17Operator Interface
Nortec EL
2582954_D_EN_1811_Nortec-EL_OM
Message Description
Keep Warm The humidiî‚¿er is in standby mode, and the keep warm function is activated.
Disabled The Nortec EL humidiî‚¿er is disabled by the BMS (building management
system).
Stopped The humidiî‚¿er is stopped because a condition with a "Fault" status is
active.
Safety Loop One or more contacts in the external safety loop is open, so the humidiî‚¿er
has stopped producing steam.
Blower Pack The blower pack input signal to the humidiî‚¿er is open. The humidiî‚¿er will
not produce steam.
Warning A condition with a "Warning" status is active. In addition, the message
"Warning" is shown in the maintenance/fault status area of the Home
screen. The humidiî‚¿er will continue to produce steam when there is a
demand (unless the warning relates to a control signal).
Fault A condition with a "Fault" status is active. The humidiî‚¿er is stopped. In ad-
dition, the message "Fault" is shown in the maintenance/fault status area
of the Home screen.
Table 3: Status Icon Descriptions
Icon Description
The icon appears to the left of the operating status message or the main-
tenance/fault message when the system is working normally.
The icon appears to the left of the maintenance/fault status message
when a maintenance reminder or a condition with a "Warning" status is
active. The humidiî‚¿er will continue to produce steam when there is a
demand (unless the warning relates to a control signal).
The icon shown appears to the left of the maintenance/fault status mes-
sage when a condition with a "Fault" status is active. The humidiî‚¿er stops
producing steam.
4.2.4 Maintenance and Fault Status
The Service/Warning/Fault status area of the Home screen (refer to Figure 5 on page 15) shows mainte-
nance reminders, maintenance and fault status messages along with associated status icons. This î‚¿eld
also allows access to the "Service Menu". When a maintenance reminder, warning or fault status message
is active, the Fault History list can be accessed directly from this î‚¿eld to view additional details.
The general maintenance reminders and alarm messages displayed in this area are described in Table 4,
and the status icons are described in Table 3. Refer to "Warning and Fault List" on page 78 for a detailed list
of warning and fault messages.
Table 4: Maintenance/Fault Status Descriptions
Message Description
Service info No faults conditions present.
Cylinder Spent This message appears if the control software has detected that the steam
cylinder is î‚¿lled with scale and can no longer achieve the required output.
If the steam cylinder is not replaced, and the maintenance cylinder is not
reset within 72 hours (run time), a corresponding fault message appears.
Replace the steam cylinder, then reset the maintenance cylinder in the
Service menu. Refer to "Removal and Installation of Steam Cylinder" on page 66.