Function block SPA address CNT_VAL SPA address NEW_VAL
PCFCNT:10 6-O-2842 6-O-2841
PCFCNT:11 6-O-2848 6-O-2847
PCFCNT:12 6-O-2854 6-O-2853
PCFCNT:13 6-O-2860 6-O-2859
PCFCNT:14 6-O-2866 6-O-2865
PCFCNT:15 6-O-2872 6-O-2871
PCFCNT:16 6-O-2878 6-O-2877
3.1.2.1 I/O modules
M11880-16 v4
To read binary inputs, the SPA-addresses for the outputs of the I/O-module
function block are used, that is, the addresses for BI1 – BI16. For SPA addresses,
refer to section Related documents in Product Guide.
M11880-35 v1
3.1.2.2 Single command, 16 signals
M11880-51 v5
The IEDs can be provided with a function to receive signals either from a
substation automation system or from the local HMI. That receiving function block
has 16 outputs that can be used, for example, to control high voltage apparatuses in
switchyards. For local control functions, the local HMI can also be used.
The single command, 16 signals function consists of four function blocks:
SINGLECMD:1 to SINGLECMD:4 for 16 binary output signals each.
The signals can be individually controlled from the operator station, remote-control
gateway, or from the local HMI on the IED. For Single command, 3 signals
function block, SINGLECMD:1 to SINGLECMD:3, the address is for the first
output. The other outputs follow consecutively after the first one. For example,
output 7 on the SINGLECMD:2 function block has the 5O533 address.
The SPA addresses for Single command, 16 signals functions SINGLECMD:1 to
SINGLECMD:4 are found in table
2.
Table 2: SPA addresses for SINGLECMD function
Function block
SPA address CMD Input SPA address CMD output
SINGLECMD1-Cmd1 4-S-4639 5-O-511
SINGLECMD1-Cmd2 4-S-4640 5-O-512
SINGLECMD1-Cmd3 4-S-4641 5-O-513
SINGLECMD1-Cmd4 4-S-4642 5-O-514
SINGLECMD1-Cmd5 4-S-4643 5-O-515
SINGLECMD1-Cmd6 4-S-4644 5-O-516
SINGLECMD1-Cmd7 4-S-4645 5-O-517
SINGLECMD1-Cmd8 4-S-4646 5-O-518
Table continues on next page
Section 3 1MRK 511 418-UEN A
SPA operation principle
14 650 series 2.2 IEC
Communication protocol manual