  • Hello! I am an AI chatbot trained to assist you with the Danfoss AKV 20 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
100 µ m
FIL
Warning
Never switch on power to the coil when the coil is dismounted
from the valve. Otherwise the coil may be damaged and there
is risk of injuries and burns.
Min 5% Ag
Installation Guide
Electrically Operated Expansion Valve
Type AKV 20
© Danfoss A/S (AC-MCI sw) 2013-04 DKRCC.PI.VA1.D3.53 / 520H7569 1
068R9523
068R9523
Clip-on coil
Max. 700 ºC
(1300 ºF)
Max. 150 ºC
(300 ºF)
On
O
FIL
100 μm
AKV 20
(en-gb) Do not insulate
(da) Må ikke isoleres
(de) Nicht isolieren
(fr) Ne pas isoler
(es) No encerrar para
evitar condensación
Media temperatur range: t
media
Min. -40 °C (-40 °F)
t
media
Max. 60 °C (140 °F)
Ambient temperatur range: t
amb
Min. -40 °C (-40 °F)
t
amb
Max. 50 °C (120 °F)
Refrigerants:
R744, R22/R407C, R404A/R507, R410A, R134a, R407A, R23.
For other refrigerants, please contactDanfoss.
Max. working pressure: PS/MWP = 28 barg (400 psig)
Max. test pressure: Pe = 31 barg (260 psig)
Max. dierential pressure: MOPD = P
1
- P
2
= 20 bar (290 psi)
= 1
= 2
= 3
= 4
= 5
Danfoss
42H33.14
2 DKRCC.PI.VA1.D3.53 / 520H7569 © Danfoss A/S (AC-MCI sw) 2013-04
en-gb da de fr es
The gasket must be
exchanged, if the valve
is dismantled.
Pakningen skal skiftes,
hvis ventilen adskilles.
Bei Zerlegung des
Ventils muß dieDichtung
ausgewechselt werden.
Changer le joint
chaque fois que la
vanne est démontée.
Es preciso cambiar la
junta si se desmonta la
válvula
75 Nm ± 5 Nm
12 Nm ± 2 Nm
AKV 20-1
AKV 20-2
AKV 20-3
AKV 20-4
AKV 20-5
AKV 20
/