Nortec
SAM-e
Engineering Manual
Includes technical specifications,
guidelines, and options for selection and
application of Nortec SAM-e and Nortec
Mini SAM-e Short Absorption Manifolds
1503529-H | 08/01/2020
Your guide to selecting and specifying Nortec SAM-e Short Absorption Manifolds!
Thank you for choosing Condair.
Proprietary Notice
This document and the information disclosed herein are proprietary data of Condair. Neither this document nor the
information contained herein shall be reproduced used, or disclosed to others without the written authorization of Condair.,
except to the extent required for installation or maintenance of recipient’s equipment. All references to the Condair name
should be taken as referring to Condair.
Liability Notice
Condair does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of
parts/components/equipment that are not authorized or approved by Condair.
Copyright Notice
Copyright 2020, Condair. All rights reserved.
Contents
1 General
1 Features
3 Determining the Steam
Absorption Distance
7 Static Air Pressure
7 Condensate Losses
8 Correct Choice of Product
Applications
15 Product Selection
16 Step 1 Header Selection
24 Step 2 Steam Tube Selection
27 Step 3 Nortec SAM-e Steam Inlet
Configuration Selection
30 Select Options
35 Installation Drawings
45 Specification
51 Appendix Inlet Adapter
Configurations
1 | Nortec SAM-e Engineering
Nortec Short Absorption Manifold (SAM-e)
The Nortec SAM-e is Condair’s best performing steam absorption system for use in Air Handling Units and duct
systems where short steam absorption distance is critical.
Precisely controlled clean steam is distributed uniformly into the air stream by the Nortec SAM-e without any
condensate spray. Steam distribution takes place via distributor tubes with integrated nozzles. The steam is
kept dry as condensate is drained through the main header.
The stainless steel distribution tubes are typically mounted vertically but may also be mounted horizontally (10º
slope) for vertical airflow applications. The distribution tubes come equipped with evenly-spaced stainless steel
nozzles, providing optimum steam distribution.
The nozzles extend into the center of the distribution tube ensuring only condensate-free steam is released.
Condensate drains out of the distribution tubes through the header, eliminating the need for jacketed tubes. A
permanent bond between the nozzle and distribution tube is made when the nozzle is pressed into the tube. The
nozzles and tubes have the same thermal expansion characteristics guaranteeing a permanent union. The
precise manufactured orifices ensure consistent output from each nozzle.
Features
Inlets/Outlets located on same side, one access point required.
All stainless steel distributors and nozzles ensure permanent bond.
Stainless steel header with rubber grommet seals for easy installation of distribution tubes.
Tubes available in 409 or 304 stainless steel to fit every budget.
Available with optional stainless steel insulating shielding for increased energy efficiency and
decreased condensate losses.
Adjustable mounting frame available for quick and easy installation.
Available with 3", 6", 9”, or 12” center to center distributor spacing – (Nortec SAM-e).
Available in 3” and 6” center to center distributor spacing - (Nortec Mini SAM-e).
Atmospheric or pressure steam source.
Ten-year limited warranty (two years on tube coupling seals).
Note: Nortec SAM-e Header / Separator assembly distributes the steam evenly along its length and
allows condensate to settle for easy removal through the trap.
Nortec SAM-e Engineering | 2
Figure 1: Nortec SAM-e
Figure 2: Cross-section of distributor pipe
3 | Nortec SAM-e Engineering
Determining the Steam Absorption Distance
A certain amount of time is required for complete absorption when injecting steam into the air.
During this time, steam moves a fixed distance from the distribution manifold before it is fully absorbed into a
moving air stream.
The absorption distance is the distance required for steam to be fully absorbed by the airstream. Identifying this
distance is essential to ensure that unabsorbed steam does not condense on downstream components.
The system should be designed to eliminate the possibility of wetting internal components by positioning the
manifold in an optimum location and by maximizing the available distance for steam absorption.
Shorter absorption is not always desirable. Sizing a Nortec SAM-e to produce unnecessarily short absorption
distances may result in increased condensate losses and require a larger humidifier to compensate. It is
important to balance available absorption distance with Nortec SAM-e
capacity.
Additional Information
Data is based on velocities between 200 fpm (1 m/s) and 2500 fpm (12.7 m/s).
Available absorption distance: the distance between Nortec SAM-e and first obstruction (coil, elbow, damper,
etc.) that steam may contact. Traces of steam may pass this obstruction, but will not condense, leaving
obstructions dry.
Absorption distance is a function of various conditions including; duct temperature, duct humidity level, duct
static pressure, and air flow rate. Changes in duct geometry, flow rates, or flow conditions will require
recalculating Nortec SAM-e performance. It is always recommended to size Nortec SAM-e
to “worst case”
conditions.
Note: Visit www.condair.com to download our Humidification Engineering & Loadsizing Program
(H.E.L.P.) to help calculate absorption distances.
Nortec SAM-e Engineering | 4
Static Air Pressure
Table 1 shows the static pressure loss created by a Nortec SAM-e in various velocities.
Table 1: Air Pressure Loss in AHU / Duct
Air Velocity
[ fpm (m/s) ]
Air Pressure Loss [ in(mm) of water column ]
Nortec SAM-e
Tube Spacing
3” (762 mm) 6” (152 mm) 9” (229 mm) 12” (305 mm)
500 (2.5) 0.01 (0.3) 0.01 (0.3)
No measurable data
750 (3.8) 0.03 (0.8) 0.01 (0.3)
1000 (5.1) 0.05 (1.3) 0.02 (0.5)
1250 (6.4) 0.07 (1.8) 0.03 (0.8)
1500 (7.6) 0.09 (2.3) 0.04 (1.0) 0.01 (0.3) 0.01 (0.3)
1750 (8.9) 0.10 (2.5) 0.06 (1.5) 0.01 (0.3) 0.01 (0.3)
2000 (10.2) 0.12 (3.0) 0.08 (2.0) 0.01 (0.3) 0.01 (0.3)
Condensate Losses
Some of the steam generated by Condair humidifiers will condense due to Nortec SAM-e. To compensate for
this loss in capacity, calculated humidification load must be increased accordingly. Please refer to Table 2.
Condair recommends the installation of a condensate drain on the steam-line run prior to entering the
Nortec SAM-e. This will prevent condensate from the lines from entering the Nortec SAM-e.
Table 2: Condensate Loss for Un-insulated Nortec SAM-e
Air Velocity
[ fpm (m/s) ]
Condensate Losses [ % of Maximum Capacity ]
Atmospheric Steam Pressurized Steam
55ºF (13°C) 70ºF (21°C) 55ºF (13°C) 70ºF (21°C)
500 (2.5) 15% 12% 8% 5%
1000 (5.1) 20% 15% 10% 7%
Note: These values may increase or decrease due to many unknown conditions or
variables. This is only a guideline.
5 | Nortec SAM-e Engineering
The Nortec SAM-e is available with optional stainless steel insulation for headers and tubes. Insulation is
desirable to reduce air-stream heat gain, reduce condensate losses, and improve energy efficiency. Please refer
to Table 3 when estimating condensate losses with insulated Nortec SAM-e’s.
Table 3: Condensate Loss for Insulated Nortec SAM-e
Air
Velocity
[ fpm (m/s) ]
Condensate Losses [ % of Maximum Capacity ]
Atmospheric Steam
Pressurized Steam
55ºF (13°C) 70ºF (21°C) 55ºF (13°C) 70ºF (21°C)
500 (2.5) 5% 4% 6% 3%
1000 (5.1) 10% 8% 8% 5%
Correct Choice of Product Applications (within Nortec SAM-e)
The Nortec SAM-e has been designed exclusively for use in building ventilation duct systems where short
absorption is critical. Condair offers various humidification technologies to suit virtually all applications and can
recommend the most appropriate system for each case.
Note: These values may increase or decrease due to many unknown conditions or variables. This is only a
guideline.
Nortec SAM-e Engineering | 6
Figure 3: General Nortec SAM-e Dimensions
7 | Nortec SAM-e Engineering
Table 4: Nortec SAM-e DimensionsWidth
Duct Width
Dimension A
Frame Width - Bottom
Dimension B
Frame Width - Top
Dimension C
Header Assembly Width
in
mm
mm
in
mm
in
mm
18
457
333
14.9
378
16.3
413
24
610
486
20.9
530
22.3
57
30
762
638
26.9
683
28.3
72
36
914
791
32.9
835
34.3
87
42
1067
943
38.9
987
40.3
102
48
1219
1095
44.9
1140
46.3
117
54
1372
1248
50.9
1292
52.3
133
60
1524
1400
56.9
1445
58.3
148
66
1676
1553
62.9
1597
64.3
163
72
1829
1705
68.9
1749
70.3
178
78
1981
1857
74.9
1902
76.3
194
84
2134
2010
80.9
2054
82.3
209
90
2286
2162
86.9
2207
88.3
224
96
2438
2315
92.9
2359
94.3
239
102
2591
2467
98.9
2511
100.3
255
108
2743
2619
104.9
2664
106.3
270
114
2896
2772
110.9
2816
112.3
285
120
3048
2924
116.9
2969
118.3
300
126
3200
3077
122.9
3121
124.3
316
132
3353
3229
128.9
3273
130.3
331
138
3505
3381
134.9
3426
136.3
346
144
3658
3534
140.9
3578
142.3
361
Nortec SAM-e Engineering | 8
Table 5: Nortec SAM-e DimensionsHeight
Duct Height
Dimension D
Steam Tube Height
Dimension E Min.
Minimum Overall Height
Dimension E Max.
Maximum Overall Height
in
mm
in
mm
in
mm
in
mm
18
457
5.5
140
17
432
24.7
627
24
610
11.5
292
23
584
30.7
779
30
762
17.5
445
29
737
36.7
931
36
914
23.5
597
35
889
42.7
1084
42
1067
29.5
749
41
1041
48.7
1236
48
1219
35.5
902
47
1194
54.7
1389
54
1372
41.5
1054
53
1346
60.7
1541
60
1524
47.5
1207
59
1499
66.7
1693
66
1676
53.5
1359
65
1651
72.7
1846
72
1829
59.5
1511
71
1803
78.7
1998
78
1981
65.5
1664
77
1956
84.7
2151
84
2134
71.5
1816
83
2108
90.7
2303
90
2286
77.5
1969
89
2261
96.7
2455
96
2438
83.5
2121
95
2413
102.7
2608
102
2591
89.5
2273
101
2565
108.7
2760
108
2743
95.5
2426
107
2718
114.7
2913
114
2896
101.5
2578
113
2870
120.7
3065
120
3048
107.5
2731
119
3023
126.7
3217
126
3200
113.5
2883
125
3175
132.7
3370
132
3353
119.5
3035
131
3327
138.7
3522
138
3505
125.5
3188
137
3480
144.7
3675
144
3658
131.5
3340
143
3632
150.7
3827
9 | Nortec SAM-e Engineering
Figure 4: General Nortec Mini SAM-e Dimensions
Nortec SAM-e Engineering | 10
Table 6: Nortec Mini SAM-e DimensionsWidth
Duct Width
Dimension A
Nortec Mini SAM-e Width
in
mm
in
mm
12
305
11.1
281
18
457
17.1
433
24
610
23.1
586
Table 7: Nortec Mini SAM-e DimensionsHeight
Duct Height
Dimension B
Nortec Mini SAM-e Height
Dimension C
Mini Steam Tube Height
in
mm
in
mm
in
mm
8
203
7.9
200
4.4
113
10
254
9.9
251
6.4
164
12
305
11.9
302
8.4
214
14
356
13.9
352
10.4
265
16
406
15.9
403
12.4
316
18
457
17.9
454
14.4
367
20
508
19.9
505
16.4
418
22
559
21.9
556
18.4
468
24
610
23.9
606
20.4
519
11 | Nortec SAM-e Engineering
Product Selection
Nortec SAM-e Engineering | 12
Step 1 Nortec SAM-e Header Selection
Condair offers a ranges of manifolds to cover various capacities and duct sizes. The absorption distance and
capacity required determines the center-to-center spacing between each steam tube. There are four options: 3”
(76 mm) or 6” (152 mm) or 9” (229 mm) or 12” (305 mm). Nortec Mini SAM-e’s are only available with 3” and
6” spacing. The smaller the spacing, the more tubes the header can accommodate, thus giving a better
absorption distance and greater capacity, but at the cost of higher condensate losses.
The header / separator remain the same for atmospheric or pressurized steam, and for vertical or horizontal
flow applications.
Atmospheric manifolds with a capacity over 801 lb/hr (362 kg/hr) include a second steam inlet on the header.
Consult factory submittal drawings for specific details.
Select the header part number associated with your duct or air handling unit’s width.
For example, if duct width is 80” (2032 mm), select part number 1503279 for 3” (76 mm) center-to-center
spacing.
Some smaller duct sizes are too small to accommodate a full-size Nortec SAM-e, and a Nortec Mini SAM-e must
be used. As a rule-of-thumb, when duct width is less than 30” (762mm), a Nortec Mini SAM-e is the best choice.
Air Handling Unit (AHU) Installation
In some LiveSteam installations where there is no available room to install steam components such as F&T
traps, separator, etc., a stand may be ordered. Stands are available in 12- or 20- inch heights, and allow traps
and components to be installed in the duct along with the Nortec SAM-e. If a stand is required, the overall
height of the Nortec SAM-e must be reduced by the height of the selected stand. This enables proper steam tube
selection. Nortec SAM-e width must also be reduced to allow components to fit in the duct beside the Nortec
SAM-e. Please refer to LiveSteam Engineering Manual for component sizes.
Table 8: Nortec SAM-e Stand Kits
Dimension A
[ in (mm) ]
Part Number
12" (305) 1509947
20" (508) 1509948
Note: Refer to Nortec SAM-e submittal drawings for more information. All stand kits are complete with
both left and right stands and required fasteners.
13 | Nortec SAM-e Engineering
Figure 5: Header / Separator Assembly
Figure 6: Nortec SAM-e Stand
Nortec SAM-e Engineering | 14
Table 9: Nortec SAM-e Header / Separator Assembly, Atmospheric Steam – 3” Centers
ATMOSPHERIC STEAM3” HEADERS
Duct Width
[ in (mm) ]
Steam
Tube Qty
Header
Part Number
Maximum Capacity Atmospheric Steam [ lb/hr (kg/hr) ]
Type A
Type B
Type B+
Type C
18 (457)
3
1503269
45 (20)
105 (48)
165 (75)
225 (102)
24 (610)
5
1503270
75 (34)
175 (79)
275 (125)
375 (170)
30 (762)
7
1503271
105 (48)
245 (111)
385 (175)
525 (238)
36 (914)
9
1503272
135 (61)
315 (143)
495 (225)
675 (306)
42 (1067)
11
1503273
165 (75)
385 (174)
605 (274)
800 (363)
Double Inlet
1503291
-
-
825 (374)
48 (1219)
13
1503274
195 (88)
455 (206)
715 (324)
800 (363)
Double Inlet
1503292
-
-
-
975 (442)
54 (1372)
15
1503275
225 (102)
525 (238)
800 (363)
-
Double Inlet
1503293
-
-
825 (374)
1125 (510)
60 (1524)
17
1503276
255 (116)
595 (270)
800 (363)
-
Double Inlet
1503294
-
-
935 (424)
1200 (544)
66 (1676)
19
1503277
285 (129)
665 (301)
800 (363)
-
Double Inlet
1503295
-
-
1045 (474)
1200 (544)
72 (1829)
21
1503278
315 (143)
735 (333)
800 (363)
-
Double Inlet
1503296
-
-
1155 (524)
1200 (544)
78 (1981)
23
1503279
345 (156)
800 (363)
-
-
Double Inlet
1503297
-
805 (365)
1200 (544)
-
84 (2134)
25
1503280
375 (170)
800 (363)
-
-
Double Inlet
1503298
-
875 (396)
1200 (544)
-
90 (2286)
27
1503281
405 (183)
800 (363)
-
-
Double Inlet
1503299
-
945 (428)
1200 (544)
-
96 (2438)
29
1503282
435 (197)
800 (363)
-
-
Double Inlet
1503300
-
1015 (460)
1200 (544)
-
102 (2591)
31
1503283
465 (211)
800 (363)
-
-
Double Inlet
1503301
-
1085 (492)
1200 (544)
-
108 (2743)
33
1503284
495 (224)
800 (363)
-
-
Double Inlet
1503302
-
1155 (523)
1200 (544)
-
114 (3048)
35
1503285
525 (238)
800 (363)
-
-
Double Inlet
1503303
-
1200 (544)
-
-
120 (3048)
37
1503286
555 (251)
800 (363)
-
-
Double Inlet
1503304
-
1200 (544)
-
-
126 (3200)
39
1503287
585 (265)
800 (363)
-
-
Double Inlet
1503305
-
1200 (544)
-
-
132 (3353)
41
1503288
615 (279)
800 (363)
-
-
Double Inlet
1503306
-
1200 (544)
-
-
138 (3505)
43
1503289
645 (292)
800 (363)
-
-
Double Inlet
1503307
-
1200 (544)
-
-
144 (3658)
45
1503290
675 (306)
800 (363)
-
-
Double Inlet
1503308
-
1200 (544)
-
-
144+
36 8
Consult Factory
15 | Nortec SAM-e Engineering
Table 10: Nortec SAM-e Header / Separator Assembly, Pressure Steam – 3” Centers
PRESSURE STEAM3” Headers
Duct Width
[ in (mm) ]
Steam Tube
Qty
Header
Part Number
Maximum Capacity Pressure Steam [ lb/hr (kg/hr) ]
Type A
Type B
Type B+
Type C
18 (457)
3
1503269
45 (20)
105 (48)
165 (75)
225 (102)
24 (610)
5
1503270
75 (34)
175 (79)
275 (125)
375 (170)
30 (762)
7
1503271
105 (48)
245 (111)
385 (175)
525 (238)
36 (914)
9
1503272
135 (61)
315 (143)
495 (225)
675 (306)
42 (1067)
11
1503273
165 (75)
385 (174)
605 (274)
825 (374)
48 (1219)
13
1503274
195 (88)
455 (206)
715 (324)
975 (442)
54 (1372)
15
1503275
225 (102)
525 (238)
825 (374)
1125 (510)
60 (1524)
17
1503276
255 (116)
595 (270)
935 (424)
1275 (578)
66 (1676)
19
1503277
285 (129)
665 (301)
1045 (474)
1425 (646)
72 (1829)
21
1503278
315 (143)
735 (333)
1155 (524)
1575 (713)
78 (1981)
23
1503279
345 (156)
805 (365)
1265 (574)
1745 (790)
84 (2134)
25
1503280
375 (170)
875 (396)
1375 (624)
1875 (849)
90 (2286)
27
1503281
405 (183)
945 (428)
1485 (674)
2025 (917)
96 (2438)
29
1503282
435 (197)
1015 (460)
1595 (723)
2175 (985)
102 (2591)
31
1503283
465 (211)
1085 (492)
1705 (773)
2325 (1053)
108 (2743)
33
1503284
495 (224)
1155 (523)
1815 (823)
2475 (1121)
114 (3048)
35
1503285
525 (238)
1225 (555)
1925 (873)
2625 (1189)
120 (3048)
37
1503286
555 (251)
1295 (587)
2035 (923)
2775 (1257)
126 (3200)
39
1503287
585 (265)
1365 (618)
2145 (973)
2925 (1325)
132 (3353)
41
1503288
615 (279)
1435 (650)
2255 (1023)
3075 (1393)
138 (3505)
43
1503289
645 (292)
1505 (682)
2365 (1073)
3200 (1450)
144 (3658)
45
1503290
675 (306)
1575 (713)
2475 (1123)
3200 (1450)
144+ (3658+)
Consult Factory
Nortec SAM-e Engineering | 16
Table 11: Nortec SAM-e Header / Separator Assembly, Atmospheric Steam – 6” Centers
ATMOSPHERIC STEAM6” HEADERS
Duct Width
[ in (mm) ]
Steam
Tube Qty
Header
Part Number
Maximum Capacity Atmospheric Steam [ lb/hr (kg/hr) ]
Type A
Type B
Type B+
Type C
18 (457)
2
1503309
30 (14)
70 (32)
110 (50)
150 (68)
24 (610)
3
1503310
45 (20)
105 (48)
165 (75)
225 (102)
30 (762)
4
1503311
60 (27)
140 (63)
220 (100)
300 (136)
36 (914)
5
1503312
75 (34)
175 (79)
275 (125)
375 (170)
42 (1067)
6
1503313
90 (41)
210 (95)
330 (150)
450 (204)
48 (1219)
7
1503314
105 (48)
245 (111)
385 (175)
525 (238)
54 (1372)
8
1503315
120 (54)
280 (127)
440 (200)
600 (272)
60 (1524)
9
1503316
135 (61)
315 (143)
495 (225)
675 (306)
66 (1676)
10
1503317
150 (68)
350 (159)
550 (249)
750 (340)
72 (1829)
11
1503318
165 (75)
385 (174)
605 (274)
800 (363)
Double Inlet
1503331
-
-
-
825 (374)
78 (1981)
12
1503319
180 (82)
420 (190)
660 (299)
800 (363)
Double Inlet
1503332
-
-
-
900 (408)
84 (2134)
13
1503320
195 (88)
455 (206)
715 (324)
800 (363)
Double Inlet
1503333
-
-
975 (442)
90 (2286)
14
1503321
210 (95)
490 (222)
770 (349)
800 (363)
Double Inlet
1503334
-
-
-
1050 (476)
96 (2438)
15
1503322
225 (102)
525 (238)
800 (363)
-
Double Inlet
1503335
-
-
825 (374)
1125 (510)
102 (2591)
16
1503323
240 (109)
560 (254)
800 (363)
-
Double Inlet
1503336
-
-
880 (399)
1200 (544)
108 (2743)
17
1503324
255 (116)
595 (270)
800 (363)
-
Double Inlet
1503337
-
-
935 (424)
1200 (544)
114 (3048)
18
1503325
270 (122)
630 (271)
800 (363)
-
Double Inlet
1503338
-
-
990 (449)
1200 (544)
120 (3048)
19
1503326
285 (129)
665 (301)
800 (363)
-
Double Inlet
1503339
-
-
1045 (474)
1200 (544)
126 (3200)
20
1503327
300 (136)
700 (317)
800 (363)
-
Double Inlet
1503340
-
-
1100 (499)
1200 (544)
132 (3353)
21
1503328
315 (143)
735 (333)
800 (363)
-
Double Inlet
1503341
-
-
1155 (524)
1200 (544)
138 (3505)
22
1503329
330 (149)
770 (349)
800 (363)
-
Double Inlet
1503342
-
-
1200 (544)
-
144 (3658)
23
1503330
345 (156)
805 (365)
800 (363)
-
Double Inlet
1503343
-
-
1200 (544)
-
144+ (3658+)
Consult Factory
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89

Condair SAM-e Engineering User manual

Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI