60 psig. The control can be checked
by throwing the individual
pumpdown
switches to
the manual position and observing the cutout point
on the gauge.
Freezestat Thermostatic Contro l
(TC2)
This control has a bulb located in a well in the
water piping leaving the cooler. To check this con-
trol, remove the operating thermostat bulb in enter-
ing water to chiller from its well to prevent it from
shutting down the system. Then drop the water
temperature until the freeze control in the leaving
water of chiller shuts down the system. The control
should be set to cut out when the water tempera-
ture leaving the chiller reaches 36F
+
1F.
Thermostat
(TC1)
The thermostat supplied on all packaged water
chillers are factory calibrated for use in the return
water line to the cooler inlet. The thermostat bulb
is installed in a well in the return water line in
order to be more stable under temperature changes
due to load conditions. Figure 9, Page 24, illus-
trates the recommended method of installing the
bulb and well in the return water line. The return
water does not change temperature as rapidly as
the outlet
becaus e of the “fly wheel effect” of the
total water system. This results in a stable, non-
recycling control of the outlet water temperature.
Normally the thermostat requires no adjustment
in the field other than the dial setting for the re-
quired control point. The control is preset at the
factory
to
maintain a 44F average leaving water
temperature throughout the loading and unloading
sequence of the unit, based on a full load cooling
range of 10F. It should be realized, however, that
there will be a fluctuation in the leaving water
temperature as the unit cycles, unloads and loads.
The magnitude of fluctuation will decrease as the
number of capacity control steps increases.
On a two stage thermostat, the dial setting indi-
cates the average leaving water temperature that
the control will maintain. At a 44F setting, the
high stage should actuate at approximately
5lF
return
water
and
41
F
leaving
based
on
10
cooling
ra
nge
.
The low stage will open at 46F return or
41F leaving
(5O
TD at 50% capacity).
Page
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30

McQuay Seasonpak PAB-020S Installation And Maintenance Data

Category
Split-system air conditioners
Type
Installation And Maintenance Data

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI