Dell UPS 10000R User guide

Category
Uninterruptible power supplies (UPSs)
Type
User guide
Dellt Online Rack UPS
10 kW
User's Guide
DELL10KWOLHVUS, DELL10KWOLHV, DELL10KWOLHVB
DELL10KWEBM
w w w . d e l l . c o m | w w w . s u p p o r t . d e l l . c o m | w w w . d e l l u p s . c o m
Notes and Warnings
NOTE: A NOTE indicates important information that helps you make better use of your product.
CAUTION: A CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury or in property damage incidents.
WARNING: A WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or
injury.
DANGER: A DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
DANGER: Observe the following instruction to help prevent an imminently hazardous situation which, if not
avoided, will result in death or serious injury:
S The UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS
inside the UPS or EBM.
S This is Class A Interference Causing Equipment. In a residential environment, this product may cause
radio interference, in which case the user may be required to take additional measures.
Information in this document is subject to change without notice.
E 2012 Dell Inc. All rights reserved.
Reproduction in any manner whatsoever without the written permission of Dell Inc. is strictly forbidden.
Trademarks used in this text: Dell and the DELL logo are trademarks of Dell Inc.; National Electrical Code and NEC are registered
trademarks of National Fire Protection Association, Inc.; ENERGY STAR name is a registered trademark owned by the U.S. Environmental
Protection Agency.
Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their
products. Dell Inc. disclaims any proprietary interest in trademarks and trade names other than its own.
December 2012 • P-164000156 2
3
Table of Contents
|
Table of Contents
1 Introduction 6.....................................
Finding Information 8...............................................
2 Safety Warnings 9.................................
3 Installation 12......................................
Inspecting the Equipment 12..........................................
Unpacking the Cabinet 14............................................
Rackmount Setup 19................................................
Installing the UPS 25................................................
Connecting the EBM to the UPS 26.....................................
Installing Remote Emergency Power-off 26..............................
Hardwiring the UPS Input 28..........................................
UPS Initial Startup 32...............................................
UPS Rear Panels 34.................................................
4 Operation 37.......................................
UPS Startup and Shutdown 38.........................................
Starting the UPS 38..............................................
Starting the UPS on Battery 38.....................................
UPS Shutdown 39...............................................
Control Panel Functions 39...........................................
Changing the Language 40...........................................
Display Functions 41................................................
Startup Screen 41...............................................
Screen Locked 41...............................................
4
|
Table of Contents
Operating Modes 42.............................................
Active Notices and Alarms 44......................................
Battery Operating Status 44.......................................
Event Log 45...................................................
Measurements 46...............................................
Control Screens 47..............................................
Identification 48.................................................
Settings 48....................................................
Transferring the UPS Between Modes 53................................
Transferring from Normal to Bypass Mode 53..........................
Transferring from Bypass to Normal Mode 54..........................
Setting the Power Strategy 54.........................................
Retrieving the Event Log 56...........................................
Behavior on Overload 56.............................................
Configuring Load Segments 57........................................
Controlling Load Segments Through the Display 58.....................
Configuring Automatic Start Delay 58................................
Configuring Automatic on Battery Shutdown 59........................
Configuring Battery Settings 60........................................
Configuring the UPS for an EBM 60..................................
Running Automatic Battery Tests 61.................................
Configuring Automatic Battery Tests 61..............................
Configuring Automatic Restart 61......................................
5 Additional UPS Features 62...........................
RS-232 and USB Communication Ports 62................................
Dell UPS Network Management Card (Optional) 64........................
Environmental Monitoring Probe (Optional) 64............................
Dell MUMC and Dell ULNM Software 65................................
5
Table of Contents
|
6 UPS Maintenance 66................................
UPS and Battery Care 66.............................................
Transporting the UPS 66.............................................
Recharging and Replacing Batteries 71.................................
Testing Batteries 78................................................
Updating the UPS Firmware 78........................................
7 Specifications 79...................................
8 Troubleshooting 84..................................
Accessing Alarms and Conditions 84...................................
UPS Status Menu 84.............................................
Event Log Menu 85..............................................
Alarms, Notices, and Events 85........................................
Silencing the Alarm 92..............................................
6
|
Introduction
Introduction
The Dellt Online Rack uninterruptible power system (UPS) protects your sensitive electronic
equipment from basic power problems such as power failures, power sags, power surges, brownouts, and
line noise.
Power outages can occur when you least expect them and power quality can be erratic. These power
problems have the potential to corrupt critical data, destroy unsaved work sessions, and damage
hardware — causing hours of lost productivity and expensive repairs.
With the Dell Online Rack UPS, you can safely eliminate the effects of power disturbances and guard
the integrity of your equipment. The UPS provides flexibility to handle an array of network devices
makes it the perfect choice to protect your LANs, high density servers, blade chassis, and workstations as
well as other electrical equipment. The UPS becomes an ideal solution for cloud applications and a wide
range of virtualization implementations when the Dell Multi-UPS Management Console (MUMC) and
Dell UPS Local Node Manager (ULNM) are used to manage the UPS.
Figure 1 shows the Dell Online Rack 10 kW UPS.
Figure 1. The Dell Online Rack 10 kW UPS
1
7
Introduction
|
Providing outstanding performance and reliability, the UPS's unique benefits include:
S Online UPS design with pure sine wave output.
S True online double-conversion technology with high power density, utility frequency
independence, and generator compatibility.
S Buck and Boost voltage regulation that ensures regulated voltage to your load by correcting voltage
fluctuations.
S The UPS filters and regulates incoming AC power and provides consistent power to your
equipment without draining the battery.
S Selectable High Efficiency mode of operation.
S 5U UPS height.
S Start‐on‐battery capability for powering up the UPS even if utility power is not available.
S Maintenance is simplified by allowing the safe replacement of batteries without powering down the
UPS.
S Dell service tag information can be read from the front panel LCD display.
S Extended runtime with an optional External Battery Module (EBM).
S Emergency shutdown control through the Remote Emergency Power-off (REPO) ports.
S Two standard communication ports (USB and RS-232 serial port).
S Optional Dell UPS Network Management Card (also known as the NMC) with enhanced
communication capabilities for increased power protection and control.
S Optional Environmental Monitoring Probe (EMP) for collecting temperature and humidity
readings in the frame environment and monitoring the environmental data remotely. You can also
collect and retrieve the status of two user-provided contact devices.
S Advanced power management with the Dell MUMC and Dell ULNM Web-based software
applications for graceful shutdowns and power monitoring.
S Sequential shutdown and load management through separate receptacle groups called load
segments.
S Firmware that is easily upgradable without a service call.
S Backed by worldwide agency approvals.
S ENERGY STAR
®
certified UPSs.
8
|
Introduction
Finding Information
CAUTION: The Safety, Environmental, and Regulatory Information document provides important safety and
regulatory information.
What are You Looking For?
Find It Here
S The user's guide for my UPS
S The user's guide for the Dell UPS Network
Management Card
S Dell MUMC and Dell ULNM User's Guides
NOTE: Documentation and software updates can be
found at www.support.dell.com and at
www.dellups.com.
Dell UPS Disc
S Specifications
S How to configure UPS settings
S How to troubleshoot and solve problems
S How to install REPO control
Dell UPS User's Guide
The user's guide is available on the Dell UPS disc and
on www.support.dell.com.
S Safety instructions
S Regulatory information
S Recycling information
Safety, Environmental, and Regulatory Information
S Warranty information
S Terms and Conditions (U.S. only)
S End User License Agreement
Dell Warranty and Support Information
S Support information Dell Support Website — www.support.dell.com
NOTE: Select your region or business segment to view
the appropriate support site.
9
Safety Warnings
|
Safety Warnings
CAUTION: Before performing the procedures in this document, read and follow the safety instructions and
important regulatory information in your Safety, Environmental, and Regulatory Information document.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the equipment and
save this manual for future reference.
DANGER:
Observe the following instruction to help prevent an imminently hazardous situation which, if not
avoided, will result in death or serious injury:
S The UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE
PARTS inside the UPS or EBM.
WARNING:
Risk of electrical shock. Only qualified service personnel (such as a licensed electrician) shall
perform the electrical installation.
WARNING: Observe the following instructions to help prevent a potentially hazardous situation which, if not
avoided, could result in death or injury:
S The UPS outputs are protected against overcurrent by circuit breakers.
S This UPS contains its own energy source (batteries). The output receptacles may carry live voltage
even when the UPS is not connected to an AC supply.
S To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent
protection with an ampere rating in accordance with the National Electrical Code
®
(NEC
®
),
ANSI/NFPA 70 or your local electrical code:
UPS Output Power 200V 208V 230V
10 kW 63A (Europe) and 80A (North America and Japan)
2-pole circuit breaker
S To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature must not
exceed 40°C (104°F). Do not operate near water or excessive humidity (95% maximum).
S Unpacking the cabinet in a low-temperature environment may cause condensation to occur in and
on the cabinet. Do not install the cabinet until the inside and outside of the cabinet are absolutely
dry (hazard of electric shock).
2
10
|
Safety Warnings
S If the UPS requires any type of transportation, disconnect the internal UPS batteries before
transporting (see page 66).
CAUTION:
Observe the following instructions to help prevent a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury or in property damage incidents:
S Servicing of batteries should be performed or supervised by personnel knowledgeable about
batteries and the required precautions. Keep unauthorized personnel away from batteries.
S Batteries can present a risk of electrical shock or burn from high short-circuit current. The
following precautions should be observed: 1) Remove watches, rings, or other metal objects; 2) Use
tools with insulated handles; 3) Wear rubber gloves and boots; 4) Do not lay tools or metal parts on
top of batteries; 5) Disconnect the charging source prior to connecting or disconnecting battery
terminals.
S Determine if the battery is inadvertently grounded. If inadvertently grounded, remove the utility
source from the ground. Contact with any part of a grounded battery can result in electrical shock.
The likelihood of such shock can be reduced if such grounds are removed during installation and
maintenance (applicable to equipment and remote battery supplies not having a grounded supply
circuit).
S ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors.
Attempting to alter wiring can cause injury.
S Replace batteries with the same number and type of batteries as originally installed in the UPS.
S Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
S Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and
eyes and may be extremely toxic.
S The UPS may be connected to a maximum of one External Battery Module (EBM).
WARNING:
Additional instructions for Rack-Mounted Systems:
S Your rack kit has been approved only for the rack cabinet provided. It is your responsibility to
ensure that installation of the equipment into any other rack complies with all applicable
standards. Dell disclaims all liability and warranties with respect to combinations of equipment
with any other rack.
S Before installing your equipment in a rack, install all required stabilizers. Failure to install
stabilizers can allow the rack to tip over.
S Always load from the bottom up, and load the heaviest items first.
S Do not overload the AC power supply branch circuit that provides power to the rack.
S Do not stand or step on any components in the rack.
S When installing multiple systems in a rack, complete all of the procedures for the current system
before attempting to install the next system.
11
Safety Warnings
|
WARNING: Slide/rail mounted equipment is not to be used as a shelf or work space.
Do not add weight to slide/rail mounted equipment.
12
|
Installation
Installation
This chapter explains:
S Equipment inspection
S Unpacking the cabinet
S UPS rear panels
S UPS setup and installation, including the External Battery Module (EBM)
S Remote Emergency Power-off (REPO) installation
S Initial startup
NOTE:
Discard or recycle the packaging in a responsible manner, or store it for future use.
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping cartons and packing materials
for the carrier (see Figure 2) or place of purchase and file a claim for shipping damage. If you discover
damage after acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of
receipt of the equipment; 2) Send a copy of the damage claim within 15 days to your service
representative.
NOTE:
Check the battery recharge date on the shipping carton label. If the date has passed, do not use the
UPS. Contact your service representative.
3
13
Installation
|
Figure 2. Shipping Carton Contents
14
|
Installation
Unpacking the Cabinet
CAUTION: Unpacking the cabinet in a low-temperature environment may cause condensation to occur in and
on the cabinet. Do not install the cabinet until the inside and outside of the cabinet are absolutely dry (hazard
of electric shock).
CAUTION: Installing or removing the battery trays should be performed or supervised by personnel
knowledgeable about batteries and the required precautions. Keep unauthorized personnel away from
batteries.
CAUTION: The cabinet is heavy (see page 79): Always remove both battery trays from the UPS before lifting
the cabinet. Lifting the cabinet into the rack requires a minimum of two people.
CAUTION: The batteries are heavy (32 kg/71 lb). Use proper lifting techniques when removing the batteries.
NOTE: Use care when moving and opening the carton. Leave the components packaged until ready to install.
To unpack the system:
1 Using a forklift or pallet jack, move the shipping carton and pallet near the rack where you will
install the UPS (see Figure 3).
Figure 3. Lifting the Pallet with Shipping Carton
15
Installation
|
2 Detach and remove the outer carton (see Figure 4).
Figure 4. Detaching the Outer Carton
3 Remove the two accessory boxes tucked into the channels in the top Styrofoam section. Open the
accessory boxes and set them on a flat, stable surface nearby (see Figure 5).
NOTE:
The Dell Online Rack UPS 10 kW Getting Started Guide provides unpacking and installation procedures.
To refer to it, remove it from the accessory box before you set the accessory boxes aside.
Figure 5. Removing the Accessory Boxes
16
|
Installation
4 Remove the top Styrofoam section and set it on a flat, stable surface nearby (see Figure 6).
Figure 6. Removing the Top Styrofoam Section
NOTE: The battery retaining brackets are labeled L (left) and R (right) to indicate where they must be installed.
5 Remove both battery retaining brackets from the UPS (see Figure 7):
Locate the left (labeled L) retaining bracket. On the left side of the chassis, turn the thumbscrew
counter-clockwise to release the left retaining bracket.
Push the bracket toward the center post to disengage it from the chassis. Swing the bracket toward
you and pull the bracket to the left to remove it. Set the bracket aside.
Locate the right (labeled R) retaining bracket. On the right side of the chassis, turn the
thumbscrew counter-clockwise to release the right retaining bracket.
Push the bracket toward the center post to disengage it from the chassis. Swing the bracket toward
you and pull the bracket to the right to remove it. Set the bracket aside.
Figure 7. Removing the Battery Retaining Brackets
17
Installation
|
6 Ensure all battery connectors are disconnected.
CAUTION:
The batteries are heavy (32 kg/71 lb). Use proper lifting techniques when removing the batteries.
7 Remove the battery trays from the UPS (see Figure 8):
Move the disconnected UPS battery connectors at the top of the battery compartment out of the
way.
Grip the two plastic loop tabs on the front of the battery tray. Pull the tray toward you to remove.
NOTE:
The orange PULL HERE labels indicate where to grasp the loop tabs.
Set the battery tray on the Styrofoam section you removed from the top of the UPS.
Repeat with the second battery tray.
Figure 8. Removing the Battery Trays
18
|
Installation
CAUTION: The cabinet is heavy (46 kg/101 lb) with the batteries removed. Lifting the cabinet from the shipping
carton requires a minimum of two people.
8 With one person on each side, carefully lift the cabinet out of the styrofoam using the handles on
the cardboard (see Figure 9).
Figure 9. Lifting the Cabinet
9 Place the cabinet on a flat, stable surface in a protected area near the rack where you will install it.
NOTE:
Ensure that the area has adequate airflow and is free of humidity, flammable gas, and corrosion.
19
Installation
|
Rackmount Setup
CAUTION: The cabinet is heavy (see page 79): Always remove both battery trays from the UPS before lifting
the cabinet and installing the UPS on the rails in the rack. Lifting the cabinet into the rack requires a minimum
of two people.
CAUTION: Installing or removing the batteries should be performed or supervised by personnel
knowledgeable about batteries and the required precautions. Keep unauthorized personnel away from
batteries.
CAUTION: The batteries are heavy (32 kg/71 lb). Use proper lifting techniques when removing the batteries.
CAUTION: If installing an optional EBM, the EBM must be located below the UPS with no U space between
the UPS and EBM. This provides better weight distribution in the rack, easier access to the UPS control panel,
and easier routing for the battery cable connections. This also prevents strain between the EBM cord and the
UPS connection and possible connection failure.
WARNING: For Rack-Mounted Systems: When installing multiple systems in a rack, complete all of the
procedures for the current system before attempting to install the next system.
NOTE: Mounting rails are required for each individual cabinet.
NOTE: The cabinet is shipped without the front cover attached.
NOTE: The following instructions are the same for square-hole racks and unthreaded, round-hole racks. The
rails fit both rack styles.
To install the UPS in a rack:
1 Ensure that the following are placed on a flat, stable surface near the rack where you will install the
UPS:
S cabinet
S two accessory boxes
S two battery trays (UPS only)
S two battery retaining brackets (UPS only)
2 Remove the rails from the rail kit accessory box.
3 Select the proper holes in the rail for positioning the cabinet in the desired location in the rack.
Locate the rails at the bottom of the 5U space allocated for the UPS.
20
|
Installation
CAUTION: If installing an optional EBM, make provision for installing the EBM directly below the UPS with
no U space between the UPS and EBM.
4 Position the left and right rails as illustrated (see Figure 10).
NOTE:
Observe the labels on the rails for right front (labeled RIGHT FRONT) and left front (labeled LEFT
FRONT).
5 Attach the left and right rails to the rack:
Engage the back end of the rail until it fully seats on the vertical rack flange and the hook latch
locks in place (see Figure 10).
Pull the rail just past the front of the rack.
Push the front end of the rail until it fully seats on the vertical rack flange and the hook latch locks
in place.
Figure 10. Installing the Rails
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92

Dell UPS 10000R User guide

Category
Uninterruptible power supplies (UPSs)
Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI